HomeMy WebLinkAbout03 0010Job Addr:
Location:
Parcel No:
Applicant:
I3RFEME:RT'10" PERF" 1=T GE:_- "TaR
286 4th Street, Bremerton, i4A 98337
-Phon'e': ( 360 ) 478-5275 FAX: ( 360 ) 478-5278
BUILDING PERMIT
2900 WHEATON WAY Permit No: 03-0010
ALBERTSON'S GROCERY STORE Status: ISSUED
Applied: 01/07/2003
Issued: 01/13/2003
SIMPLEXGRINNELL LP 206-291-1400 Expires: 07/12/2003
9520 10TH AVE S #.100 SEATTLE WA 93108
Owner: ALBERTSON'S INC 208-395-6275
250 PARK CENTER BLVD BOISE IDAHO 83726
Contractor: SIMPLEXG RINNELL LP 206-291-14OLic #: SIMPLL*933BG Exp: 01-07-•2004
9520 10TH AVE S #100 SEATTLE WA 93103
Subcontr:
Desc: INSTALLATION OF FIRE SUPPRESSION SYSTEM FOR HOOD IN KITCHEN
*************************;KYF*3***iK***)K********* **%******************************k:*****.*�*:K***W.
Valuation * Permit Fees: 33.25 Total Calculated Fee: x.41.36
2,500.00 * 'Plan Check Fees: 54.11 Additional Fees'...`
.00
Other Fees: 4.50 Total Permit Fee' \ 141.86
This permit shall become null and void if the building or work authorized by this permit is not commenced within
180 day, from the date of such permit, or if this building or work authorized by such permit is suspended or
abandoned at any time after the work is commenced for a period of 180 days.
NOTICE - It. is the responsibility of the permit holder, not the City of 8remertoi. "�uYlding Of�i ia1_to see
to it that required inspections are made. The permit holder must notify thie Building Official when readyllflor
inspection=:. Failure of the permit holder to notify the Building Official sof required ing_ ections may result 1
in the stoppage of the work until such time that the permit holder can substantiate "the building fficial
that the concealed work meets or exceeds code requirements. Any demolition, testing, or nang2a`lrden shall
be borne directly by the permit holder. Failure to substantiate code requirements wi11 ind4mnlfy the/eity
against any and all responsibility or liability connected with the construction. !
I hereby certify that I have read and examined this permit and know the same o b <.h
and COY' 1
provisions of laws and ordinances governing this type of work will be complie witther specified herei
or not. The granting of a permit does not presume to give authority to \r\iolate or�cancel the provisions of
any other state or local law regulating construction or the performance oi*..construction. /
pate
I certify that I am exempt from the requirements of the state contractor's registration law, under
Section 3, Chapter 126, laws of 1967.
Signature
Date:
Permit Cem ter, W --Approved By':_. Date:_
____1 � _..—! I -S
I..286 4th Street, Bremerton, WA 98337
'e. ( 360) 4.78-5275 FAX: ( 360) 478-5278
Building Permit No: 03-0010
Job Address: 2900 WHEATON WAY Status: ISSUED
Location: ALBERTSON'S GROCERY STORE Issued: 01/13/2003
Assr Acct No: Expires: 07/12/200:3
R E. Q U I R E D I N S P E C T 1 0 N S
Item: 02150 CROSS CONNECTION CONTROL Dept: CROSSCC Division:
Item: 02000 FIRE SPRINKLERS/SUPPRESSION Dept: EIRE Division:
�K*=K*Y:�:�*k�K�k.KIK*��=�K;*;K�K�-k7kxc**��f::YAK*�K�K�k��F::ic�I:�K�K�K�S:�*�Ic�Y•�K�k*;Y*�K*�=�k�K�K�K�c�k��K�i:�K*�K*xc�lc**�K*�:***�k��P:�
TESTING: Must be recognized by the Washington Association of Building Officials
SPECINSP: Must be registered with the State of WA
ST OF WA: Stat; of WA Dept. of Labor and Industries 475-11.921
HEALTH: Bremerton/Kitsap Health District 475-S2:3S
ALL INSPECTIONS PERFORMED BY THE CITY OF BREMERTON MUST BE SCHEDULED THROUGH THE
PERMIT CENTER, ( 360) 478--5275. J
�;;;Kx',>k�:%k%f:%K*�K%K*.'I,"k.%k:%�•'•�K��K`-Y.y,:y(-�r=*�*�'�K*aK%K=KYc**�c:/.�i:�:T>K*�K%K�:�c%K>Y��•;�k>Y-Yc�K�'.%K�k%K*=k�K*���k�'.**xc*�:�=0c h;yF�*'K =k�=
Permit Holder's
Signature: _._._
Date".
s
f
'00���;^� ----------------��.����
BREMERTON PERMIT CENTER
.»-•"" PERMIT CONDITIONS
Permit No,: 03-0014.) Page: 1
Job Address: 2900 WHEATON WAY Applied: 01/07/2003
Assr Acct No: Approved: 01/13/2003
Location: ALBERTSON'S GROCERY STORE Issued: 01/13/2003
Applicant: SIMPLEXGRINNELL LP
Owner: ALBERTSON'S INC
Contractor: SIMPLEXGRINNELL LP
Description:
INSTALLATION OF FIRE SUPPRESSION SYSTEM
FOR HOOD IN KITCHEN
Conditions:
1. PRIOR TO PERFORMING ANY RENOVATION OR DEMOLITION WORK,
PUGET SOUND CLEAN AIR AGENCY (CLEAN AIR AGENCY) AND
WASHINGTON DEPARTMENT OF LABOR AND INDUSTRIES (L&I)
REGULATIONS REQUIRE AN ASBESTOS SURVEY BE PERFORMED TO
DETERMINE WHETHER THERE ARE ASBESTOS -CONTAINING MATERIALS
IN THE WORK AREA OR STRUCTURE. THE ASBESTOS SURVEY MUST BE
CONDUCTEDBY AN EPA CERTIFIED (AHERA) BUILDING INSPECTOR
(EXCEPT RENOVATION OF OWNER -OCCUPIED SINGLE FAMILY
RESIDENCES).
