HomeMy WebLinkAbout3424· -~ _ ~ Dist~bution:
At~ qey/'
Bre.. rton Sun/ ~
F±re Dept./
AN ORDINANCE adoPt±rig the 1977 Fire Alarm Code
for the City of Bremerton and declaring an emergency.
THE CITY COUNCIL OF THE CITY OF BREMERTON DOES ORDAIN
SECTION 1. There is adopted, for the purpose of pre-
scribing regulations governing the installation, use and maintenance
of fire alarm systems within the City, that certain document en-
titled "1977 Fire Alarm Code for City of Bremerton," three copies
of which are now on file in the office of the City Clerk, and said
code is adopted and incorporated as fully as though set out herein
in length.
SECTION 2. Any person who shall violate any provisions
of this ordinance incorporating the 1977 Fire Alarm Code for the
City of Bremerton, or fail to comply therewith, or who shall violate
or fail to comply with any order made thereunder, or who shall build
in violation of any detailed statement or specifications or plans
submitted and approved thereunder, within the time fixed therein,
shall for each and every such violation or failure to comply, be
guilty of a misdemeanor. The imposition of a criminal penalty shall
not excuse the violation or permit it to continue and shall not be
held to prevent the enforced removal of prohibited conditions, and
all such persons shall be required to correct or remedy such viola-
tions or defects within a reasonable time. Each ben days that
prohibited conditions are maintained shall constitute a separate
offense.
SECTION 3. This ordinance is a public emergency ordinance
necessary for the protection of public health, public safety, public
property and the public peace, and shall be effective upon its adop-
tion by the City Council.
PASSED BY THE CITY COUNCIL THIS ~/~ day of ~ 3~ ,
197~.
-1-
ATTEST:
City Clerk
2
APPENDIX "A"
A Brief of Occupanc~7 Requirements from Section VIII
NUMBER OF STORIES NUMBER OF PERSONS TYPE OF
OCCUPANCY OR SQUARE FEET OR UNITS SYSTEM
Apartments 1 or more without 3 or more units Type E
direct exiting
2 or more 3 or more units Type A plus
Smoke
Detection
I Occupancies except 100 or more beds Type D
Jails, Prisons, Less than 100 beds Type E
Reform
Dormitories/ 2 or more 50 or more beds Type D
Fraternities 2 or more and/or 2 to 50 beds Type E
1 6 or more Type A
Educational 6 or more Type A plus
automatic in
Hazardous
areas
Hotels, Motels 2 or more 50 or more people Type D
2 or more and/or 6 to 49 people Type E
1 6 or more people Type A
All non-sprinklered 5,000 square feet Type E
or more
One and Two Family Individual
Dwe 11 in gs Smoke
Detectors
Office, Mercantile 3 or more 50 or more but less Type B
etc. than 1,000 persons
(Sprinklered) 75' or more 1,000 or more Type D
Assembly B2) 5,000 square feet Type E
or more
All PUblic
Address
System
Any building Over 5,000 square feet - Type E
1977
FIRE ALARM CODE
for
C I TY OF B REME RT ON
TABLE OF CONTENTS
Page(s)
I Introduction 1
A. Purpose
Definitions 1-4
A. Alarm Service
B. Alarms
C. Annunciator
D. Approved
E. Coded Signal
F. Dwelling Unit
G. Educational Building
H. Fire Control
I. Fire Divisions
J. Institutional Buildings
K. Local Fire Alarm System
L. Maintenance
M. Mercantile Buildings
N. I4ulti-Family Buildings
O. Owner
P. Product of Combustion Detection
Q. Protective Signaling Systems
R. Public Assembly Building
S. Residential Building
T. Smoke/Product of Combustion
U. Trouble Signal
III General Information 5-8
A. Scope
B. Conflict with Standards
C. Test on Completion
D. Maintenance
E. Connection Fee
F. Indemnity Agreement
G. Prohibited Equipment
H. Termination and Penalties
IV Review and Acceptance 8-9
A. Information Required
B. Acceptance of System after Installation
V Alarm System ComRonents 9-14
A. Manual Sending Stations
B. Sounding Devices
C. Annunciator
D. Power Supply
E. Alarm and Supervision Circuits
F. Sprinkler Systems
i
TABLE OF CONTENTS (contd.)
