HomeMy WebLinkAbout2022-01-18 1010 BURWELL ST - PermitsCostumer: BFS - Fife
Contact: Mike Hughes
Email: Mike.Hughes@BLDR.com
Phone: (253) 405-5148
Date: 01/18/2022
Job Name: 1010 Apartments
Job Address: 1010 Burwell Street
City: Bremerton, WA
Joist: 11-7/8" BCI 5000
Loading: 40psf LL / 10psf DL
Spacing: 16" oc
A total of (10) scenarios of penetrations in close
proximity of bearing ends and with close spacing
conditions of penetrations are presented in the
following descriptions. Each condition is addressed
as to the amount of reinforcing required per the
attached (3) detailed reinforcing conditions. See the
following descriptions for locations of each
reinforcement condition required.
01/18/2022
This condition requires
web reinforcing per the
attached "DETAIL - A"
This condition requires
web reinforcing per the
attached "DETAIL - B"
This condition requires
web reinforcing per the
attached "DETAIL - A"
These penetrations do
not require additional
reinforcing.
These penetrations do
not require additional
reinforcing.
SCENARIO
01
SCENARIO
02
SCENARIO
03
01/18/2022
This condition requires
web reinforcing per the
attached "DETAIL - A"
These penetrations do
not require additional
reinforcing.
This penetration does
not require additional
reinforcing.
SCENARIO
04
SCENARIO
05
01/18/2022
SCENARIO
06
SCENARIO
07
This condition requires
web reinforcing per the
attached "DETAIL - A"
These penetrations do
not require additional
reinforcing.
These penetrations do
not require additional
reinforcing.
01/18/2022
SCENARIO
08
SCENARIO
09
SCENARIO
10
These penetrations do
not require additional
reinforcing.
This condition requires
web reinforcing per the
attached "DETAIL - D"
This condition requires
web reinforcing per the
attached "DETAIL - C"
01/18/2022
1'-6"Min. Repair/Reinforcement Detail [R-7] Web Restoration Page 1 of 1 r03/14 NOTE: This certification is for an individual building component only and not for the building system as a whole. The component design as shown is based upon loading and dimensions provided by others. The project’s design professional of record is responsible for determining that the dimensions and loads for the component match those required by the structural plans and by the actual end use of the component. Verification of framing methods, bracing design, support conditions, connections, etc. is the responsibility of the project’s design professional of record. THIS REPAIR VALID ONLY FOR THE BOISE CASCADE ENGINEERED WOOD PRODUCT LISTED ABOVE.Clinched NailsInstallation Notes:1) Apply construction adhesive to cover all contact surface area.2) Install reinforcement tight to top of bottom flange.3) Nail reinforcement with 3 rows 10d nails at 4"c.c. or #8 wood screws. Provide a staggered placement as shown above. Clinch nails on opposite side of web.Costumer: BFS - FifeContact: Mike HughesEmail: Mike.Hughes@BLDR.comPhone: (253) 405-5148Date: 01/18/2022Job Name: 1010 ApartmentsJob Address: 1010 Burwell StreetCity: Bremerton, WAJoist: 11-7/8" BCI 5000Loading: 40psf LL / 10psf DLSpacing: 16" ocDETAIL - AWebReinforcingExisting HolesExisting holes to bemaintained throughthe web reinforcingProvide new 23/32" x 18" ratedply/OSB, one side of web. Cut to fitaround hole with face grain horizontal. Center splice about the centerline ofhole. Apply construction adhesive tocover all contact surface area .6"Min.
Repair/Reinforcement Detail [R-7] Web Restoration Page 1 of 1 r03/14 NOTE: This certification is for an individual building component only and not for the building system as a whole. The component design as shown is based upon loading and dimensions provided by others. The project’s design professional of record is responsible for determining that the dimensions and loads for the component match those required by the structural plans and by the actual end use of the component. Verification of framing methods, bracing design, support conditions, connections, etc. is the responsibility of the project’s design professional of record. THIS REPAIR VALID ONLY FOR THE BOISE CASCADE ENGINEERED WOOD PRODUCT LISTED ABOVE.Clinched NailsExisting HolesWebReinforcingInstallation Notes:1) Apply construction adhesive to cover all contact surface area.2) Install reinforcement tight to top of bottom flange.3) Nail reinforcement with 3 rows 10d nails at 4"c.c. or #8 wood screws. Provide a staggered placement as shown above. Clinch nails on opposite side of web.Costumer: BFS - FifeContact: Mike HughesEmail: Mike.Hughes@BLDR.comPhone: (253) 405-5148Date: 01/18/2022Job Name: 1010 ApartmentsJob Address: 1010 Burwell StreetCity: Bremerton, WAJoist: 11-7/8" BCI 5000Loading: 40psf LL / 10psf DLSpacing: 16" ocDETAIL - BExisting holes to bemaintained throughthe web reinforcingProvide new 23/32"rated ply/OSB, onone side of web. Cut to fit around holewith face grain horizontal. Applyconstruction adhesive to cover allcontact surface area. 3" Min.