FOR MORE INFORMATION, PLEASE CONTACT CLEAN AIR AGENCY
THROUGH THEIR WEB SITE AT www.pscleanair.org OR BY PHONE AT
800--552--3565 OR 206-689-4058. THE L&I WEB SITE CAN BE
FOUND AT www.lni.wa.gov/wisha/p,-ts/asbestos/asbeet-o-s-.ht-m..
2. FIRE DEPT CONDITIONS OF APPROVAL:
A) TEST REQUIRED AT COMPLETION.
R) SY�-;TFM SHALL BE MONITORED BY FIRE ALARM SYST,,EM --
Permit Holder'
Signatu.re.,_
_ ate �=�
RECEIPT
RECEIPF Number:
03000032 Amount: 87.75
01/13/03 10:10
Paymeol Net hod:
CHECK Notation: DARRELL SACWAR
!nit: PC
-------------------------
Permit Not
-------------------------------------
03-0010 Type; FIRESPR FIRE
SPRINKLER PERMI
Site Address
2900 WHEATON WAY
Location:
ALBERTSON'S GROCERY STORE
Total Fees;
141.86
This Paymen!
87.75 Total ALL QVI
141.86
Balance'
.00
Account Code
Description
AmounL
16-322.1001 (2211)
BUILDING PERMIT FEES
83.25
643-2012V (0236)
-----------------------------------------------------------------
SFATE OF WA SURCHARGE
4.50
-CCC
E3RaMaR-F-a ! RERBMI I T CERlTER
286 4th Street, Bremerton, WA 98337
•
Phone: ( 360 ) 478-5,2175 FAX: ( 360 ) 478-5278 _ 0
BUILDING PERNU
_ C'KJ
Job Addr- a I D � Permit No: 03 0010
Location. ALBERTSON'S GROCERY STORE Status: PENDING
Parcel No: Applied: 01/07/2003
Issued:
Applicant: SIMPLEXGRINNELL. LP 206-291-1400 Expires:
9520 10TH AVE S #100 SEATTLE WA 98108
Owner: ALBERTSON'S INC 208-395-6275
250 PARK CENTER BLVD BOISE IDAHO 83726
Contractor: SI.MPLEXGRINNELL LP 206-291-1401.ic #: SIMPLL*988BG Exp: 01-07-2004
9520 10TH AVE S 4100 SEATTLE WA 98108
Subcontr:
Desc: INSTALLATION OF FIRE SUPPRESSION SYSTEM
Valuation * Permit Fees: 83.25 Total Calculated Fee: 141.86
2,500.00 * Plan Check Fees: 54.11 Additional Fees: .00
* Other Fees: -4.50 Total Permit Fee: 141.86
This p&rmit shall become null and void if the building or work authorized by this permit is not commenced within
180 days from the date of such permit, or if this, building or work authorized by such permit is suspended or
abandoned at any time after the work is commenced for a period of 180 clays.
NOTICE -- It is the responsibility of the permit holder, not the City of Bremerton or Building official to see
to it that required inspections are made. The permit holder must notify the Building official when ready for
inspections. Failure of the permit holder to notify the Building Official. of required inspections may result
in the stoppage of the work until ouch time that the permit holder can substantiate to the building official
that the concealed work meets or exceeds code requirements. Any demolition, testingzzx urden shall
be borne directly by the permit holder. Failure to substantiate code requireme swill indemnify the Ci ;
against any and all responsibility or liability connected with the construct n.
I hereby certify that I have read and examined this permit and know the
Provisions of laws and ordinances governing this type of work will be c
or not.. The granting of a permit does not presume to give authority to
any other state or local law regulating construction or the performance
Signature:
Date:
ne to be trFheyty.ecrflezKein
erlied with w
olate or caovislrf
construct'o
i or_,, `��
I certify that I am exempt from the requirements of the otate contractor's i istrati
Section 3, Chapter 126, laws of 1967.
Permit Center ---Approved By: _6�__'Lr Date:
Date:
X2003
BREMERTON___
VC,
0 03-0010
PERMIT CENTER
Department of Community Development 286 4th Street * Bremerton WA'* 98337
(360) 478-5275' Fax (360) 478-5278
Building Permit Application
APPLICANT: ❑ OWNER CONTRACTOR ErAUTHORIZED AGENT
Site Address
Tax Account Number:
CONTRACTOR: s;
(
OWNER or Authorized Agent:
Address: Z() 4 A
NEW DUPLEX
p 5
City,State'zip fe «
Dk
Address:
j License # & Expir. Date:
Co o Z 12
City, State, Zip
Contact Name:
RESIDENTIAL ADDITION
Phone #: ( )
Contact Phone #: (2d6) Z q
/- lyylk'
_t`
%tv U vc
Check the tvDe of aoolication for below
.7
NEW SINGLE-FAMILY RESIDENCE
d
❑
NEW DUPLEX
❑
❑
NEW MANUFACTURED HOME
❑
❑
RESIDENTIAL REMODEL
❑
❑
RESIDENTIAL ADDITION
❑
❑
RESIDENTIAL REPAIR
❑
JTV`"JAIL 07 70ol
NEW COMMERCIAL
❑
COMMERCIAL REMODEL
❑
COMMERCIAL ADDITION
❑
COMMERCIAL REPAIR
❑
NEW MULTI -FAMILY
❑
TENANT IMPROVEMENT
❑
NEW GARA lENT
NEW ACCESSORY BLDG
NEW SIGN
STRUCTURE DEMOLITION
GRADING (Cubic yards: )
OTHER
IS THIS PROPERTY WITHIN 200 FEET OF A SHORELINE? YES ❑ NO [✓]�
Scope of Work Proposed:
Square Footage: Dwelling:
Garage:
Decks:
Valuation
Plan Review Fee
Permit Fee
Surcharge
Total Fees i
zsoD -
5 II
g3�5
iso
Application for which no permit is issued within 180 days following the date of application shall expire by limitation, and
plans and other data submitted for review may thereafter be returned to the applicant or destroyed by the building official.
