HomeMy WebLinkAbout5234 ORDINANCE NO. 5234
AN ORDINANCE of the City Council of the City of
Bremerton, Washington, amending Chapter 1802 of the
Bremerton Municipal Code entitled "City Fire Code" to adopt the
2012 edition of the International Fire Code, as amended by the
Washington State Building Code Council in Chapter 51 -54 of the
Washington Administrative Code ( "WAC ") and to incorporate
additional amendments
WHEREAS, the City adopted the state International Fire Code as Chapter 18 02
of the Bremerton Municipal Code, and
WHEREAS, the International Fire Code has been updated with the publication of
the 2012 International Fire Code, and
WHEREAS, Chapter 18 02 of the Bremerton Municipal Code needs to be
amended to reflect the changes to the 2012 edition of the International Fire Code as well as to
incorporate additional amendments, NOW THEREFORE,
THE CITY COUNCIL OF THE CITY OF BREMERTON, WASHINGTON,
DOES HEREBY ORDAIN AS FOLLOWS
SECTION 1. Chapter 18 02 of the Bremerton Municipal Code entitled "City Fire
Code" is hereby amended to read as follows
Chapter 18.02
CITY FIRE CODE
18.02.010 PURPOSE.
The purpose of the City Fire Code is to prescribe regulations consistent with nationally
recognized good practice for safeguarding to a reasonable degree of protection the life and
property of our citizens from the hazards of fire and explosion arising from the storage, handling
and use of hazardous substances, materials and devices, and from conditions hazardous to life or
property in the use or occupancy of buildings or premises It is understood the fire code and its
referenced documents are to provide a framework for the fire and life safety requirements to
protect the citizens and emergency responders from the predictable situations the codes regulate
Therefore under no circumstance shall any space, occupancy or other location be allowed to be
occupied or otherwise utilized, whether temporarily or permanently, without the Fire Code
Official's written authorization
18.02.020 FIRE CODE - ADOPTED.
In accordance with Chapter 19 27 RCW, the International Fire Code, 2089 - 2012 Edition,
published by the International Code Council, Inc., together with any additions, deletions, and
exceptions currently enacted or as may be amended from time to time by the State of
1
2012 International Fire Code Adoption
Washington through its Building Code Council pursuant to Chapter 51 -54 of the Washington
Administrative Code ( "WAC "), and International Fire Code, 2N9 - 2012 Edition, Appendices B,
C, D, H, and I and4, and as further amended in this chapter, is hereby adopted and incorporated
by this reference
One (1) copy of the International Fire Code is on file with the City's Fire Code Official
18.02.025 AUTHORITY.
The Fire Code Official is authorized to enforce the provisions of the fire code Fire Code
Official shall mean the City of Bremerton Fire Marshal or other City official designated ted by the
City of Bremerton Fire Chief who shall be the formal administrator of the Crty Fire Code
18.02.030 CODE CONFLICTS.
To the extent allowed by RCW 19 27 040, if a conflict exists between the provisions of
the International Fire Code adopted and amended by the Washington State Building Code
Council and the provisions of this chapter, the Bremerton Municipal Code provisions shall
govern
18.02.040 AMENDMENTS TO THE IFC - ADMINISTRATION.
(a) General Authority and Responsibilities - Retained Authority. Section 104 of the
International Fire Code, entitled "General Authority and Responsibilities," is amended by adding
the following new Subsection 104 1 1
Sec. 104.1.1 Retained authority - Additional conditions. The fire -eede
effiefal Code Official retains the authority to impose additional
conditions where the official determines it necessary to mitigate identified
fire protection impacts These conditions may include, by way of example
and without limitation, increased setbacks, use of fire retardant materials,
installation of standpipes, smoke and heat vents, draft curtains, smoke
control, fire sprinkler and fire alarm systems, including temporary
provisions and without limitation such as fire watch, fire department
standby, blocking of roads and additional fire safety inspections
(b) General Authority and Responsibilities - Lot Lines and Setback Lines Section
104 of the International Fire Code, entitled "General Authority and Responsibilities," is amended
by adding the following new Subsection 104 12
Sec. 104.12 Lot lines and setback lines. Notwithstanding the authority of
the fire Bede- effeml Code Official to administer and enforce the fire
code, the €ire cede- effieW Code Official shall have no duty to verify
or establish lot lines or setback lines No such duty is created by this code
and none shall be implied
(c) Permits - Fees Section 105 of the International Fire Code, entitled "Permits," is
amended by adding the following new Subsection 105.1.4.
2
2012 International Fire Code Adoption
Sec. 105.1.4 Fees. The fiFe- eede -offie al Fire Code Official shall prepare a
resolution establislung a schedule of fees, if any, for council consideration,
which fees shall include the cost involved in the processing, issuance, and
renewal of permits and certificates Any fee schedule adopted by
resolution shall govern the fee amount to be assessed for any permit or
certificate and the fire cede effie 4 l 7 ire Code Official shall collect those
fees as a condition to issuance or renewal of any permit or certificate.
Failure to pay for either an original permit or the required renewal within
30 days of the date notice is given, shall result in the City's termination of
the permit or certificate application
(d) Permits - Term Section 105 of the International Fire Code, entitled "Permits," is
amended by adding the following new Subsections, 0 �d - 105 3 6 1
See. 105.1.4 Term. Pefmits and eefhfieates issued in aeoerdanee with dms
eede "I be valid for- a 12 fneWth pefted and are mnewable at the end e
th 12 in Leff
Sec. 105.3.6.1 Unsafe Situations: Actions taken outside of the guidelines
contained within any permit required by section 105 of the IFC shall be
deemed unsafe and shall entitle the fire- eede effieml Code Official to
immediately have all utilities including but not limited to electricity,
water, sewer and gas shut off or otherwise disconnected from the site.
Utilities shall not be restored without the conditions of all required
permit(s) resolved
(e) Board of Appeals Section 108 of the International Fire Code, entitled "Board of
appeals," is amended by substituting Section 108 with the following
Sec. 108 Board of appeals. The City of Bremerton hearings examiner is
designated as the board of appeals in order to hear and decide appeals of
orders, decisions, or determinations made by the fire - eede- effieff
Code Official relative to the suitability of alternate materials, designs, and
methods of construction and appeals of the reasonable application of the
Fire of the building and fire ee Appeals shall
be made as set forth in section 18 02 4-90200 of the Bremerton Municipal
Code
(f) Violation Penalties Section 109 of the International Fire Code, entitled
"Violations," is amended by substituting Subsection 109 3 with the following
Sec. 109.3 Violation penalties. Any person, company or corporation who
violates any provision of this code or fails to comply with any of its
requirements or who erects, constructs, alters, or repairs a building or
structure or building system in violation or inconsistent with of (a) the
approved construction documents, (b) a directive of the fire -sede
3
2012 International Fire Code Adoption
Offs Fire Code Official or (c) a permit or certificate issued under the
provisions of this code, or operates without such permit, shall be subject to
penalties as set forth in section 18 02 4SO- of the Bremerton Municipal
Code or as otherwise provided by law
(g) General Definitions Section 202 of the International Fire Code is amended to add
the following general definitions
APWA is the American Public Works Association
AWWA is the American Water Works Association
FIRE FLOW. A measure of the sustained flow of available water for
firefighting t�a specific building or within a specific area at 20 pounds -
per- square -inch residual pressure
FIRE WALL. An approved wall of not less than 4 hour fire - resistive
construction with no openings, which extends vertically from the
foundation to terminate in a parapet not less than 30 inches above the roof,
and which extends horizontally to the furthest projection of any portion of
the building or r to a point 30 inches beyond the intersecting exterior wall,
whichever is furthest As an alternative to the horizontal requirements,
such fire wall may be extended a minimum of 30 inches along both sides
of the intersecting exterior wall provided there are no projections beyond
the intersecting exterior wall
LIFE SAFETY RESCUE ACCESS. Unobstructed access to all floor
levels and each roof level of a building on not less than 20 percent of the
building perimeter by utilizing a 35 foot ladder An alternate method
would be at least 1 stairway enclosure with exit doorways from each floor
level and with a door opening onto each roof level which conforms to the
requirements of the International Building Code
OCCUPANCY CLASSIFICATION RESIDENTIAL GROUP R.2. R 2
PRIVATE HYDRANT is a fire hydrant situated and maintained to
provide water for firefighting purposes with restrictions as to use
PUBLIC HYDRANT is a fire hydrant situated and maintained to provide
water for firefighting purposes without restrictions as to use for that
purpose and is accessible for immediate use at all times
REMODEL is the butldmg or- buildings in question will have more
50
improved and/or- other-wise r-eeanditioned or-, two or- mer-e majef building
4
2012 International Fire Code Adoption
systems iWr-eved or- ether-wise r-eeendittened widmn any 60 month h
pefted Major- building systems inelude but are not lffmted to- Wat-e.r-,-
Sewer-, or t plumbing, b 1 cEtae•,1 uy n r F,. ndat.,.,,
, , vcn°rPrairr°inbz E , , ,
18.02.050 AMENDMENTS TO THE INTERNATIONAL FIRE CODE -
SECTION 311, VACANT PREMISES.