Page ( s )
VI Existing Buildings 14
VII Alarm Systems Defined
A. Type A - Local Alarm, Non-Coded
B. Type B - General Alarm, Non-Coded
C. Type C - General Alarm, Zone Coded, Annunciated
D. Type D - Dual Coded Alarm
E. Type E - Automatic Fire Detection System
VIII Occupancy Requirements
A. Definitions
B. Occupancy Groups
1. Occupancy Groups A, B1, B2
2. Occupancy Groups Cl, C2, C3 and other
Educational Occupancies
3. Group D3 and D3 Occupancies
4. Group H Occupancies
5. Group I Occupancies
6. Other Occupancies
APPENDIX "A" - Occupancy Requirements
ii
I Introduction
A. Purpose
The purpose of these standards is to specify use of fire
alarm systems providing the highest degree of public
safety and building protection from fire which can
reasonably be required without involving unreasonable
hardships or interference with normal use and occupancy
of the structure. These standards, in general, provide
for:
1. The installation of automatic detection in all
new unsprinklered construction over 5,000 square
feet gross floor area.
2. Products of combustion detection in hallways and
certain other areas in building where a life
hazard exists.
3. An intertie of the water flow alarm of sprinkler
systems to the Fire Department Central Dispatch
II Definitions
A. Alarm Service: A fire alarm system providing for (1)
the manual operation of a fire alarm signal station;
or (2) the transmission of an alarm indicating the
operation of protective equipment or systems; or (3)
the transmission of an automatic fire alarm signal;
or (4) the transmission or actuation of any other
emergency fire alarm signal; or (5) any combination of
these.
--1--
B. Alarms: Type A - General Alarm (noncoded)
Type B - General Alarm (zone noncoded)
Type C - General Alarm (zone coded)
Type D - Dual Coded Alarm.
C. Annunciator: A unit containing two or more identified
targets or indicator lamps in which each target or lamp
indicates the circuit, condition or location to be
annunciated.
D. Approved: Accepted in writing by the Fire Chief as a
result of investigation and experience and by reason of
test, listing or approval for specific use by Under-
writers' Laboratories, Inc., Factory Mutual Research
Corporation or other nationally recognized testing agencies.
E. Coded Signal: An alarm signal which consists of not
less than three complete rounds of the number trans-
mitted.
F. Dwelling Unit: One or more habitable rooms which are
occupied, or which are intended or designed to be
occupied, by one'family, and which include the facilities
for living, sleeping, cooking and eating.
G. Educational Building: A building or structure, or any
portion thereof, used by persons harbored to receive
instructions such as schools, universities, colleges
and academies. It also includes part-day nursery
schools, kindergartens and other schools whose purpose
-2-
is primarliy educational.
H. Fire Control: The Dispatch Agency used by the City of
Bremerton.
I. Fire Divisions: Those divisions established by area
separation walls which may be vertical, horizontal or
both, when necessary. Each portion of a building sepa-
rated by one or more such four-hour fire resistant walls
may be considered a separate building.
J. Institutional Building: A structure, or any portion
thereof, used by persons harbored or detained to
receive medical, charitable, or other care or treat-
ment, or used to detain persons involuntarily.
K. Local Fire Alarm System: A local system used exclusively
to sound a fire alarm at the protected premises as the
result of the manual or automatic operation of pro-
tection equipment or signaling systems.
L. Maintenance: Repair Service, including periodic
inspections and tests required to keep the protective
signaling system and its component parts in an operative
condition at all times.
M. Mercantile Building: A structure, or any portion thereof,
used for the displaying, selling, or buying of goods,
wares, or merchandise.