The building official may extend the time for action by the applicant for a period not exceeding 180 days on request by
the applicant showing the circumstances beyond the control of the applicant have prevented action from being taken. No
applicant shall be extended more than once. In order to renew action on an application after expiration, the applicant
shall resubmit plans and pay a new plan review fee.
APPLICANT'S SIGNATURE:%,IA&DATE: 01Z�10?
t
jw
4' 1), A,.
RECEIPT
Ac le -!:>'.;if 'k* A :4Z
-,Ic** V,** ***
Numb+ r 03000019 Amount" 54, '11
.1
01./0 /03 16 01
Payment 11(i. -it -hod: CK Nota -i-. .on: SACKWAR CK
snit: VW
10ermli.t. N.D: 0,3-0010 FIRESPR FIRE
SPRINKLER PERMI
!.-occ ation: ALeER,r'-sows GROCERY STORE
Total Fees'.
.1.41.., 86
541. 1
his Payflif.-mt Total ALL Pmts:
8 a la� ri c e,
01'.%5
t)ccount Code D (- s c. r J. pt -ion
Amount
16-345,8300 (4 580) OUILD.MG PLAN CHECK' FEES
54.1.1
t
jw
GA5 VA Iv?
r -T -
i
25-35 3 -3
ryes
o APPROVE®yo
a rr,
�zXzo"
3 yea l
uZ 300
Cd "v
O ue,t'j
D ,aN ®� 2p03
--Jr Or)
oi
ao
1
Z4?420 41-4e.44"4a'4i
?9-337
SYSTEM DESIGN
The R-102 and the PIRANHA systems use compatible agents and
components, therefore, they may be used together for cooking
appliance, hood, and duct protection. The primary ANSUL
AUTOMAN Release can be either an R-102 or a PIRANHA
ANSUL AUTOMAN Release and can actuate up to two additional
R-102 or PIRANHA Regulated Actuators. In systems utilizing a
101 remote release, any combination of the maximum number of
regulated actuators can be used.
• Both systems must actuate simultaneously.
• Each system must be designed and installed per its appropri-
ate manual.
• Adjacent appliances requiring protection must be protected
with the same type of system, either R-102 or PIRANHA,
unless the center -to -center spacing between the adjacent
R-102 and PIRANHA nozzles is no less than 36 inches.
• When appliances are protected with R-102 nozzles, the hood
and connecting duct above those appliances cannot be pro-
tected with PIRANHA nozzles.
• Mixing systems in a common plenum is not allowed.
The Ansul R-102 Restaurant Fire Suppression System may be
used on a number of different types of restaurant cooking appli-
ances and hood and duct configurations. The design information
listed in this section deals with the limitations and parameters of
this pre-engineered system. Those individuals responsible for the
design of the R-102 system must be trained and hold a current
Ansul certificate in an R-102 training program.
One of the key elements for restaurant fire protection is a correct
system design. This section is divided into ten sub -sections: Noz-
zle Placement Requirements, Tank Quantity Requirements, Actu-
ation and Expellant Gas Line Requirements, Distribution Piping
Requirements, Detection System Requirements, Manual Pull Sta-
tion Requirements, Mechanical Gas Valve Requirements, Electri-
cal Gas Valve Requirements, Electrical Switch Requirements, and
Pressure Switch Requirements. Each of these sections must be
completed before attempting any installation. System design
sketches should be made of all aspects of design for reference
during installation.
NOZZLE PLACEMENT REQUIREMENTS
This section gives guidelines for nozzle type, positioning, and
quantity for plenum, duct, and individual appliance protection. This
section must be completed before determining tank quantity and
piping requirements.
Duct Protection
All duct protection is UL approved without limitation of maximum
duct length (unlimited length). This includes all varieties of duct-
works both horizontal and vertical including ducts that run at
angles to the horizontal and ducts with directional bends.
The R-102 system uses several different duct nozzles depending
on the size of duct being protected.
1. 1W Nozzle (Part No. 419336) — 1.5 Gallon and 3.0 Gallon
Systems:
The R-102 systems, both 1.5 gallon and 3.0 gallon, use the
1W nozzle (Part No. 419336) for duct protection of 27 in.
(68.6 cm) perimeter or less or 8.5 in. (21.6 cm) diameter or
less. The nozzle tip is stamped with 1 W, indicating that this is
a one -flow nozzle and is to be counted as one flow number.
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-1
7-1-98 REV.3
— Single Nozzle (One Flow Number) Duct Protection:
One 1W nozzle (Part No. 419336) will protect ducts with a
maximum perimeter of 27 in. (68.6 cm) or a maximum
diameter of 8.5 in. (21.6 cm). The nozzle must be installed
2-8 in. (5-20 cm) into the center of the duct opening and
positioned as shown in Figure 1.
2-8 IN.
(5 — 20 cm)
FIGURE 1
000173
Single Nozzle (One Flow Number) Transition Protection:
One 1W nozzle (Part No. 419336) will protect transitions
where the perimeter of 27 in. (68.6 cm) or the diameter of
8.5 in. (21.6 cm) or less begins within that transition. The
nozzle must be placed in the center of the transition open-
ing where the maximum perimeter or diameter begins as
shown in Figures 2 and 3.
MODUI
NOT M
27 IN. (
MC
NO
8.5
FIGURE 2
000174
FIGURE 3
000175
SECTION IV — SYSTEM DESIGN
► UL EX. 3470 ULC CEx747 Page 4-2
7-1-98 REV.1
NOZZLE PLACEMENT REQUIREMENTS (Continued)
Duct Protection (Continued)
NOTICE
A 2WH nozzle must be substituted for a 2W
nozzle for any installation using Option 2 of the No
1.5 gallon system coverage (6 flow duct and 24
plenum protection only).