The following local amendments to Section 311 of the International Fire Code, entitled
"Fire Protection," are adopted and incorporated into the International Fire Code
(a) Vacant Premises - Fire Protection Systems Section 311 of the International Fire
Code, entitled "Vacant Premises," is amended by substituting Subsection 3112 2 with the
following
Sec. 311.2.2 Fire protection. Fire alarm, sprinkler, and standpipe systems
shall be maintained in an operable condition at all times
Exception: If, in the opinion of the fire - ee a°�alFire Code Official
the premises (a) has been cleared of all combustible materials and debris,
(b) is of the type of construction with sufficient fire separation distance so
as to not create a fire hazard, (c) has been secured to prohibit entry by
unauthorized persons, and (d) has buildings that will not be heated,
potentially exposing fire protection systems to freezing temperatures, then
the fire - eede- e€fsW Code Official may allow fire alarm and sprinkler
systems to be placed out of service and may allow standpipes to be
maintained as dry systems (without an automatic water supply)
18.02.055 AMENDMENTS TO THE INTERNATIONAL FIRE CODE -
CHAPTER 4, EMERGENCY PREPAREDNESS.
The following local amendments to Chapter 4 of the International Fire Code, entitled
"Emergency Planning and Preparedness," are hereby adopted
Sec. 401.9 Hardwired Telephones. All occupancies with hardwired
telephones, new and existing, when 911 is dialed shall correctly report the
address of the actual location dialed from
18.02.060 AMENDMENTS TO THE INTERNATIONAL FIRE CODE -
CHAPTER 5, FIRE SERVICE FEATURES.
The following local amendments to Chapter 5 of the International Fire Code, entitled
"Fire Service Features," are adopted and incorporated into the International Fire Code
(a) Fire Service Features - Fire Apparatus Access Roads Section 503 of the
International Fire Code, entitled "Fire Apparatus Access Roads," is hereby adopted
(b) Fire Apparatus Access Roads — Where Required Section 503 of the International
Fire Code entitled "Fire Apparatus Access Roads," is amended by adding the following new
Subsection 503 14
5
2012 International Fire Code Adoption
Sec. 503.1.4 Residential access. For development of Group R -3
occupancies accessed from a fire apparatus access road that does not meet
specifications set forth In Seaton 503 and Appendix D. and automatic fire
sprinkler system is required in compliance with BMC 18 02080(n)
Exception: All residential development on lots that are existing or have
received preliminary subdivision approval prior to December 1, 2013,
unless otherwise required
(bc) Fire Apparatus Access Roads - Dimensions Section 503 of the International Fire
Code, entitled "Fire Apparatus Access Roads," is amended by substituting Subsection 503 2 1
with the following
Sec. 503.2.1 Dimensions. Unless otherwise approved by the Fire Code
Official, following minimum dimensions shall apply for fire
apparatus access roads
1 Fire apparatus access roads shall have an unobstructed width of not
less than 20 feet (6096 mm), except for approved security gates in
accordance with section 503 6 and Appendix D 103 5, and an
unobstructed vertical clearance of not less than 13 feet 6 inches (4115
mm)
2 In the immediate vicinity of any building or portion thereof in
excess of 28 feet in height, the fire apparatus access road shall have an
unobstructed width of not less than 26 feet (7924 mm) and an
unobstructed vertical clearance of not less than 13 feet 6 inches (4115
mm)
3 At least one of the required fire appaFeAus aeeess roads shall be
leeated a minimum of 15 feet and a maxifaum of 25 feet fr-em ea
building on the premises and shali be positioned parallel te one entire
of eaeh building The measuremen4 for- this requirement shall be taken
VALVr
h t
&ef °„tew wa ll o f the building t o th nearest e . f th fi,.°
11 Vlll 11V
(edd) Fire Apparatus Access Roads - Bridges and Elevated Surfaces. Section 503 of the
International Fire Code, entitled "Fire Apparatus Access Roads," is amended by substituting
Subsection 503 2 6 with the following
Sec. 503.2.6 Bridges and elevated surfaces. Where a bridge or an
elevated surface is part of a fire apparatus access road or likely to be used
during emergency operations, including EMS, the bridge or elevated
surface shall be constructed and maintained in accordance with
specifications established by the fire - eede- e€€etal Code Official and
the City's public works director, or their designees, at a minimum,
6
2012 International Fire Code Adoption
however, the bridge or elevated surface shall be constructed and
maintained in accordance with AASHTO Standard Specifications for
Highway Bridges Bridges and elevated surfaces shall be designed for a
live load sufficient to carry the imposed loads of a 35 or more ton fire
apparatus, the total imposed load to be determined by the €rye -eede
ef€etal Code Official Vehicle load limits shall be posted at both
entrances to bridges when required by the ire eede effieffg Code
Official Where elevated surfaces designed for emergency vehicle use are
adjacent to surfaces which are not designed for that use, approved barriers
or approved signs, or both, shall be installed and maintained, if required
by the fire- eede effietal Code Official
(de) Fire Apparatus Access Roads - Marking Section 503 of the International Fire
Code, entitled "Fire Apparatus Access Roads," is amended by substituting Subsection 503 3 with
the following
Sec. 503.3 Marking. Fire apparatus access roads shall be marked
whenever necessary to maintain the unobstructed mimmum required width
of roadways as determined by the Fire Code Official Subject to the fire
eede effieffit Code Official prior written approval, marked fire
apparatus access roads, or "fire lanes" as defined in section 502.1 of the
code, may be established or relocated at the time of plan review, pre -
construction site inspection, and/or post construction site inspection as
well as any time during the life of the occupancy Only those fire
apparatus access roads established by the €ire- eede effieig Code
Official can utilize red marking paint and the term "fire lane " Once a fire
lane is established it shall be maintained in a clean and legible condition at
all times or repair /replaced to maintain visibility. Fire lanes shall be
marked as directed by the fire - eede- ef€e}al Code Official with one or
more of the following types of marking
503.3.1 Type 1. The following shall apply to Type 1 marking
1 Curbs shall be identified by red traffic paint with a 6 inch wide
stripe on the top and front, extending the length of the designated fire lane
2 Rolled curbs shall be identified by red traffic paint with a 6 inch
wide stripe on the curb, extending the length of the designated fire lane
3 Lanes without curbs shall be identified by red traffic paint with a 6
inch wide stripe on the pavement, extending the length of the designated
fire lane
4 The words "NO PARKING - FIRE LANE" shall be in 3 inch
stroke white letters 18 inches in height, and placed 8 inches measured
perpendicular from the red paint stripe on the pavement In most cases,
7
2012 International Fire Code Adoption
both sides of the access road shall be marked Where long drives are to be
marked, the repetitions shall alternate sides of the drive
503.3.2 Type 2. The following shall apply to Type 2 marking
4- In addition to the requirements for Type 1 marking, Type 2
marking shall also include the addition of metal signs stating "NO
PARKING - FIRE LANE" to be installed at intervals or locations
designated by the fire - cede- effieml Code Official The signs shall be
approximately 12 inches in width and 18 inches in height and have red
letters on a white background. Metal signs shall be installed on either 2
inch metal pipes, for private property, or treated 4 inch by 4 inch wood
posts, for public property, and shall be located so that the bottom of the
sign is a minimum of 7 feet above the curb Where fire lanes are adjacent
to buildings or structures and when approved or directed by the fire Bede
effi Fire Code Official the signs may be placed on the face of the
building or structure
503.3.3 Type 3. The following shall apply to Type 3 marking
4- Where directed by the fire- eede effwwl Code Official specific
areas shall be designated and those areas are to be marked with diagonal
striping across the width of the fire lane Diagonal marking shall be used
in conjunction with painted curbs and/or edge striping and shall run at an
angle of 30 to 60 degrees from one side to the other These diagonal lines
shall be in red traffic paint, parallel with each other, at least 6 inches in
width, and 24 inches apart Lettering shall occur as with Type 1 marking
503.3.4 Street or Road Signs. Street or road signs shall be provided for
all private and public roads All private street and road signs shall be
designed and installed to meet public road sign standards as set by the City
of Bremerton Street Department, any expense shall be the responsibility of
the property owner New street and road signs shall be posted within 30
days after receiving approval from the City of Bremerton Engineering
Department
503.3.5 Alternate materials and methods. The fire- eede effwml
Code Official may modify, on a case -by -case basis, any of the marking
provisions in this subsection 503 3 where practical difficulties exist
Modification requests shall be submitted in writing to the ire -eede
effie+al Code Official setting forth a suggested alternative
(e) Fire Appafatus Aeoess Roads Seehen 503 ef the latemattenal Fire Cede, efAid
"Fife AppanAus Aeoess Roads," is amended by adding the fellewing new Subseehen 503 7
8
2012 International Fire Code Adoption
503.7 Residential Dr-ivewayMr-ivate Read Aeeess and SpAnIde
will b e 9 if a m side„ +,,,l fire s fAde. system i i nstalled i eaeh a
stmetufe-
(f) Access to Building Openings and Roofs - Required Access Section 504 of the
International Fire Code, entitled "Access to Building Openings and Roofs," is amended by
substituting Subsection 504 1 with the following
Sec. 504.1 Required access. The following points of access must be
provided
1 Exterior doors and openings required by this code or the
International Building Code shall be maintained readily accessible for
emergency access by the fire department
2 Each tenant space provided with a secondary exit to the exterior or
exit corridor shall be provided with tenant identification by business name
and/or address Letters and numbers shall be posted on the
comdor /exterior side of the door, be plainly legible, and shall contrast
with their background
3 An approved access walkway shall be provided to connect fire
apparatus access roads to exterior openings
4 All rescue windows shall be accessible by a 35 -foot ground
extension ladder placed so that the inclination of the ladder does not
exceed 70 degrees An area of discharge, 36 inches in all directions around
the base of the ladder, shall be provided Ladders and associated areas of
discharge shall be located within the property lines
5 All occupancies shall be required to provide approved life safety
rescue access, as defined in section 902 of this - eede of the
International Building Code or the International Residential Code as
applicable
in question will have fner-e than 0
wAin any 60 menth time pened Major building systems inelude but ar-R
not lifnited te water-, sewer-, stefm, or- other- plumbing, eleetfirml, ,
Exeeptions:
9
2012 International Fire Code Adoption
(g) Premises Identification. Section 505 of the International Fire Code, entitled
"Premises Identification," is amended by adding the following new Subsection 505 1 1
505.1.1 Address numbers for Commercial Buildings. Address numbers
for commercial buildings shall be 12" and contrast with the background
Individual unit/suite or space numbers or letter shall be 6" in size and
contrasting with the background and visible from the approach side or
angle
Housing developments which contain 100 or more dwelling units which
alley ways are or may be used for access to dwelling units shall have 4"
mimmum house numbers including street designation included The street
designation may be a smaller size, but no less than 2" in size
, 1234.