[R-7] Web Restoration Page 1 of 1 r03/14 Repair/Reinforcement Detail Section A-AClinched NailsNOTE: This certification is for an individual building component only and not for the building system as a whole. The component design as shown is based upon loading and dimensions provided by others. The project’s design professional of record is responsible for determining that the dimensions and loads for the component match those required by the structural plans and by the actual end use of the component. Verification of framing methods, bracing design, support conditions, connections, etc. is the responsibility of the project’s design professional of record. THIS REPAIR VALID ONLY FOR THE BOISE CASCADE ENGINEERED WOOD PRODUCT LISTED ABOVE.Web Hole1/8" to 1/4"Gap2'-0"Existing web holepenetrationExisting web holepenetration3/4" Ply/OSB Reinforcementcentered at the penetration onone side of joist, cut to fit aroundexisting mechanical/electrical asshown2'-0"AAOverlap 2"Min Beyond Edgeof HoleInstallation Notes:1) Apply construction adhesive to cover all contact surface area.2) Install reinforcement tight to top of bottom flange.3) Nail reinforcement with 3 rows 10d nails at 4"c.c. or #8 wood screws. Provide a staggered placement as shown above. Clinch nails on opposite side of web.Costumer: BFS - FifeContact: Mike HughesEmail: Mike.Hughes@BLDR.comPhone: (253) 405-5148Date: 01/18/2022Job Name: 1010 ApartmentsJob Address: 1010 Burwell StreetCity: Bremerton, WAJoist: 11-7/8" BCI 5000Loading: 40psf LL / 10psf DLSpacing: 16" ocDETAIL - C
[R-7] Web Restoration Page 1 of 1 r03/14 Repair/Reinforcement Detail 1'-6"Section A-AClinched NailsAANOTE: This certification is for an individual building component only and not for the building system as a whole. The component design as shown is based upon loading and dimensions provided by others. The project’s design professional of record is responsible for determining that the dimensions and loads for the component match those required by the structural plans and by the actual end use of the component. Verification of framing methods, bracing design, support conditions, connections, etc. is the responsibility of the project’s design professional of record. THIS REPAIR VALID ONLY FOR THE BOISE CASCADE ENGINEERED WOOD PRODUCT LISTED ABOVE.Web Hole3/4" Ply/OSB Reinforcement oneach side of joist, cut to fit aroundexisting mechanical/electrical asshownDETAIL - DCostumer: BFS - FifeContact: Mike HughesEmail: Mike.Hughes@BLDR.comPhone: (253) 405-5148Date: 01/18/2022Job Name: 1010 ApartmentsJob Address: 1010 Burwell StreetCity: Bremerton, WAJoist: 11-7/8" BCI 5000Loading: 40psf LL / 10psf DLSpacing: 16" ocInstallation Notes:1) Apply construction adhesive to cover all contact surface area.2) Install reinforcement tight to top of bottom flange.3) Nail reinforcement with 3 rows 10d nails at 4"c.c. or #8 wood screws. Provide a staggered placement as shown above. Clinch nails on opposite side of web.1/8" to 1/4"GapWeb HolePenetration
This condition requires
web reinforcing per the
attached "DETAIL - A"
SCENARIO
01
01/18/2022
This certification is for a Boise Cascade
individual building component only and
not for the building system as a whole.
The component design as shown on this
report is based upon loadings and
dimensions provided by others. Building
designer is responsible for determining
that the dimensions and loads for each
component match those required by the
plans and by the actual end use of the
component. Verification of framing
methods, bracing design, support
conditions, connections, etc. is the
responsibility of the building designer.
SCENARIO
01
This penetration requires
web reinforcing per the
attached "DETAIL - B"
These penetrations do
not require web
reinforcing
SCENARIO
02
01/18/2022
This certification is for a Boise Cascade
individual building component only and
not for the building system as a whole.
The component design as shown on this
report is based upon loadings and
dimensions provided by others. Building
designer is responsible for determining
that the dimensions and loads for each
component match those required by the
plans and by the actual end use of the
component. Verification of framing
methods, bracing design, support
conditions, connections, etc. is the
responsibility of the building designer.
SCENARIO
02
This penetration requires
web reinforcing per the
attached "DETAIL - A"
These penetrations do
not require web
reinforcing
SCENARIO
03
01/18/2022
This certification is for a Boise Cascade
individual building component only and
not for the building system as a whole.
The component design as shown on
this report is based upon loadings and
dimensions provided by others. Building
designer is responsible for determining
that the dimensions and loads for each
component match those required by the
plans and by the actual end use of the
component. Verification of framing
methods, bracing design, support
conditions, connections, etc. is the
responsibility of the building designer.
SCENARIO
03
This penetration requires
web reinforcing per the
attached "DETAIL - A"
These penetrations do
not require web
reinforcing
SCENARIO
04
01/18/2022
This certification is for a Boise Cascade
individual building component only and
not for the building system as a whole.