2.2W Nozzle (Part No. 419337):
The R-102 System, uses the 2W nozzle (Part No. 419337) for
duct protection of 75 in. (190.5 cm) perimeter or less, or 24 in.
(61 cm) diameter or less. The nozzle tip is stamped with 2W,
indicating that this is a two -flow nozzle and must be counted
as two flow numbers.
The 1W and 2W nozzles will protect the following:
3. Single Nozzle (2W) Duct Protection:
One 2W nozzle will protect ducts with a maximum perimeter
of 75 in. (190.5 cm) or a maximum diameter of 24 in. (61 cm).
The nozzle must be installed 2-8 in. (5-20 cm) into the center
of the duct opening and positioned as shown in Figure 4.
2-8 IN
(5-20
FIGURE 4
000173
4. Single Nozzle (2W) Transition Protection:
One 2W nozzle will protect transitions at the point where the
perimeter of 75. in. (190.5 cm) or the diameter of 24 in.
(61 cm) or less begins within that transition. The nozzle must
be placed in the center of the transition opening where the
maximum perimeter or diameter begins as shown in Figures 5
and 6.
MODU
NOT M
75. IN.
FIGURE 5
000174
FIGURE 6
000175
5. Dual -Nozzle Duct Protection:
Two 2W nozzles will protect ducts with a maximum perimeter
of 150 in. (381 cm) or a maximum diameter of 48 in. (122 cm).
The nozzles must be installed 2-8 in. (5-20 cm) into the duct
opening and positioned as in Figure 7.
LENGTH
CT
"H
FIGURE 7
000176
NOTICE
In installations where a UL listed damper
assembly is employed, the duct nozzle can be
installed beyond the 8 in. (20 cm) maximum, to
a point just beyond the damper assembly that
will not interfere with the damper. Exceeding the
maximum of 8 in. (20 cm) in this way will not void
the UL listing of the system.
SECTION IV — SYSTEM DESIGN
► UL EX. 3470 ULC CEx747 Page 4-8
7-1-98 REV.3
NOZZLE PLACEMENT REQUIREMENTS (Continued)
Plenum Protection (Continued)
4 IN.
(10 c
NOZZLE TIP �
MUST BE WITHIN
THIS AREA
12 IN. (30 cm)
MAXIMUM
8 IN. (20 cm)
MAXIMUM
FIGURE 26
►1 N NOZZLE — PART NO.419335 — SINGLE BANK PROTECTION
One 1 N nozzle will protect 8 linear feet (2.4 m) of single filter bank
plenum. The nozzle(s) must be mounted in the plenum, 2 to 4 in.
(5 to 10 cm) from the face of the filter, centered between the filter
height dimension, and aimed down the length. The filter height must
►not exceed 20 in. (51 cm). See Figure 27a.
FIGURE 27a
►1 N NOZZLE — PART NO. 419335 — "V" BANK PROTECTION
Two IN nozzles will protect 8 linear feet (2.4 m) of "V" bank plenum.
The nozzles must be mounted in the plenum, 2 to 4 in. (5 to 10 cm)
from the face of the filter, centered between the filter height dimen-
sion, and aimed down the length. The filter height must not
►exceed 20 in. (51 cm). See Figure 27b.
2
► FIGURE 27b
Exception: When the plenum chamber contains filters that do not
exceed 10 in. (25.4 cm) in height and the 1N nozzle can be
installed at the intersecting center lines of both filter banks and not
exceed the 2-4 in. (5 to 10 cm) distance from either filters, a single
►1 N nozzle can be used. See Figure 27c.
2 -41N.2 -41N.
(5 —10 cm) (5 — 10 cm)
1N NOZZLE
10 IN. (25.4 cm)
MAXIMUM
► FIGURE 27c
ODOM
NOTICE
If 1 N nozzle coverage does not exceed 7 linear
ft. (2.1 m), the nozzle can be mounted 2 to 6 in.
(5-15 cm) from the face of the filter.
SECTION IV — SYSTEM DESIGN
► UL EX. 3470 ULC CEx747 Page 4-11
7-1-98 REV.5
► NOZZLE PLACEMENT REQUIREMENTS (Continued)
34 IN. (86 cm) MAXIMUM DIAGONAL
Fryer — Single Nozzle Protection (Continued)
CENTER OF HAZARD AREA
Maximum Area Dimensions — Single Nozzle Fryer Protection (Continued)
Max. Size
Max. Size
Overall
Type of
Nozzle Height
Frypot Only
With Dripboard
Nozzle
Above Top of Fryer
HEIGHT
19.5 in. x 19 in.
19.5 in. x 25 3/8 in.
290
13 in. to 16 in.
(50 cm x 48 cm)
(50 cm x 65 cm)
(33 to 41 cm)
19.5 in. x 19 in.
19.5 in. x 25 3/8 in.
3N
See Figure
(50 cm x 48 cm)
(50 cm x 65 cm)
34
18 in. x 18 in.
18 in. x 27 5/8 in.
3N
25 in. to 35 in.
(46 cm x 46 cm)
(46 cm x 70 cm)
(64 cm to 89 cm)
I
I
I I I I
I
1 , I
FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD
290 NOZZLE TIP POSITIONED OVER THE MIDPOINT OF THE HAZARD AREA t 3 IN.
(7.6 cm) FROM THE MIDPOINT ALONG THE LONGEST SIDE OF THE HAZARD AND t 1
IN. (2.5 cm) FROM THE MIDPOINT ALONG THE SHORTEST SIDE OF THE HAZARD AND
AIMED AT THE MIDPOINT OF THE COOKING AREA.
FIGURE 33
002288
J
FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD
3N NOZZLE TIP POSITIONED ANYWHERE ALONG OR WITHIN PERIMETER OF COOK-
ING SURFACE AND AIMED TO THE CENTER OF THE COOKING AREA.