Example Washington Aven
(h) Fire - etee4k6n Water- upplievs - Existing Non -eenf „ u.,d Seetten 507
ef the Wemmieaal Fire Code, entitled ' Tim Pfeteetten Water- n is amended te add
new Subseetten 507 1 1 as follows
See. 507.1.1 Existing non eonfer-ming hydrants. At sueh time as
existing hydmat, whieh does net eeafimm te the requirements and
> > it shall be Feplareed with a hydfant
that does eeafefm te the standaMs and requirements of this see4ten
(th) Fire Protection Water Supplies - Where Required Section 507 of the International
Fire Code, entitled "Fire Protection Water Supplies," is amended by substituting Subsection
507 5 1 with the following
See. 507.5.1 Where required. All buildings or structures shall be located
so that there is at least 1 hydrant within 150 feet, and no portion of the
building or structure is more than 300 feet from a hydrant, as measured by
an approved route
Exceptions:
1 For Group R -3 and Group U occupancies the distance required
shall be 600 feet (183 m)
10
2012 International Fire Code Adoption
2 For buildings equipped throughout with an approved automatic
sprinkler system installed in accordance with section 903 3 1 1-01
903 3 12, or other approved fire protection system, the distance
requirement shall be 600 feet (183 m)
(1) Fire Protection Water Supplies - Existing Non - conforming Hydrants Section 507
of the International Fire Code, entitled "Fire Protection Water Supplies," is amended to add a
new Subsection 507 5 7 as follows
Sec. 507.5.7 Existing non - conforming hvdrants. At such time as an
existing hydrant, which does not conform to the requirements and
standards of this section, is replaced, it shall be replaced with a hydrant
that does conform to the standards and requirements of this section
�) Fire Protection Water Supplies - Installation Requirements. Section 507 of the
International Fire Code, entitled "Fire Protection Water Supplies," is amended by substituting
Subsection 507 5 -7 5 8 with the following
Sec. 507.5.78 Installation requirements. All fire hydrants shall be
installed in accordance with the specifications established by the fire -eede
effieml Fire Code Official and the Director of Public Works and Utilities,
or his or her designee, or at a mimmum, in accordance with the currently
adopted NFPA, APWA, or AWWA standards In addition, unless
modified by written decision of the ire eede- effeff Oire Code Official
the following requirements shall apply to all building construction
projects
1 All fire hydrant piping, valves, and related appurtenances shall be
approved by the City's public works department
2 The fire hydrant installation and its attendant water system
connection shall conform to the City's specifications and design and
construction standards
3 An auxiliary gate valve shall be installed at the main line tee to
permit the repair and replacement of the hydrant without disruption of
water service
4 All hydrants shall be plumb, plus or minus 3 degrees, to be set to
finished grade with the bottom flange 2 inches above the ground or curb
grade and have no less than 36 inches in diameter of clear area around the
hydrant for the clearance of hydrant wrenches on both outlets and the
operating nut
11
2012 International Fire Code Adoption
5 The largest port shall face the most likely direction of approach
and location of the fire apparatus while pumping as determined by the fife
cede -e€f eW Fire Code Official Distance from the pumper port to the
street curb shall be no further than 10 feet
6 The lead from the service main to the hydrant shall be no less than
6 inches in diameter Any hydrant leads over 50 feet in length from the
water main to hydrant shall be no less than 8 inches in diameter
7 All hydrants installed in single family residential areas shall be
supplied by not less than 6 inch mains and shall be capable of delivering
1,000 gpm fire flow over and above average maximum demands at the
farthest point of the installation except with fire- eede effieW Code
Official approval and the home is installed with a fire sprinkler system in
accordance with this code
8 All hydrants shall have at least 5 inch minimum valve openings,
"O" ring stem seal, two 2 -1/2 inch national standard thread hose ports, one
4 -1/2 inch steamer port with national standard threads or otherwise
determined by the fire cede efi Code Official In addition, all
hydrants shall meet AWWA standards for public hydrants and be of a type
approved for use in the City by the City's public works department In
addition, all hydrants shall be equipped with a 5 inch Storz adapter on the
steamer port and, when required by the fire - Bode- e€fieW Code
Official locking Storz caps
9 All pipe shall meet the City standards as determined by the public
works department Piping located entirely within private property and
maintained by the property owner shall meet the requirements and be
approved by the fire - eede- effieW Code Official The fire eede
e€f ratal Code Official may approve any piping material that has been
tested and approved by a nationally recognized testing laboratory
10 The maximum distance between hydrants in single family use
district zones shall be 600 feet
11 The maximum distance between hydrants in commercial,
industrial, and apartment (including duplex) use zones shall be 300 feet
12. Lateral spacing of hydrants shall be predicated on hydrants being
located at street intersections
13 The appropriate water authority and the fire department shall be
notified in writing of the anticipated date the hydrant installation and its
attendant water connection system will be available for use
12
2012 International Fire Code Adoption
14. All hydrants shall meet City of Bremerton Hydrant Identification
standards as established by the €ire- sede e€sW Code Official
(k) Fire Protection Water Supplies - Notification Section 507 of the International
Fire Code, entitled "Fire Protection Water Supplies," is amended by adding a new Subsection
507 6 as follows
See. 507.6 Notification. The owner of property on which private hydrants
are located and the public agencies that own or control public hydrants
must provide the fire- eede effietal Code Official with the following
written service notifications
Sec. 507.6.1 In- service notification. The fire Bede- ef€etd Code
Official shall be notified when any newly installed hydrant or main is
placed into service
Sec. 507.6.2 Out -of- service notification. Where any hydrant is out of
service or has not yet been placed in service, the hydrant shall be
identified as being out of service and shall be appropriately marked as out
of service, by a method approved by the fire - eesral Code
Official
(1) Fire Protection Water Supplies - Dead -End Mains Prohibited Section 507 of the
International Fire Code, entitled "Fire Protection Water Supplies," is amended by adding a new
Subsection 507 7 as follows
Sec. 507.7 Dead -end mains prohibited. When appropriate, all water
mains in any project shall be looped
(m) Fire Protection Water Supplies - Building Permit Requirements Section 507 of
the International Fire Code, entitled "Fire Protection Water Supplies," is amended by adding a
new Subsection 507 8 as follows
Sec. 507.8 Building permit requirements. No building permit shall be
issued until all plans required by this section have been submitted and
approved in accordance with the provisions of this section No
combustible construction beyond the foundation shall be allow ed permitted
until all hydrants and mains required by this section are in place and
approved
(n) Fire Department Access to Equipment - Identification Section 509 of the
International Fire Code, entitled "Fire Department Access to Equipment," is amended by
substituting Subsection 509 1 with the following
Sec. 509.1 Identification. The following identification requirements shall
apply to access to equipment
13
2012 International Fire Code Adoption
1 Fire protection equipment and fire hydrants shall be clearly
identified in an approved manner to prevent parking and/or other
obstructions
2 Entrances to rooms containing controls for air - conditioning
systems, sprinkler risers and valves, or other fire detection, suppression, or
control elements shall be identified for the use of the fire department
3 Approved signs are required to identify fire protection equipment
and equipment location Signs shall be constructed of durable materials,
permanently installed, and readily visible
4 All fire department connections shall have a sign approved by the
fire- Bede- effistal Code Official The sign shall specify the type of
water -based fire protection system it serves and the building areas served
5 All main control valves and sectional valves for water -based fire
protection systems shall have a sign specifying what the valves control
6 All sprinklers and standpipe risers shall have signs to indicate
which type of water -based fire protection system is being used
18.02.070 AMENDMENTS TO THE INTERNATIONAL FIRE CODE -
SECTION 901, GENERAL.