The component design as shown on this
report is based upon loadings and
dimensions provided by others. Building
designer is responsible for determining
that the dimensions and loads for each
component match those required by the
plans and by the actual end use of the
component. Verification of framing
methods, bracing design, support
conditions, connections, etc. is the
responsibility of the building designer.
SCENARIO
04
This penetrations does
not require additional
reinforcing.
SCENARIO
05
01/18/2022
This certification is for a Boise
Cascade individual building
component only and not for the
building system as a whole. The
component design as shown on this
report is based upon loadings and
dimensions provided by others.
Building designer is responsible for
determining that the dimensions and
loads for each component match
those required by the plans and by the
actual end use of the component.
Verification of framing methods,
bracing design, support conditions,
connections, etc. is the responsibility
of the building designer.
SCENARIO
05
SCENARIO
06
This penetration requires
web reinforcing per the
attached "DETAIL - A"
These penetrations do
not require web
reinforcing
01/18/2022
This certification is for a Boise Cascade
individual building component only and not
for the building system as a whole. The
component design as shown on this report
is based upon loadings and dimensions
provided by others. Building designer is
responsible for determining that the
dimensions and loads for each component
match those required by the plans and by
the actual end use of the component.
Verification of framing methods, bracing
design, support conditions, connections,
etc. is the responsibility of the building
designer.
SCENARIO
06
SCENARIO
07
01/18/2022
This certification is for a Boise Cascade individual building component only and not for the building
system as a whole. The component design as shown on this report is based upon loadings and
dimensions provided by others. Building designer is responsible for determining that the
dimensions and loads for each component match those required by the plans and by the actual
end use of the component. Verification of framing methods, bracing design, support conditions,
connections, etc. is the responsibility of the building designer.
These penetrations do
not require web
reinforcing
SCENARIO
07
SCENARIO
08
01/18/2022
This certification is for a Boise
Cascade individual building
component only and not for the
building system as a whole. The
component design as shown on this
report is based upon loadings and
dimensions provided by others.
Building designer is responsible for
determining that the dimensions and
loads for each component match
those required by the plans and by
the actual end use of the
component. Verification of framing
methods, bracing design, support
conditions, connections, etc. is the
responsibility of the building
designer.
These penetrations do
not require web
reinforcing
SCENARIO
08
SCENARIO
09
01/18/2022
This certification is for a Boise
Cascade individual building
component only and not for the
building system as a whole. The
component design as shown on
this report is based upon loadings
and dimensions provided by
others. Building designer is
responsible for determining that
the dimensions and loads for
each component match those
required by the plans and by the
actual end use of the component.
Verification of framing methods,
bracing design, support
conditions, connections, etc. is
the responsibility of the building
designer.
This penetration requires
web reinforcing per the
attached "DETAIL - C"
SCENARIO
09
SCENARIO
10
01/18/2022
This certification is for a Boise Cascade individual building component only and not for the building
system as a whole. The component design as shown on this report is based upon loadings and
dimensions provided by others. Building designer is responsible for determining that the
dimensions and loads for each component match those required by the plans and by the actual
end use of the component. Verification of framing methods, bracing design, support conditions,
connections, etc. is the responsibility of the building designer.
This penetration requires
web reinforcing per the
attached "DETAIL - D"
SCENARIO
10
1
Rapich, Jason P
From:Mike Hughes <mike.hughes@bldr.com>
Sent:Thursday, January 13, 2022 10:26 AM
To:Simmons, Brent
Subject:[EXTERNAL] 19001204 - 1010 BURWELL
Attachments:Resized_20220113_073635.jpeg; vmacocsoak_2071525866792-1-
Resized952022011395073532.jpg; 1010 Burwell - Bremerton Apts Framing Layouts Rev
2.pdf
Hi Brent,
Will you please help me out with this one. Please see dialog below along with the attached.
Thank you,
Mike
MIKE HUGHES
OUTSIDE SALES REPRESENTATIVE
5519 20TH ST.E FIFE WA.98424
MIKE.HUGHES@BLDR.com
O: 253.922.8779 | C: 253.405.5148 | BLDR.com
From: Igor@serpanok.com [mailto:Igor@serpanok.com]
Sent: Thursday, January 13, 2022 8:33 AM
To: Mike Hughes <mike.hughes@bldr.com>
Cc: Igor@serpanok.com
Subject: FW:
EXTERNAL MESSAGE This email from igor@serpanok.com originated from outside of the organization.
Do not click links or open attachments unless you recognize the sender and know the content is safe.
Good morning Mike
Is there way to get help here
We have building inspector that saying that we need joist manufacturer OK or provide fix for these area
That we penetrated joist within 6” of bearing with electrical wire please see attached picture
Also we penetrated joist with two or three pipes and separation between pipes is less them 2 diameters of larger pipe
What would be fix for this or this OK
Thank you so much
Igor