FIGURE 34
002297
Nozzle
Location
See Figure
33
See Figure
34
See Figure
35
TOP OF FRYER
FRO j
'
RIGHT-TO-LEFT �8
°00010 CENTERLINE
FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD
NOTE: 3N NOZZLE TIP MUST BE LOCATED WITHIN THE PERIMETER OF THE SURFACE
AREA AND FORWARD OF THE RIGHT-TO-LEFT CENTERLINE.
FIGURE 35
34 IN. (86 cm) MAXIMUM DIAGONAL
DISTANCE BETWEEN NOZZLE AND
CENTER OF HAZARD AREA
21 in (53 Cm)
MINIMUM
VERTICAL
I NOZZLE
HEIGHT
J
FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD
3N NOZZLE TIP POSITIONED ANYWHERE ALONG OR WITHIN PERIMETER OF COOK-
ING SURFACE AND AIMED TO THE CENTER OF THE COOKING AREA.
FIGURE 34
002297
Nozzle
Location
See Figure
33
See Figure
34
See Figure
35
TOP OF FRYER
FRO j
'
RIGHT-TO-LEFT �8
°00010 CENTERLINE
FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD
NOTE: 3N NOZZLE TIP MUST BE LOCATED WITHIN THE PERIMETER OF THE SURFACE
AREA AND FORWARD OF THE RIGHT-TO-LEFT CENTERLINE.
FIGURE 35
SECTION IV — SYSTEM DESIGN
► UL EX. 3470 ULC CEx747 Page 4-34
7-1-98 REV.4
TANK AND CARTRIDGE REQUIREMENTS
Once the hazard analysis is completed and the total nozzle flow
numbers are established, the quantity and size of agent tanks and
cartridges needed to supply the nozzles with the proper volumes
of agent at the proper flow rates can be determined. For cartridges
used in the regulated release mechanism, flow capacities, tank
quantities and sizes, and regulated release cartridge options are
given in the table below.
Total Quantity and Regulated Release
Flow Size of Cartridge Options
Numbers* Tanks Nitrogen Carbon Dioxide
1— 5 (1) 1.5 Gallon LT -20-R (7032) 101-10 (15850)
6-11 (1) 3.0 Gallon LT 30-R (5373) 101-20 (17492)
11 —16 (1) 1.5 Gallon Double (73022) 101-30 (15851)
(1) 3.0 Gallon
16-22 (2) 3.0 Gallon Double (73022) 101-30 (15851)**
,-When one or more regulated actuators are used, the following
tank and cartridge combinations apply for each regulated actuator:
Regulated Actuator
Tank(s)
(1) 1.5 Gallon
(1) 3.0 Gallon
(1) 1.5 Gallon and
(1) 3.0 Gallon
►(2) 3.0 Gallon
Regulated Actuator
Cartridge
LT -20-R or 101-10
LT30-R or 101-20
LT -A-101-30 or 101-30**
LT -A-101-30 or 101-30**
For exceptions to maximum flow numbers, see Distribution Piping Requirements for 1.5 gal-
lon and 3.0 gallon systems in this Section.
The 101-30 cartndge Part No. 15851, can not be used when (2) two 3.0 gallon tanks are man-
ifokied together.)
For higher total flow numbers (23 to 110), multiple cartridges and
regulated actuators are required as shown in the System Selection
Guide in Section IX — Appendix.
ACTUATION GAS LINE WITH AN LT -20-R,
LT -30-R, 101-10 OR 101-20 CARTRIDGE
MAXIMUM LENGTH OF 20 Fr. (6 m),
MAXIMUM NO. OF FITTINGS 9
"ANSUL AUTOMAN"
REGULATED RELEASE
ASSEMBLY
ACTUATION AND EXPELLANT GAS LINE REQUIREMENTS
This section contains the guidelines for installing the actuation and
expellant gas lines between the regulated release mechanism reg-
ulator, each regulated actuator regulator, and each agent tank.
These limitations should be considered when selecting the com-
ponent mounting locations.
P. Actuation Gas Line — 6 to 8* Tanks Maximum
i' 8 Tank maximum reflects the utilization of 3 tank regulated actuators.
1. Use only 1/4 in. Schedule 40 black iron, hot -dipped galva-
nized, chrome -plated, or stainless steel pipe and fittings.
2. The actuation gas line piping is installed from the regulated
release mechanism to each regulated actuator connected
within the system. The total length of the actuation gas line
from the regulated release assembly to the regulated actuator
assembly(ies) must not exceed 20 ft. (6 m) when using an
LT20-R (Part No. 7032), an LT30-R nitrogen cartridge (Part
No. 5373), or a 101-10 (Part No. 15850) or a 101-20 (Part No.
► 17492) carbon dioxide cartridge. See Figure 73.
REGULATED ACTUATOR ASSEMBLY
EXPELLANT GAS LINES
NOT INCLUDED IN ACTUATION /
GAS LINE LENGTH TOTALS
ACTUATOR
REGULATED
ACTUATOR
ASSEMBLY
FIGURE 73
00=5
DISTRIBUTION PIPING REQUIREMENTS (Continued)
Supply and Branch Line Identification
The R-102 distribution piping network is broken down into four
specific pipe runs: the Supply Line, the Duct Branch Line,
the Plenum Branch Line, and the Appliance Branch Line. See
► Figure 79.
DUCT
BRANCH LINE
SUPPLY \. �•
LINE
PLENUM APPLIANCE
BRANCH LINE BRANCH LINE
NOTE: THIS IS A CONCEPTUAL DRAWING ONLY.
THIS IS NOT AN ACTUAL INSTALLATION.
' FIGURE 79
000779
NOTE: THESE ARE EXAMPLES ONLY. OTHER CONFIGURATIONS CAN BE DESIGNED.