The following local amendments to Section 901 of the International Fire Code, entitled
"General," are adopted and incorporated into the International Fire Code
(a) Fire Protection Systems - Scope Section 901 of the International Fire Code,
entitled "General," is amended by substituting Subsection 901 1 with the following
Sec. 901.1 Scope. The provisions of this chapter shall apply to all
occupancies and buildings, shall specify where fire protection systems are
required, and shall apply to the design, installation, inspection, operation,
testing, and maintenance of all fire protection systems, however, nothing
contained in this chapter shall diminish or reduce the requirements of any
duly adopted building codes, including state and local amendments, or
other City ordinances, resolutions, or regulations In the event of any
conflict in requirements among these codes, ordinances, resolutions, or
regulations, the more stringent provision shall apply
(b) Fire Protection Systems - Alterations, Repairs, and Additions Section 901 of the
International Fire Code, entitled "General," is amended by adding a new Subsection
901 1 1 9014 2.1 as follows:
14
2012 International Fire Code Adoption
See. 901 Ak ,tion" a nd a dditi ons. The previsions „� +t„"
subseetten shaM apply if-, the building er- buildings in queshen will h
fl-n-e-ve than 0
r-emedeled >
60 fneath time pened Major- building systems melude but are not lifnited
to > > Steffn, > Eleetfteal, HVAG,
area >
the requirements of dms seetten, the entire building will then be required te
eemply with this see4eft--
" General," is amended by adding a new Subseehen 901 1 2 as fellews
See. esfi ,
901.4.2.1 Fire Alarm Systems no longer required by the Fire Code or an y
other applicable code or that were not installed as an alternative method to
other code provisions may, after the wntten approval of the Fire Code
Official, may be discontinued and removed The removal of the system
shall be pursuant to the regulations of Washington State Department of
Labor and Industnes Electncal Division as applicable, but as a minimum
shall require the removal of visible winng, fire alarm panels and other
related visible devices The Fire Alarm System may be maintained as a
local system rather than be removed Fire alarm systems that remain in
service, either monitored or local, shall be inspected, maintained and
tested per the International Fire Code, NFPA 72 and this code
(d) Fire Pmteetten Systems Standffds Seetien 901 ef the intefflatienal Fire Code,
efAided "Genera4," is amended by substittAing Subseetten 9016 1 and Table 901.6.1 wM th-e
fig
.. ,
taspe tested a nd „„ n t a ea i n ,.,.,,,.,r ,,,A the National F ire P fe ,
Asseeiation ("NFPA") standafds listed in Table 9016.1 below.
15
2012 International Fire Code Adoption
T 901 4.4
FIRE PROTECTION SYSTEM
MAINTENANCE STANDARDS
SYSTE14 STANDARD
Car-bon dioxide fire ATFPA P
extifigHISIHfig systems
Clean agent fire N D� A 0"
ext1Hj,%1S1*ffg systems
Dr ehemtt7al fire � 1
ex4faguislung systems
Effiefgeney pew N DA 110 B,
Systems NF PA 144
Fire alann systems ATL FPA 72
Fire doer-s. AT1 x�FPA 80
NF PA A 1
r�rrrr 1 r
r
L7�
Halogenate fie- ATL'D rrrPA 12A
extifiguishing systems
Smoke eei#Fel systems AT7; D A 92A
UndeFgetmd fire lines AT F PA 25
and hydmats
Water- based fire NFPA 2-5
pmteetten-systeffis
AT rrFPA 50
Wet ehemteal fire ATFP A 7 A
rrtTZ 1 rrrrr
fe} cZ Fire Protection Systems - Records Section 901 of the International Fire Code,
entitled "General," is amended by substituting Subsection 9016 2 with the following
Sec. 901.6.2 Records. Records of all system inspections, tests, and
maintenance required by the referenced standards shall be maintained on
the premises for a mimmum of 3 years A copy of each inspection, test, or
maintenance record shall be forwarded to the fire- eede effietd Code
Official, by an =roved electronic method of delivery, within 30 seven
(7 ` s -r ten 0 0) business days of the date the inspection, test, or
maintenance occurred All fire protection systems taken off line or out of
service, and subsequently returned to service shall be reported to the Fire
Code Official's office by an gpproved method of delivery
16
2012 International Fire Code Adoption
A copy of all system inspections shall be maintained in a three -ring binder
or other folder type cover and located at the fire alarm main panel or other
approved location
(f) Fire D..e teetl9n Syste to ffl t ion l Fire redo
enfifled n " is amended by adding the fellewing definitions
FIRE AREA. The total area ffem all floors enelesed by the outennest
an e xit to a he w a y, sh be , eluded in the fire
.' a r e a e
FIRE FLOW. A fneasufe of the sustained flow of available watff-fer-
firefighting at a ee.fie b ui ld ing a . .. ee.fie a r e a at 20 p .,d
WALL ,,, appr w a ll tha n t, � t...e
. An �J' Sr1TiO�R�1 III'G'TG7S7lTPG
eenstmebon with no openings
Caundation to tefminate in a parapet not less than 30 inehes above the f
the e building e.. to „ poi 30 . «el.e beyond the inter- seeting e..te 11
v
7
seeh fire wall may be extended a fnimmum of 30 mehes along beth sides
of the inteFseeting exteaeF 7 pr-evided there are no p"eetiens beyond
the ...te.- seet. «e e..tewer- w
LIFE SAFETY RESCUE ACCESS. Unobstfueted aeeess to all fleofi!
levels
and e.,e1, o f level of bu o n ot less tha 20 « t o f4 he
bu ld r ete« by u .. 35 fe et l.,dde An l tefnat tl.. d
weuld be at least 1 stair-way enelesufe wA exit deer-ways &em eaeh floof
level and with a door- opening onto eaeh mof level whieh eenfefms to the
18.02.080 AMENDMENTS TO THE INTERNATIONAL FIRE CODE -
SECTION 903, AUTOMATIC SPRINKLER SYSTEMS.
The following local amendments to Section 903 of the International Fire Code, entitled
"Automatic Sprinkler Systems," are adopted and incorporated into the International Fire Code
(a) Automatic Sprinkler Systems - Where Required Section 903 of the International
Fire Code, entitled "Automatic Sprinkler Systems," is amended by substituting Subsection 903 2
with the following
Sec. 903.2 Where required. Approved fire sprinkler systems shall be
installed throughout buildings and structures as follows
17
2012 International Fire Code Adoption
I In all new buildings and structures without adequate fire flow as
required by this code
Exception: Group U Occupancies and remodels and replacements to
existing Group R -3 residential structures as defined in the International
Residential Code regardless of the requirements of Chapter 5 of the
International Fire Code
2 All new or- r-efaedeled- buildings and structures with a gross floor
area of 10,000 or more square feet (929 M 2 ), or where this code provides a
more restrictive floor area requirement, and shall be provided in all
locations or where described by the International Fire CodetIms
Exception: Spaces or areas in telecommunications buildings used
exclusively for telecommunications equipment, associated electrical
power distribution equipment, batteries, and standby engines, provided
those spaces or areas are equipped throughout with an automatic fire alarm
system and are separated from the remainder of the building by a wall
with a fire - resistance rating of not less than 1 hour and a floor /ceiling
assembly with a fire - resistance rating of not less than 2 hours
3 Where this code requires the installation of an automatic sprinkler
system to protect an occupancy within an otherwise non - sprinkled
building, then automatic sprinkler protections will be required throughout
the entire buildin unless otherwise authorized by the fire - Bede- ef€eta}Fire
Code Official
4 Only 4 hour area separation walls without openings shall constitute
separate buildings to allow for a fire sprinkler exemption When thAs
exemption is tAilized, the sepam4ten wall must sepafate eseupaney types
(b) Automatic Sprinkler Systems - Where Required Section 903 of the International
Fire Code, entitled "Automatic Sprinkler Systems," is amended by substituting Subsection
903 2 1 with the following
Sec. 903.2.1 Group A. An automatic sprinkler system shall be provided
throughout buildings and portions thereof used as Group A occupancies as
provided in this section For Group A -1, A -2, A -3, and A -4 occupancies,
the automatic sprinkler system shall be provided throughout the entire
building For Group A -5 occupancies, the automatic sprinkler system shall
be provided in the spaces indicated in 903 2 15
(c) Automatic Sprinkler Systems - Where Required. Section 903 of the International
Fire Code, entitled "Automatic Sprinkler Systems," is amended by substituting Subsection
903 2 1 1 with the following -
18
2012 International Fire Code Adoption
Sec. 903.2.1.1 Group A -1. An automatic sprinkler system shall be
provided for Group A -1 occupancies where one of the following
conditions exists
1 The gross fire area of the building exceeds 10,000 square feet
2 The fire area has an occupant load of 300 or more
3 The fire area is located on a floor other than the level of exit
discharge
4 The fire area contains a multi- theater complex
5 Dance halls where the total gross floor area exceeds 5,000 square
feet (465 m 2 )
(d) Automatic Sprinkler Systems - Where Required Section 903 of the International
Fire Code, entitled "Automatic Sprinkler Systems," is amended by substituting Subsection
903 2 12 with the following
Sec. 903.2.1.2 Group A -2. An automatiC sprinkler system shall be
provided for Group A -2 occupancies where one of the following
conditions exists
1 The fire area of the building exceeds 5,000 square feet
2 The fire area has an occupant load of 100 or more
3 The fire area is located on a floor other than the level of exit
discharge
(e) Automatic Sprinkler Systems - Where Required Section 903 of the International
Fire Code, entitled "Automatic Sprinkler Systems," is amended by substituting Subsection
903 2 13 with the following
Sec. 903.2.1.3 Group A -3. An automatic sprinkler system shall be
provided for Group A -3 occupancies where one of the following
conditions exists
1. The fire area of the building exceeds 10,000 square feet
2 The fire area has an occupant load of 300 or more
3 The fire area is located on a floor other than the level of exit
discharge
19
2012 International Fire Code Adoption
Exception: Areas used exclusively as participant sports arena areas where
the main floor area is located at the same level as the level of exit
discharge of the main entrance and exit
(f) Automatic Sprinkler Systems - Where Required Section 903 of the International
Fire Code, entitled "Automatic Sprinkler Systems," is amended by substituting Subsection
903 2 14 with the following
Sec. 903.2.1.4 Group A -4. An automatic sprinkler system shall be
provided for Group A -4 occupancies where one of the following
conditions exists
1 The fire area of the building exceeds 10,000 square feet
2 The fire area has an occupant load of 300 or more
3 The fire area is located on a floor other than the level of exit
discharge
Exception: Areas used exclusively as participant sports arena areas where
the main floor area is located at the same level as the level of exit
discharge of the main entrance and exit
Fire Code, entitled "AtAemahe Spfink4er- Systems," is amended by substitWing Subseette.n.
> >
(13g) Automatic Sprinkler Systems - Where Required Section 903 of the International
Fire Code, entitled "Automatic Sprinkler Systems," is amended by substituting Subsection
903 2 3, Group E, with the following
Sec. 903.2.3 Group E. An automatic sprinkler system shall be provided
for Group E occupancies as follows
1 Throughout all buildings with a group E fire area
)-,
20
2012 International Fire Code Adoption
build Vl VN k „ gs
afea stf-uetmeAly remodeled, improved er- other-wise r-eeonEhtiened and/9
witMo any 60 faefith time pefted Major- building systems inelude but are
area separatten walls shall define separeAe buildings r-egaF&ag spn
r-equir-ements
( }h) Automatic Sprinkler Systems - Where Required Section 903 of the International
Fire Code, entitled "Automatic Sprinkler Systems," is amended by substituting Subsection
903 2 4, Group F -1, with the following
Sec. 903.2.4 Group F -1: An automatic sprinkler system shall be provided
throughout all buildings containing a Group F occupancy where one of the
following conditions exists
1 Where the fire area of the building exceeds 10,000 square feet, or
2 Where a Group F -1 fire area is located more than three stones
above grade
(ti) Automatic Sprinkler Systems - Where Required Section 903 of the International
Fire Code, entitled "Automatic Sprinkler Systems," is amended by substituting Subsection
903 2 7 with the following
See. 903.2.7 Group M. An automatic sprinkler system shall be provided
throughout all buildings containing a Group M occupancy where one of
the following conditions exists*
1 Where the fire area of the building exceeds 10,000 square feet, or
2 Where a Group M fire area is located more than three stones above
grade
(kl) Automatic Sprinkler Systems - Where Required Section 903 of the International
Fire Code, entitled "Automatic Sprinkler Systems," is amended by substituting 94seetlen
903 2 ...,a, t h e f ll,,w amending Subsection 903 2 8 and by adding Subsections 903 2.8 3
and 903 2 8 4 as follows
21
2012 International Fire Code Adoption
See. 903.2.8 Group R. An outemane &pnnkkj- sys�m installed i
Sec. 903.2.8.4-3 Existing Group R -1 and R -2 buildings shall install a full
fire sprinkler system when any one of the following occurs
(1) A fire occurs which migrates from the unit of origin to involve a
neighboring unit
(2_) Two or more separate fires occur, which require a fire department
response, in the same complex within a two year span
Sec. 903.2.8.34 Sprinkler heads in kitchens shall be installed (on the
ceiling) with at least one sprinkler head no more than 4 feet out from the
front of the stove top
See. 903.2.8.3 All nefmally habitable spaees shall be eever-ed r-egaFdless e
size -
(1k) Automatic Sprinkler Systems - Where Required Section 903 of the International
Fire Code, entitled "Automatic Sprinkler Systems," is amended by substituting Subsection
903 2 9 with the following
Sec. 903.2.9 Group S -1. An automatic sprinkler system shall be provided
throughout all buildings containing a Group S -1 occupancy where one of
the following conditions exists
1 Where the fire area of the building exceeds 10,000 square feet, or
2 Where a Group S -1 fire area is located more than three stones
above grade
Wemat4eaal Fire Code, efAided "Autematte Spnak4ef Systems," is amended by adding the
following new subseetleft 903 2 9 3-
S ee. - .2: 9- 3. Spee'ml&t- e u se - ;'; c rn vro- the eeeupant, c v rs mr
or- use of the building or- stemge eeffHnedity has not been detefmined
spnpAdef system shall be designed and installed in aereManee with
f " n
i The destgn area shall be net less than 5,600 squafe feet )
2 The density s1W1 be no t less tha a,.,. fie elffilss- n / n on
22
2012 International Fire Code Adoption
pallets, eneapsWated eenunedittes on wood with no solid, slafted, or- wir-e
shelving, inesh up -to
lar 20 fM in height
pr ovide
appFeving of the point and dead leads
(el) Automatic Sprinkler Systems Section 903 of the International Fire Code, entitled
"Automatic Sprinkler Systems," is amended by substituting Subsection 903 3 1 1 1 with the
following
Sec. 903.3.1.1.1 Exempt locations. When approved by the Fire Code
Official automatic sprinklers shaH - may not be required in the following
rooms or areas where such rooms or areas are protected with an approved
automatic fire detection system in accordance with Section 907 2 that will
respond to visible or invisible particles of combustion Sprinklers shall not
be omitted from any room merely because it is damp, of fire - resistance
rated construction, or contains electrical equipment
1. Any room where the application of water, or flame and water,
constitutes a serious life or fire hazard
2 Any room or space where sprinklers are considered undesirable
because of the nature of the contents, when approved by the ire -eede
of eW Fire Code Official
3 Generator and transformer rooms separated from the remainder of
the building by walls and floor /ceiling or roof/ceiling assemblies having a
fire - resistance rating of not less than 2 hours
4 In rooms or areas that are of noncombustible construction with
wholly noncombustible contents
(em) Automatic Sprinkler Systems Section 903 of the International Fire Code, entitled
"Automatic Sprinkler Systems," is amended by substituting Subsection 903 3 12 1 with the
following
Sec. 903.3.1.2.1 Balconies and decks. Sprinkler protection shall be
provided for exterior balconies, decks and ground floor patios of dwelling
units
(n) Automatic Sprinkler Systems Section 903 of the International Fire Code,
entitled "Automatic Sprinkler Systems," is amended by substituting Subsection 903 3 13
with the following
23
2012 International Fire Code Adoption
i
Sec 903.3.1.3 NFPA 13D Sprinkler Systems. The design of NFPA 13D
fire sprinkler systems shall comply with the flow - through options listed in
NFPA 13D It is eg nerally understood the flow-through _ systems be
interconnected with the domestic plumbing system, sized accordingly, to
provide adequate turnover of potable water as well as the minimum
required density required by that of NFPA 13D
Sec 903 3.1.3.1 Design. In addition to the general design/coverage of the
NFPA 13D fire sprinkler system a single sidewall, or other approved
design shall be installed above the man door between the habitable space
and the attached garage When the garage also contains a fuel fired
Upliance the sidewall head if within the listed spacing, will be adequate
coverage for that appliance All habitable Maces and other spaces with the
potential to be occupied are to be covered
_All spaees in exeess ef 10 squar-e feet shall be provided wA spmAder-
eeverage-
(po) Automatic Sprinkler Systems - Installation Requirements Section 903 of the
International Fire Code, entitled "Automatic Sprinkler Systems," is amended by substituting
Subsection 903 3 7 with the following
Sec. 903.3.7 Fire department connection locations. All fire department
connection locations (F D C 's) to automatic sprinklers and/or standpipe
systems shall be located not less than 3 feet, nor more than 10 feet from
the finished edge of an approved fire apparatus access road F D C 's shall
not be located more than 50 feet from a fire hydrant F D C 's and F D C 's
serving sprinkler systems shall not be located on the wall of a building,
unless approved by the fire eede offieW Code Official F D.0 's
serving class 1 or 3 standpipe systems may be located on walls, provided
such walls are of fire resistive or noncombustible construction
Exception: F D C.'s that are not able to be located away from a wall due
to physical restrictions may be located in an area approved by the firee
efifieW Code Official F D C 's shall be installed/located at the front of
the building not less than 18 inches nor more than 36 inches above the
finished grade of an approved fire apparatus access road F D C 's shall
not be obstructed by vehicle parking, carports, garages, refuse storage
containers, fences, landscaping or other obscuring features F D C.'s shall
be provided with tight fitting threaded caps or Knox type lockable caps
(qp) Automatic Sprinkler Systems - Alarms Section 903 of the International Fire
Code, entitled "Automatic Sprinkler Systems," is amended by substituting Subsection 903 4 2
with the following
Sec. 903.4.2 Alarms - Exterior notification. Approved audible alarm
devices shall be connected to every automatic sprinkler system Such
24
2012 International Fire Code Adoption
sprinkler water -flow alarm devices shall be activated by water flow
equivalent to the flow of a single sprinkler of the smallest onfice size
installed in the system Alarm devices shall be water -motor og�or
approved electric bell which operates with water flow and epemted
shall be provided on the exterior of the building in an approved location at
each riser or riser group
Exception: NFPA 13D and NFPA 13R sprinkler systems may utilize an
electrically operated alarm bell on the exterior of the building in an
approved location at each riser or riser group, provided that the electrically
operated alarm bell cannot be silenced during water flow
903.4.2.1 Alarms - Interior notification. Actuation of the automatic
sprinkler system shall actuate interior audible /visual notification
appliances as outlined in NFPA 72 at all exits from all floors or where a
fire alarm system is installed The fire alarm system notification circuits
shall provide the interior notification When a structure exceeds one floor,
a flow switch shall be provided for each floor A flow alarm shall be
identified by floor
Exception: NFPA 13D sprinkler systems do not require interior
audible /visual notification appliances, except if a fire alarm system is
installed, then the fire alarm system notification circuits shall provide the
interior notification
(fq) Automatic Sprinkler Systems Section 903 of the International Fire Code, entitled
"Automatic Sprinkler Systems," is amended by substituting Subsection 903 4 3 with the
following
Sec. 903.4.3 Floor control valves. Approved supervised indicating
control valves shall be provided at the point of connection to the riser on
each floor on buildings /structures four (4) or more stones in height or 30
feet above grade plane as defined in Chapter 2 of the International Fire
Code
18.02.090 AMENDMENTS TO THE INTERNATIONAL FIRE CODE -
SECTION 907, FIRE ALARM AND DETECTION SYSTEMS.