END OF
SUPPLY LINE
SECTION IV — SYSTEM DESIGN
► UL EX. 3470 ULC CEx747 Page 4-37
7-1-98 REV.2
END OF
SUPPLY LINE
l
_..D OF
SUPPLY LINE
END OF
SUPPLY LINE
ire
SUPPLY (NOZZLES FOR
LINE TEE PLENUM
PROTECTION)
END OF
SUPPLY LINE
BRANCH LINE CANNOT
START AHEAD OF A
SUPPLY LINE TEE
FIGURE 80
000780
(NOZZLES FOR
PLENUM
PROTECTION)
BRANCH LINE CANNOT
START AHEAD OF A
SUPPLY LINE TEE
FIGURE 80
000780
SECTION IV — SYSTEM DESIGN
► UL EX. 3470 ULC CEx747 Page 4-38
7-1-98 REV.3
DISTRIBUTION PIPING REQUIREMENTS (Continued)
Supply and Branch Line Identification (Continued)
SUPPLY LINE
The Supply Line is defined as the length of pipe which runs from
the agent tank outlet to the last branch line (whether a duct, appli-
ance, or plenum branch line). This includes all supply line fittings
except for the tees or elbows leading to the branch lines. See
► Figures 79 and 80.
NOTICE
Branch lines cannot start ahead of a supply line
tee.
DUCT BRANCH LINE
The Duct Branch Line is defined as the length of pipe which runs
from the supply line to the duct nozzle(s). This includes all branch
line fittings as well as the tee or elbow used to start the branch line.
► See Figures 79 and 81.
DUCT BRANCH LINE
(ELBOW INCLUDED)
DUCT BRANCH LINE
(TEE INCLUDED)
S
' .4
v
DUCT BRANCH LINE
��• (TEES INCLUDED)
C-' 1
r'
i
FIGURE 81
000781
PLENUM BRANCH LINE
The Plenum Branch Line is defined as the length of pipe which
runs from the supply line to the plenum nozzle(s). This includes all
branch line fittings as well as the tee or elbow used to start the
► branch line. See Figures 79 and 82.
.'fes
j PLENUM BRANCH LINE . -C'\•,
I (TEE INCLUDED)
1
1
PLENUM BRANCH LINE
(TEE INCLUDED)
FIGURE 82
000782
APPLIANCE BRANCH LINE
The Appliance Branch Line is defined as the length of pipe which
runs from the supply line to the appliance nozzle(s). This includes
all branch line fittings as well as the tee or elbow used to start the
branch line. See Figures 79 and 83.
i
1
I
APPLIANCE BRANCH LINES
(TEES INCLUDED)
FIGURE 83
0007M
DISTRIBUTION PIPING REQUIREMENTS (Continued)
Distribution Piping Requirements — 3.0 Gallon System
1. The maximum length between the start of the first branch line
and the start of the last branch line must not exceed 24 ft.
(7.3 m). When the supply line is split, the combined total of
both legs of the supply line (from the start of the first branch
line to the start of the last branch line) must not exceed 24 ft.
► (7.3 m). See Figure 88.
2. The total length of all branch lines must not exceed 36 ft.
► (10.9 m). See Figure 88.
3. Use a 3/8 in. union to connect the tank adaptor to the 3/8 in.
supply line.
4. A maximum of two nozzles are allowed per duct branch line.
5. The requirements of the following table must not be exceeded:
SECTION IV — SYSTEM DESIGN
► UL EX. 3470 ULC CEx747 Page 4-41
7-1-98 REV.1
SUPPLY \ ,
TEE `
\v OD0266
COMBINED LENGTH OF
BOTH LEGS OF SUPPLY
LINE MUST NOT 3 BRANCH LINES
EXCEED 24 FT. (7.3 m)
IN NOZZLE
/\ 2W NOZZLE
1N NOZZLE
1�
230 NOZZLE /
O
245 NOZZLE 1/2N NOZZLE
(BRANCH LINE IN BOLD)
COMBINED LENGTH MUST 00c
NOT EXCEED 36 FT. (10.9 m)
' FIGURE 88
Duct Plenum Appliance
Requirements Supply Line Branch Line Branch Line Branch Line
Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in.
Maximum Length 40 ft. 8 ft. 4 ft. 12 ft.
(12.2 m) (2.4 m) (1.2 m) (3.7 m)
Maximum Rise 6 ft. 4 ft. 2 ft. 2 ft.
(1.8 m) (1.2 m) (.6 m) (.6 m)
Maximum 90° 9 4 4 6
Elbows
Maximum Tees 1 2 2 4
Maximum Flow 11* 4 2 4
Numbers
'Exceptions:
1. Twelve (12) flow numbers are allowed in any one tank not containing two -flow appliance nozzles, and/or, a IN nozzle for wok or griddle protection, and/or, a 1F nozzle for range
protection, and/or, a 3N nozzle for fryer protection.
2. Twelve (12) flow numbers are allowed with any one tank using only two -flow appliance nozzles.
3. Twelve (12) flow numbers are allowed with any one tank using only three -flow appliance nozzles.
Special Instructions:
1. Twelve (12) flow numbers are allowed when four (4) Dean Industries GTI Gas Fryers are protected at low proximity as shown in Figure 101 on Page 4-52. The discharge piping
must be as shown in Figure 102 on Page 4-52.
2 For certain McDonald's applications, 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 1/2N electrostatic precipitator nozzle,
one (1) 1 N plenum nozzle, and four (4) two -flow appliance nozzles. Contact Ansul Applications Engineering Department for additional information
DETECTION SYSTEM REQUIREMENTS
Once the fire suppression system design has been determined, a
detection system design must be completed. This section contains
guidelines and limitations for detection system installation.
Detector Identification
The two types of detectors are distinguished from each other by
their location in the detection system.
1. The Terminal Detector (Part No. 56838, 15375, or 417368) is
the last in a series of detectors, or the only detector used in a
single -detector system. This detector is thus named because
it is at the point at which the wire rope ends, or "terminates"
2. A Series Detector (Part No. 56837, 15373, or 417369) is any
detector located in-line between the regulated release mech-
anism and the terminal detector.
Detector/Pulley Elbow Quantity
The quantity of detectors used in the system will vary depending
on the style of detector used.