The following local amendments to Section 907 of the International Fire Code, entitled
"Fire Alarm and Detection Systems," are adopted and incorporated into the International Fire
Code
(a) Fire Alarm and Detection Systems - General Section 907 of the International Fire
Code, entitled "Fire Alarm and Detection Systems," is amended to add the following to
Subsection 907 12
25
2012 International Fire Code Adoption
Sec. 907.1.2 Fire Alarm Shop Drawings.
14 A Bremerton Fire depaex Department submittal checklist
15 A copy of the device /zone map.
16 All F*e- alarm system s drawmgs
shall be submitted on no less than
11 -x17 "x24" sized drawings and 44!L an approved scale with a
digital copy of the design in T"W., DWF o r other .,, (PDF
are not aeeeptable -I DF format
(b) Fire Alarm and Detection Systems - Where Required Section 907 of the
International Fire Code, entitled "Fire Alarm and Detection Systems," is amended to add
the following Subsection 907 13 1 as follows:
Sec. 907.1.3.1 All fire alarm systems shall be addressable.
A fully functional annunciator panel shall be placed at the main
entrance (s) and fire sprinkler room(s)
Graphic annunciators shall be utilized in all high -rises and schools
Shielded fire alarm cable shall be utilized as required by the Fire Code
Official
(bcc) Fire Alarm and Detection Systems - Where Required Section 907 of the
International Fire Code, entitled "Fire Alarm and Detection Systems," is amended by substituting
Subsection 907 2 with the following
Sec. 907.2 Where required -new buildings and structures. All new and
remodeled occupancies where the fire area exceeds 400 10,000 square
feet, an approved manual and automatic fire alarm system shall be
provided Approved addr-voss;-Ahwe fire alann systems will be required in
Where automatic
sprinkler protection installed in accordance with Section 903 3 1 1 or
903 3 12 is provided and connected to the fire alarm system, automatic
heat detection requirements of this section may be modified upon specific
approval by the fire- eede effieial Code Official
A prescriptive design will be
1 Automatic smoke detection in common areas, corridors and/or means
of egress areas
2 Automatic heat detection throughout unless covered by a fire spnnkler
system or smoke detection
26
2012 International Fire Code Adoption
Exeeptiens;
spn ak4er - sys te..., a .,, ,lelete l,e„t .iete..t.,.-, f- ---fn the s ,ste.,,
4 These buildings that require 10 or- less fire alam deviees pufsuent
°Il �0 2
In all mmedels ef existing non spfmWed buildings ever- 4,000 square fe
gFess floor- afea when the value of any r-emedel work exemeds 50 per-
ef the building's assessed valuatien
In any nen spfinkled existing building ever- 4,000 square fiaet gross
1 Hallways, eefnder-s, exit passages and all ether- pfimar-y egFess
2 Abeve the fire alafm panel and all amianetater- panels
3 Reems, assembly areas er- ether- spaees w1meh emeeed 400 square fiaet
Exeeptioni Buildings equipped with a fire spnpAder- syst
Graphie annunetater-s shall be utilized in all high Fises and seheels
Shielded fire alann eable shall be utilized as r-eqtHr-ed by the fife eede
D..es.... pt s dete pla..e„.,e..,t shall „t,l T G 6 G G 1
Beam deteeter-s shall be utilized in eemplem designs and eethags in exeess
27
2012 International Fire Code Adoption
" Fire 907 of the Wemational Fire Cede, entided
tenant, add Subseetten 907 10 as follows
See. 907.10 Retronetive R 2 visible notifleation. At the request of
the building ew-ner- shall mplaee an existing audible deviee to an
(d) Fire Alarm and Detection Systems - Duct Smoke Detectors Section 907 of the
International Fire Code, entitled "Fire Alarm and Detection Systems," is amended to repeal
Exeeptien 1 in Subseetion 907 A 1 Th ,,...,en is amended to add the following to Subsection
Subseehen- 907.44 - 13.1 2 r-eads as follows
Sec. 907.4 2.13.1.2 Duct smoke detectors.
3 Duct smoke detectors shall be connected to the building's fire
alarm control panel when a fire alarm system is provided Activation of a
duct smoke detector shall initiate a visible and audible supervisory signal
at a constantly attended location Duct smoke detectors shall not be used
as a substitute for required open area detection
Exception: In occupancies not required to be equipped with a fire alarm
system, actuation of a smoke detector shall activate a visible and an
audible signal in an approved location Smoke detector trouble conditions
shall activate a visible or audible signal in an approved location and shall
be identified as air duct detector trouble
(e) Fire Alarm and Detection Systems - Retroactive R -2 Visible Notification Section
907 of the International Fire Code, entitled "Fire Alarm and Detection Systems," is amended to
add Subsection 907 5 2 3 5 as follows
Sec. 907.5.2.3.5 Retroactive R -2 visible notification. At the request of
the tenant, the building owner shall replace an existing audible device to
an audible /visible device to assist hearing impaired tenants Building
owners are not required to otherwise change or modify fire alarmsystems
if due to design or device placement this option is not feasible
(eD Fire Alarm and Detection Systems - Monitoring Section 907 of the International
Fire Code, entitled "Fire Alarm and Detection Systems," is amended by substituting Subsection
907 3-6_5 with the following
Sec. 907.5 -6.5 Monitoring. Where fire alarm systems are required by this
chapter or by the International Building Code, a U L - listed central
monitoring station in accordance with NFPA 72 shall monitor fire alarm
28
2012 International Fire Code Adoption
systems
Exception: Supervisory service is not required for
1 Single- and multiple- station smoke alarms required by Section
907210
2 Smoke detectors in Group I -3 occupancies
3 Automatic sprinkler systems in one- and two - family dwellings
4 Those existing R -1 and R -2 occupancies that are addressed by
section 18 03 120(a) of the Bremerton Municipal Code
( €g) Fire Alarm and Detection Systems - Testing Prerequisites Section 907 of the
International Fire Code, entitled "Fire Alarm and Detection Systems," is amended by adding a
new Subsection 907.9 1
Sec. 907.9.1 Testing Prerequisites. Upon completion of the installation
or alteration, a satisfactory test of the entire system and its functions shall
be made in the presence of the fife eede- effisml Code Official within
two weeks of completion of installation Prior to the acceptance test,
written documentation shall be provided to the fire department certifying
that the system has been installed and pre- tested in accordance with the
approved plans and specifications
(g1J Fire Alarm and Detection Systems - Location/Secunty Section 907 of the
International Fire Code, entitled "Fire Alarm and Detection Systems," is amended by adding a
new Subsection 907 4410
Sec. 907.4410. Location/Security. The control unit, remote annunciator,
alarm panel; and access keys to locked fire alarm equipment shall be
installed and maintained in a location approved by the fire Bode
effietal Code Official All occupancies equipped with a fire sprinkler
or alarm system shall install a key safe below an exterior horn strobe and
near the access to the remote annunciator or main entrance Alarm panel
access keys and building access keys or master keys shall be provided and
kept in an on -site wall mounted entry key safe provided by the building
owner and shall meet specifications of the fire eede e€€teml Code
Official
(lei) Fire Alarm and Detection Systems - Monitoring Section 907 of the International
Fire Code, entitled "Fire Alarm and Detection Systems," is amended by adding new Subsections
907 4-211, 907 4-3-12, 907 x-413, 907 4-5-14 and 907 4-615
29
2012 International Fire Code Adoption
Sec. 907.4211. Instructions. Written operating instructions for the fire
alarm system shall be provided and kept in an on -site wall mounted entry
key safe provided by the building owner and shall meet specifications of
ire eedeoffiemd Code Official All alarm systems shall be capable of
being silenced without having to be reset Alarm panels that require a reset
code to silence or reset the system shall be programmed with a fire
department reset code that is approved by the €rye- eede effieff Code
Official
Sec. 907.4212. Designer Qualifications. Persons who design fire alarm
systems shall be either a fire protection engineer registered by the State of
Washington or NICET III and current with all continuing education and
training required by NICET The designer must be NICET II by July 1,
2008 and NICET III by January 1, 2009
Sec. 907.4413. Installation Requirements. During the course of a fire
alarm installation, including all subsequent modifications and annual
testing, a NICET level II technician in fire alarms shall personally conduct
all programming and testing
Sec. 907.1314. Existing Fire Alarm Systems. All existing fire alarm
systems are subject to the provisions of 907 4-413
Sec. 907.4315. Violations. Violations of section 907 44-13 and 907 4-5-14
constitutes a mandatory $1000 violation per occurrence Each day
constitutes a separate and distinct violation Any three violations of this
provision immediately revokes the affected fire alarm company's City of
Bremerton business license and prohibits re- application for a period of not
less than three years
18.02.095 AMENDMENTS TO THE INTERNATIONAL FIRE CODE -
SECTION 913, FIRE PUMPS.
The following local amendment to Section 913 of the International Fire Code, entitled
"Fire Pumps," is adopted and incorporated into the International Fire Code
(a) Fire Pumps Section 913 of the International Fire Code is amended by adding a
new Subsection 913 2 472
Sec. 913.2.4 - Fire pumps utilizing electric drivers shall provide a back -up
power supply
Exception: In F and S occupancies when the normal occupant load does
not exceed 15, the occupancy would normally be vacated during power
outages and with the fire sode effieW Code Official approval
18.02.100 AMENDMENTS TO THE INTERNATIONAL F4RE CODE
CHAPTER _X, FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION.
30
2012 International Fire Code Adoption
" Fire The following leeal amendment to Chapter- 14�3 of the Wemahenal Fire Code, eahtled
" Water (a) Watef Supply for- Fire Pfeteehen Whem Required Seehen 1412 ef the
hMemattenal Fire Code, &Atfled Preteehen, is amended by substituting
SubserAie,, 1412 1 331 2 !with th f 11,,,..,,,x.
S ee. 1412 ,When r Am a ppro ved ,,.,, supply f fir
e n the
18.02.110 AMENDMENTS TO THE INTERNATIONAL FIRE CODE -
CHAPTER 23. MOTOR FUEL - DISPENSING FACILITIES AND REPAIR GARAGES.
The following local amendment to Chapter 23 of the International Fire Code, entitled
"Motor Fuel - Dispensing Facilities and Repair Garages," is hereby adopted and incorporated into
the International Fire Code as if fully set forth therein
Sec. 2305.3.1. Required Spill Control Equipment. Every fuel dispensing
facility and repair garage shall maintain at least 50 pounds of nce hulls or
other approved absorbent and at least 25 approved absorbent pads,
minimum dimension 16 mch by 16 inch and/or other spill control
equipment as approved by the Fire Code Official
18.02.110 AMENDMENTS TO THE INTERNATIONAL FIRE CODE
CHAPTER 22, MOT-OR FUEL DISPENSLNG FACILITIES AND REPAIR GARAGES.
The fellewing leeal amendment to Chapter- 2223 of the Wemational Fire Code, eatitle
"Meter- Fuel Dispensing Faetlities and Repair- Gamges," is hereby adopted and meer-per-ated ii#e
the Wemahenal Fire Cede as if fully set forth therein
See. 222 Required SpiH Control Equipment. Every fuel
dispensing faetlity and fepair- gar-age sMI maintain at least 50 peun
Ftee hulls or- other- appr-eved abser-beM and at least 25 approved absorb
pads, fmaimum dim-m-si-emn- 1-6- mahby 16 tae-ah ma-d-49r, ether- spill Ge
equipmeM as approved by the fire eede Fire Code Official
18.02.120 AMENDMENTS TO THE INTERNATIONAL FIRE CODE —
CHAPTER 33. FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION.
The following local amendment to Chapter 33 of the International Fire Code, entitled
"Fire Safety Dunng Construction and Demolition," is hereby adopted and incorporated into the
International Fire Code as if fully set forth therein
(a) Water Supply for Fire Protection - When Required Section 3312 of the
International Fire Code, entitled "Water Supply for Fire Protection," is amended by substituting
Subsection 3312 1with the following
Sec. 3312.1 When required. An approved water supply for fire protection
shall be made available as soon as combustible matenal amves on the site.
31
2012 International Fire Code Adoption
18.02.120 AMENDMENTS TO THE INTERNATIONAL FIRE CODE
CHAPTER 27,14AZARDOUS MAT-EP.L4LS GENERAL PROVISIONS.
The following leeal amendmei# te Chapter- 27 ef the Wemattenal Fire Code, eat-it!
Fire Cede, enfided " Ster-age," is amended by substituting Subseetten 2704 3.1 wM
fellewing
- . >~., , e s ,6te s1.a11
Code -
2 Meehameal ventilatien shall be at a rate ef net less than 1 eubte feetTef
famu4e per- squar-e feet [0 0050 /s - fn )]
3 Systems shall epereAe eentinueusly unless altema4tve designs are
appFeved-
4 A manu s1,,,te ff ee„t,.el sh be «,.e e„t.,.ae eftl,e
type and be label VENTILATION TION SY T iT EMERGENC r
914 TOFF FIRE DEPARTMENT DTMENT T SE ONLY
G Exhaust . e s h a ll be ,les......ed tee s•.le.. the dens of the
. . . 1 fumes eF vaper-s released Fer &mes er- vapors that afe hea
than air-, w4must shall be taken fr-em a peint w4m 12 mehes (305 ffffn) e
F-
1 Q 02 13n AMENDMENTS TO THE LNTERNATIONAL FIRE CODE CHAPTE
45, MARINAS.
n n is hereby adepted and meer-perated inte the Wemauenw Fire Code as if AAIY
net f„«tl, tb.e..e..,
32
2012 International Fire Code Adoption
Chapter- 45 Nk4JUNAS
4501 See"
vessels, 4501.2 Plans and Approvals
Plans for- manna fire pr-eteetion faedities shaU be approved pfier- to
msta4ahen The work shall be subjeet te final inspeetion and approval
after- installation
4501.2.1 Permits
Permits afe required to use open flame dewees fer- matatenanee or- r-epaff
on floats, '"
4502.1 Definitions. The following weFds and tefms shall, for- the puTese
of this ehaptef and as used elsewhere in &s f have the faeamags
SheW-heFeifl
FLOAT is a float-tag stmetwe nermally used as a point of tFansfer- fe.r-
f
C 7
aAifie1w11y pr etev for the mee it R 1ser - saf ety of vessels and
f
f
the ir- o pass
PIER is a stmetffe built over- the f piles,
used as a landing f
type VESSEL is wateFffaft ef any f used
weed, beatheuses-
7
o « ,«. atef tarbu hilt at the sheiz ef a haFbe lake -; tA
lie a 4 en ..s „lo „f f an fl
p « oa t b ,...,.L.,.fe t e.
33
2012 International Fire Code Adoption
4503 GENERAL PRECAUTIONS
4503.1 Combustible DebAS. Combustible debFis and rubbish sWI not b
w harves-
4503.2
de,.,.,. e the evte - of n ve set H eat p ier- w - f ohnli_ be
appmved-
4503.3 Flammable OF Combustible Liquid SpiRs. Spills of flafmnable e
eembustible liquids at or- upon the water- shall be r-epefted immediately4o
4503.4 Rubbish Containers. Containers with tigWitting er- selfelesing
fubbish
us ed i wed ,.d., t�, its list,,, .,d S+,,,, 605 ,-
e .,e„, r f
damp and hazafdous loeattens.
4503.6 Berthing and StoFage. Beftlung and ster-age shall be i
4503.7- Addressing. Each slip shall be fmffiber-ed and aleady fnar-ked
4504 FIRE PROTECTION EQUIPMENT-
4504.2 Standpipes. Mannas and beatyafds shall be equipped thfoughout
with standpipe systems in aeeerdanre with the fellewifW
e f the ,.. e f ire
i nstalled i „f ffa" with NFP n 14 a een one
t ,,, „ maximtim „fame' 4of the end oft the H E„et, h s t a b, sh
be ..,.,..,idea , A twe z-1/2" s " 0
r-edueer-s with eaps Installatten ef fire hose is net fnaadeAer-y at standpipe
34
2012 International Fire Code Adoption
I,
2 L 1+ s ste nL.nll be «re,.,aed w ., r.,m,,,++ of two 2 1/2"
4 Piping shall be fnimmum sehedule 40 elass and shall be sized te deliv
inn GPM at 6 r re sidual p r-essum „t the ,, est r-emete station with a
delivered pressure of 150 psi at the Fire Depaf#aeat eefmeetien
5 c + 1 va lves shall be provided at the el ang e f direet er, of ea
fl a t, h ++ T he 1 shall 1� a t,.e.,,.,., o f the he
rivcrc- ccr�cr-ac�uvir ° c aooiir�rr ....,..,..,........s..
station
4504 A eeess a nd Water Supply Piers and wharv shall b pFe ded
tl, f' appff r-e ads a nd wate ply systems w 4h , 4 o site fire
hydrants when required by the fire esede effieffil Seeh fflads and water-
systems shall be pmvided and maintained in aeeerdanee with Seeteas
503.2 and 508
4504.4 Portable Fire ExtinguisheFs. One fire erainguisher- for- ordififffy
(maderate) hazard type, shall be pr-e-Aded at eaeh required hese stahen
Addthena4 fire > > sh
provided and maintained in aeeer-danee with Seehen 9
be provided on the site in a leeahen appr-eved by the eede effieial
4505 MARINE MOTOR VEHICLE FUEL DISPENSING
STATIONS
4505.1 Fuel Dispensing. Maftne meter vehiele fuel dispensing stations
shall be vfl- aeae-r-d-ffinee wigi Chapter- 22 of this vande
18.02.440 A MENDMENTS TO THE INTERNATIONAL FIRE CODE -
APPENDIX D, FIRE APPARATUS ACCESS ROADS.
The following local amendments to Appendix D to the International Fire Code, entitled
"Fire Apparatus Access Roads," are hereby adopted and incorporated into the International Fire
Code as if fully set forth therein
M immum S peet f i e a t iens G S D 10 eft e t,en„ 1 Free
" Minimum
fig
See D103 !'!. -ade Fire appa r- a tas asees rend. -hall no t a eed 10
depwttwe angle for- fire appamtus aeeess "I be as detemifted by the fire
35
2012 International Fire Code Adoption
eede effiratal Unless building spmgder-s have been installed in aeeefdanrae
with this eede and the Feadway has been appr-eved by the fim eede-
effietal-
(ha) Minimum Specifications - Turning Radius Section D103 of the International Fire
Code, entitled "Minimum specifications," is amended by substituting Subsection D103 3 with the
following
Sec. D103.3 Turning radius. The fire apparatus access road shall have a
23 foot minimum inside turning radius and a 45 foot minimum outside
turning radius
(qb) Fire Apparatus Access Road Gates Section D 103 5 of the International Fire
Code, entitled "Fire Apparatus Access Road Gates," is amended by substituting Subsection
D 103 5 1 with the following
See. D103.5.1 The minimum gate width shall be 14 feet
18.02.4M FIRE CODES - FEES.