1. Conduit runs, pulley elbows, and number of detectors per sys-
tem must be within the approved system guidelines. The fol-
lowing requirements must not be exceeded:
Maximum
Maximum
Maximum
Number of
Number of
Length of 1/2
Detectors
Elbows
in. Conduit
per System
per System
per System
Clip on Style 12 18 125 ft. (38.1 m)
Detector
Hinge Style 5 8 103 ft. (31.3 m)
Detector
Scissors Style 15 20 150 ft. (45.7 m)
Detector
2. If hinge style detectors are mixed in a system with either clip -
on or scissor style, 4 series and 1 terminal is the maximum
number allowed. If clip -on style are mixed with scissor style,
the maximum allowed is 11 series and 1 terminal.
NOTICE
When using the "clip -on" style detector, the ter-
minal detector may use the "hinged" style
mounting bracket with the "clip -on" style linkage.
This is only allowed with the terminal detector.
When using this option, the total number of "clip -
on" style detectors (11 series and 1 terminal) is
still allowed.
3. If hinge style detectors are mixed in a system with either clip -
on or scissor style, the maximum length of wire rope must not
exceed 103 ft. (31.4 m) and the maximum number of pulley
elbows must not exceed 8. If clip -on style are mixed with scis-
sor style, the maximum length of wire rope must not exceed
125 ft. (3.81 m) and the maximum number of pulley elbows
must not exceed 18.
4. If the hazard requires more than 15 detectors, up to five 101
Remote Releases (Part No. 12029) can be used for system
actuation. Each 101 remote release allows the use of a maxi-
mum of 15 "scissor" style detectors (14 series and 1 terminal)
for a total of 75 detectors if needed.
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-45
7-1-98
Detector Placement Requirements
EXHAUST DUCTS
Each exhaust duct must have at least one detector installed in the
duct entrance, located in the airstream of the cooking vapors, or at
► a maximum of 20 ft. (6.1 m) into the duct opening. See Figure 93.
FIGURE 93
000271
NOTICE
When gas appliances are used and the flue
gases from the burner are exhausted into the
duct, the detector must be kept out of the air
stream of these exhaust gases. These gases
can be very hot and could actuate the system
unnecessarily.
Duct openings that are long and narrow or large
enough to require multiple duct nozzles may
require additional detectors.
ELECTROSTATIC PRECIPITATOR
If an electrostatic precipitator is located at or near the base of the
exhaust duct, it is necessary to locate a detector below the pre-
cipitator, at the base of the duct, and also locate one in the duct,
► just above the precipitator. See Figure 94.
When installing the detector bracket and system conduit, make
certain they do not interfere with the operation of the precipitator.
1--
FIGURE 94
000266
SECTION IV — SYSTEM DESIGN
► UL EX. 3470 ULC CEx747 Page 4-46
7-1-98
DETECTOR SYSTEM REQUIREMENTS (Continued)
Detector Replacement Requirements (Continued)
COOKING APPLIANCES
If the cooking appliance is located under an exhaust duct where a
detector has been mounted, it is normally not necessary to utilize
another detector for that cooking appliance, provided the detector
► is not more than 12 in. (30 cm) into the duct. See Figure 95.
APPLIANCE
APPLIANCE
APPLIANCE
APPLIANCE
REQUIRES
COVERED BY
COVERED BY
REQUIRES
SEPARATE
DETECTOR
DETECTOR
SEPARATE
DETECTOR
UNDER DUCT
UNDER DUCT
DETECTOR
K STYLE
ML STYLE
415742
500 °F (260 °C) ONLY
FIGURE 95
000269
Detectors used for cooking appliances must be located above the
surface and within the perimeter of the cooking appliance. They
must be positioned toward the exhaust duct side of the appliance
and high enough to prevent accidental actuation of the system.
The cooking appliance detectors must be located in the air stream
of the cooking fumes for quick fire detection. It is normally neces-
sary to use one detector per area of single nozzle coverage, even
though more than one appliance may be covered with a single
nozzle.
Detection Line Requirements
CONDUIT
Rigid conduit, 1/2 inch Schedule 40 galvanized pipe, or 1/2 inch
EMT thin-wall conduit may be used. Standard steel conduit fittings
(compression type are recommended) must be employed to prop-
erly install the detection system. All conduit or pipe must be firmly
supported. When using pipe, make certain that all ends are care-
fully reamed, deburred and blown clear of chips and scale before
assembly.
NOTICE
The conduit offset can be used at the top or bot-
tom of the regulated release to change direction
of the conduit. The conduit offset cannot be
used with pulley tees. All other changes in direc-
tion must be made by using Ansul approved pul-
ley elbows, Part No. 423254 or 415670. See
Figure 96.
FIGURE 96
000270
Fusible Link Selection
When possible, temperature readings should be taken at each
detector location to determine correct fusible link temperature rat-
ing. Temperature can be recorded using either a maximum regis-
tering thermometer, Part No. 15240, temperature tape or any other
accurate thermometer.
O
@T::2D
."gUL.
Fusible Link
Rating
Temperature Does
Part No.
TEMPERATURE RATING
O10N�
STAMPED ON FUSIBLE
[�
LINK BODY
0
212 °F (100 °C)
000170
000171
K STYLE
ML STYLE
415742
500 °F (260 °C) ONLY
FIGURE 97
Select correct UL Listed fusible link(s) for installation in detector(s)
according to the temperature condition chart below:
Temperature
To Be Used Where
Fusible Link
Rating
Temperature Does
Part No.
(See Figure 79)
Not Exceed
415739
165 °F (74 °C)
100 °F (38 °C)
415740
212 °F (100 °C)
150 °F (66 °C)
415741
280 °F (138 °C)
225 °F (107 °C)
415742
360 °F (182 °C)
290 °F (143 °C)
415743
450 °F (232 °C)
360 °F (182 °C)
56816
500 °F (260 °C)
400 °F (204 °C)
MANUAL PULL STATION REQUIREMENTS
A remote manual pull station allows the R-102 system to be man-
ually operated at some point distant from the regulated release
assembly. The pull station should be installed at a maximum height
of 60 in. (152 cm) and located in the path of exit. The pull station
is the only source of manual actuation of the regulated release
assembly.