The fees to be assessed for the codes adopted in this chapter shall be as set forth in BMC
3 01060, Fire Department - Rate Table E, as currently enacted or as hereafter amended
18.02.440150 CITY OF BREMERTON FALSE ALARM CODE.
(a) For the purposes of this section, a false alarm shall be deemed and construed as
being the activation of any fire protection system due to some form of maintenance or lack of
maintenance element
(b) It shall be unlawful for any person to give, signal, or transmit or for any person to
cause or permit to be given, signaled, or transmitted, in any manner any false alarm
(c) It shall be unlawful for any person to tamper with or maliciously inure or activate
any fire protection system or equipment maintained for the purpose of transmitting fire alarms to
the Fire Department
(d) Nothing in this section shall prolubit the sounding of any such signal essential for
the carrying out of any system maintenance or fire drill The ui--° r,. de 0 - ffiemlFire Code
Official his designated representative, or the responsible central station monitoring agency shall
be notified in advance when such signal will be sounded
(e) Any person, firm or corporation who is found to have signaled or transmitted a
false alarm shall be guilty of a civil infraction and shall be fined per BMC 3 01060, Fire
Department - Rate Table E
(f) Definitions
(1) "False alarm" shall mean the activation of a fire protection system at a
time when no conditions attributable to a fire or smoke condition are found to exist upon arrival
of the Fire Department
(2) I'Fir-e Code Offietal" shall fnean the Chief of the Fire DepaFtment or- h;
designated repr-eseata4ive.
( "Person" shall mean any person, firm, partnership, association,
corporation, company or organization of any kind
36
2012 International Fire Code Adoption
(43) "Preventable false alarm" shall mean a false alarm caused or initiated or
allowed to be caused or initiated by the premises owner, or by a representative, assignee, or other
persons that function under the direction or control of the owner, whether caused by direct intent,
malicious action or by system neglect or improper system maintenance
(344) "Unpreventable false alarm" shall mean a false alarm caused by power
failures or interferences unrelated to the operation of the premises
(g) Any person having or maintaining a fire alarm shall, within three (3) working
days after notice by the Fire Code Official at the scene of a false alarm, make a written report to
the Fire Code Official setting forth the cause of such false alarm, the corrective action taken,
whether such alarm has been inspected by an authorized service person, and such other
information as the Fire Code Official may reasonably require to determine the cause of such
false alarm and the prescribed action necessary
(h) The determination whether or not a false alarm was preventable shall be made by
the Fire Code Official Any fee resulting from a determination that a false alarm was preventable
shall be billed by the City Treasurer's Office and shall be deposited in the General Fund
18.02.160 Reserved.
18.02.170 AUTOMATIC SPRINKLER SYSTEMS - BUILDINGS
CONTAINING TWO OR LESS DWELLING UNITS.
(a) When automatic sprinkler systems are installed in buildings containing two (2) or
less dwelling units as defined in the International Residential Code, whether attached or
detached, they are permitted to be connected to the domestic service within said unit utilizing an
integrated fire /plumbing flow - through system
(b) Automatic sprinkler systems installed pursuant to subsection (a) of this section
shall not be subject to general facility charges, connection fees, inspections fees and other permit
fees specifically related to and other-wise assessable under- GhapteF 3 01 BMG and n� "�ztle 15
the installation of a fire sprinkler
system with a service size un to and including one (1) inch
(c) Automatic sprinkler systems installed pursuant to subsection (a) of this section are
integrated into and dependent upon the domestic water supply of the residential dwelling unit,
therefore, the property owner is responsible for maintaining a connection to and paying for an
adequate supply of water to the residential dwelling unit
18.02.473 SPECIFIC VIOLATIONS - FINES.
Any violation of any provision of the City Fire Code identified in this section may be
assessed a monetary fine for each incident or occurrence as follows
(a) Illegal burning two hundred fifty dollars ($250 00),
(b) NICET violations one thousand dollars ($1,000),
(c) False fire alarms two hundred dollars ($200 00),
(d) Fire Code violations with the knowledge of d%- a responsible party one hundred
twenty -five dollars ($125 00),
(e) Repeat Fire Code violations for failure to correct or comply with the City Fire
Code one hundred twenty -five dollars ($125 00)
Nothing in this section prohibits the City from seeking other remedies as allowed by ordinance,
including, but not limited to, those set forth in BMC 18.02.180 The Fim Mafshal Code
37
2012 International Fire Code Adoption
Official may, at his or her discretion, reduce the amount of the assessed fine due to mitigating
circumstances
18.02.180 VIOLATION - PENALTY.
(a) Any violation of any provision of the City Fire Code, BMC Title 18, constitutes a
civil violation under Chapter 1.04 BMC for which a monetary penalty may be assessed and
abatement may be required as provided therein
(b) In addition to or as an alternative to any other penalty provided in this chapter or
by law, any person who violates any of the provisions of the City Fire Code, BMC Title 18, shall
be guilty of a misdemeanor pursuant to BMC 1 12 020(2)
18.02.490200 APPEALS.
(a) Appeals to the Hearings Examiner
(1) Jurisdiction The City Hearings Examiner has been designated as the
Board of Appeals and shall have jurisdiction over all matters concerning the reasonable
application of the fire codes cited in this chapter The City Heanags ExafmneF, however-, shall
shall the City Heafings Examiner- be empewer-ed to waive r-eqwFments ef these fire e-edes; —And
(2) Filing Appeals shall be filed with the Hearings Examiner in accordance
with Chapter 2 13 BMC
(3) Standing Standing to bring an appeal under this chapter is limited to the
following persons
(i) The applicant and the owner of property to which the permit
decision is directed
(n) Another person aggrieved or adversely affected by the order,
determination, or decision, or who would be aggrieved or adversely affected by a reversal or
modification of the order, determination, or decision A person is aggrieved or adversely affected
within the meaning of this section only when all of the following conditions are present
a The order, determination, or decision has prejudiced or is
likely to prejudice that person,
b. A ,judgment in favor of that person would substantially
eliminate or redress the prejudice to that person caused or likely to be caused by the order,
determination, or decision, and
C The appellant has exhausted his or her administrative
remedies to the extent required by law.
(b) Appeals to Superior Court Appeals to the Hearings Examiner shall be made
pursuant to Chapter 2 13 BMC
SECTION2. Severabihty If anyone or more sections, subsections, or
sentences of this Ordinance are held to be unconstitutional or invalid, such decision shall not
affect the validity of the remaining portion of this Ordinance and the same shall remain in full
force and effect
38
2012 International Fire Code Adoption
SECTION 3. E fective Date This ordinance shall take effect and be in force ten
(10) days from and after its passage, approval and publication as provided by law
PASSED by the City Council the Z61--k day of wwl'hEr , 2013
j ` GREG nELER, Council President
Approved this Zs" ` may of / . Y ,0 ����f" , 2013
PATTY Lj,Mayor
ATTEST APPROVED AS TO FORM
AAA C
SHANNON L CORIN, City Clerk R ERA LUBOVICH,
PUBLISHED the day of 491234 r 2013
EFFECTIVE the ' ` da of 2W -910)�7 o* �' , 2013
ORDINANCE NO
R U. egal\L.egal \Ordmances\Fire\2012 IFC Amendments (2013) -Final docx
39
2012 International Fire Code Adoption
AFFIDAVIT OF PUBLICATION
Account #42742 AD#20137855
STATE OF WASHINGTON
COUNTY OF KITSAP
I, Christine Kendrick, being first duly sworn on oath, deposes and says That she is now, and at all times
embraced in the publication herein mentioned was the principal clerk of the printers and publishers of
KITSAP SUN, that said newspaper has been approved as a legal newspaper by order of the Superior Court
of the County of Kitsap, in which County it is published and is now and has been for more than six months
prior to the date of the publication hereinafter referred to, published in the English language continually as
a daily newspaper in Bremerton, Kitsap County, Washington, a weekly newspaper in Kitsap County,
Washington and is now and during all of said time, was printed in an office maintained in the aforesaid
place of publication of said newspaper, that the following is a true text of an advertisement as it was
published in regular issues (and not in supplement form) of said newspaper on the following date, to wit
And on Nov 27, 2013 such newspaper was regularly distributed to its subscribers during all of said period
The full amount of the fee charged for the foregoing publication is the sum of $43 26 This amount has not
been paid in full
(Signature of Principal Clerk)
Subscribed and sworn to before me this day of November 29, 2013
Notary Public in and for the State of Washington, Kitsap County NOTARY PUBLIC
STATE OF WASHINGTON
CHRISTY M MOFFITT
My Appointment Expires July 08� 2016
ORDINANCE NO 5234
AN ORDINANCE of the City Council of the City of Bremerton, Washington, amending Chapter 18 02 of
the Bremerton Municipal Code entitled "City Fire Code" to adopt the 2012 edition of the International Fire
Code, as amended by the Washington State Building Code Council in Chapter 51 -54 of the Washington
Administrative Code and to incorporate additional amendments
PASSED by the City Council on the 20th day of November, 2013
The full text of this ordinance is available from the City Clerk's Office, 345 Sixth Street, Suite 600,
Bremerton, WA 98337
November 27, 2013
AD# 20137855