Two styles of remote pull stations are available: metal stamped
and plastic molded.
The total length of the cable used for each manual pull station with-
in a system must not exceed 150 ft. (46 m).
The maximum number of pulley elbows that may be used per sys-
tem is 20.
One pulley tee, Part No. 15342, is allowed per system.
Exception: When using a pulley tee, Part No. 15342, in the pull
station line, the maximum length of wire rope to each pull station
must not exceed 125 ft. (38 m) and the maximum number of
elbows must not exceed 18.
Metal Stamped Style — Part No. 4835 or 54011
Parts that may be used for installation of a metal stamped remote
manual pull station are:
Description Part No.
Remote Manual Pull Station Assembly*
54011
Remote Manual Pull Station Assembly
4835
P- Pulley Elbow
423250
Pulley Elbow
415670
Pulley Tee**
15342
'Assembly includes parts listed below:
415256
1/16' Stainless Steel Cable 50 ft. (15 m)
15821
Oval Press -To -Crimp Sleeves
4596
Glass Break Rod (1)
4834
" Designed for 32 T to 130 IF (0 °C to 54 °C) temperature areas. Utilized when two remote
manual pull stations are being connected to one regulated release assembly.
Plastic Molded Style — Part No. 415255
55598
Parts that may be used for installation of a plastic
molded remote
manual pull station are:
55604
Description
Part No.
Remote Manual Pull Station Assembly
415255
Trim Ring Shipping Assembly (25)
415256
Replacement Seal Shipping Assembly (25)
415317
1/16" Stainless Steel Cable 500 ft. (152 cm)
79653
Oval Press -To -Crimp Sleeves
4596
Pulley Elbow
45771
Pulley Tee
15342
MECHANICAL GAS VALVE REQUIREMENTS
An Ansul or Ansul approved mechanical gas shut-off valve system
can be attached to the R-102 system. The system works both
mechanically and pneumatically by use of an air cylinder located
inside the regulated release assembly. Upon actuation of the fire
suppression system, a pneumatically -operated air cylinder assem-
bly will mechanically close the gas shut-off valve.
The total length of the cable for the mechanical gas valve must not
exceed 150 ft. (46 m). The maximum number of pulley elbows that
may be used is 20.
One pulley tee (Part No. 15342) is allowed per system.
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-47
7-1-98
Exception: When using a pulley tee, Part No. 15342, the maxi-
mum length of wire rope to each gas valve must not exceed
125 ft. (38 m) and the maximum number of elbows must not
exceed 18.
Parts that may be used for installation of a Mechanical Gas Shut-
off Valve are:
Description Part No.
Gas Valve/Actuator 3/4 in. Assembly (Ansul)*
55598
Gas Valve/Actuator 1 in. Assembly (Ansul)*
55601
Gas Valve/Actuator 1 1/4 in. Assembly (Ansul)*
55604
Gas Valve/Actuator 1 1/2 in. Assembly (Ansul)*
55607
Gas Valve/Actuator 2 in. Assembly (Ansul)*
55610
Gas Valve/Actuator 2 1/2 in. Assembly (ASCO)*
25937
Gas Valve/Actuator 3 in. Assembly (ASCO)*
25938
► Pulley Elbow**
423250
Pulley Elbow**
415670
Pulley Tee***
15342
1/16" Stainless Steel Cable
15821 or
50 ft. (15 m) or 500 ft. (152 m) roll
79653
Oval Press -To -Crimp Sleeve
4596
Stop Sleeve (2)
26317
Assembly includes parts listed below:
Approved for 700'F (371 °C) temperature areas
Used with two (2) ANSUL AUTOMAN releases to operate one (1) mechanical gas valve.
Air Cylinder Assembly 15733
Air Cylinder 15521
Tubing Assembly 15529
Copper Tubing, 1/8 in. 15525
Male Elbow 15523
Male Connector 15522
Machine Screw (2) 15421
Hex Nut (2) 15527
Lockwasher(2) 4141
Visual Inspection Seal (2) 197
All valves above are UL listed and approved. They may be mount-
ed in any position. Pipe threads are type NPT. Ambient operating
temperature range of all valves is 32 OF to 120 OF (0 °C to 49 °C).
The valves are not weatherproof and must be located indoors in
areas approved by the "authority having jurisdiction"
ELECTRICAL GAS VALVE REQUIREMENTS
A UL Listed electrically -operated gas shut-off valve can be
attached to the R-102 system to provide an electrical means of
shutting off the gas line at a predetermined point. If an electric gas
shut-off valve is used in the system it must be attached with both
an electric (snap -action) switch and a manual reset relay. For more
information on the types of electric (snap -action) switches, refer to
P- the Electrical Switch, Field Installation section. The manual reset
relay is reviewed in this section.
All electrical connections should be performed by a QUALIFIED
ELECTRICIAN and in accordance with authority having
jurisdiction.
The following is a brief explanation of how the R-102 system oper-
ates with an Electric Gas Shut-off Valve attached:
With the regulated release cocked in the ready condition, the nor-
mally closed contacts in the snap -action switch allow current to
flow to the manual reset relay. With the relay coil energized, nor-
mally open contacts in the reset relay close, allowing the solenoid
in the gas valve to be energized.
�a� ��� UUUUUUUUIMUUU UUUUUUU//IT
UUUiUUiai llllllll/lllll/lllllll /������ %111///l/ll
iaUUU�uU IUUUUUUUUUUIIUI ''''�'�'►uUu' ''''''�''
rIJJJ!*W$)lll�
,row \JDJ
Fire Supression systems
Equipment Supplied By
Fire& ell/
Security
gF�EMER A����Nr
9
�g
13 .e
f
a
4
a
0
a
0
0
x
z
0
rn
a w z
a <�
APPROM )W.
G
DRAM
aTU
PNdECr WLMM3 c
SUP -01