N. Multi-Family Buildings: A structure or portion thereof
containing three or more dwelling units, including
tenement house, apartment house, flat or condominium.
-3-
O. Owner: Any person having legal or equitable title to,
or controI of, a building or property.
P. Product of Combustion Detection: When used with smoke
detection shall mean only the following type systems:
(1) Photoelectric cell (single and dual), (2) Refrac-
tory and (3) Ionization.
Q. Protective Signalihg Systems: Electrically-operated
circuits, instruments and devices, including the
necessary electrical sources, designed to transmit
alarms, supervisory signals and trouble signals
necessary for the protection of life and property.
R. Public Assembly Building: A structure or portion thereof,
used for the gathering together of fifty' i(50)~or~more ~
persons.
S. Residential Building: A structure, or any portion there-
of, used by persons for sleeping accomodations, (such
as motels, hotels, apartment houses, dormitories,
lodging or rooming houses and multiple family residences)
which persons are not harbored or detained to receive
medical, or other such care or treatment, or are other-
wise involuntarily detained.
T. Smoke/Product of Combustion: See "Product of Combustion".
U. Trouble Signal: A signal indicating malfunction of any
nature, such as a circuit break or ground, occurring at
the devices or wiring associated with a protective sig-
naling system.
-4-
III General Information
A. Scope
The regulations contained in this code require the
installation of and govern the use and maintenance of
fire alarm systems within the City of Bremerton. The
regulations contained in this code require the installa-
tion of electrically supervised fire alarm signal
systems in premises and occupancies as specified through-
out this code.
B. Conflict with Standards
In the event of any conflict between the provisions of
the Uniform Fire Code or the Uniform Building Code
and the regulations contained in this code, this code
shall govern.
C. Test on Completion
An operational performance test of the entire fire
alarm system will be required prior to final approval.
Such test shall be coordinated by the Fire Chief or
his representative and will require a copy of the
"AS BUILT" plans of the system and the presence of a
representative of the fire alarm installer, general
contractor and the electrical contractor. During the
test where sprinkler systems are installed, a repre-
sentative of that firm should be present. EXCEPTION:
Group R3 - occupancies, ~o comPly with the 1976 U.B.C.
-5-
D. Maintenance
Maintenance of any fire alarm system shall be provided
by the person, firm or corporation that is responsible
for the building in which it is installed. Tests
shall be made at not less than 30 day intervals to
insure proper operation and maintenace of the system.
Records of testing shall be maintained available for
inspection by fire department personnel.
E. Indemnity Agreement
Any person, firm or corporation desiring to terminate
any alarm to the Fire Control Panel shall first sign
an indemnity agreement holding the City of Bremerton
harmless from any liability involving the failure of any
alarm circuit or equipment.
F. Prohibited Equipment
Alarm equipment designed to alert any municipal emer-
gency service by providing unattended automatic dialing
of any public telephone number of any emergency service
for the purpose of transmitting a pre-recorded message
shall be prohibited.
G. Termination and Penalties
The Fire Chief may at any time order the removal of
-6-
any alarm termination from the Fire Depart-
ment or Fire Control facilities due to
repeated failure of equipment or circuitry,
multiple false alarms, or failure to
comply with all of the provisions of
this code. Such notice of discontinua-
tion shall be made in writing to both
the company that installed and/or supplied
the alarm equipment and to the person,
firm or corporation that is responsible
for the building in which the alarm
system is installed, at least 48 hours
prior to the disconnection of the alarm
circuit.
In the event of temporary failure of
alarm equipment or circuitry, the Fire
Chief may order all emergency response
actions discontinued until repairs can
be made.
Violation of this subsection shall be
governed by City of Bremerton Ordinance
No. 325 ~50 as amended.
- 7 -
IV. Review and Acceptance
A. Information Required
Complete information regarding the system includ-
ing specifications, point to point wiring
diagrams, and floor plans showing device loca-
tions shall be submitted by the owner or an
engineer, architect, or electrician licensed
by the State of Washington to practice as such,
and shall be reviewed by the fire department
or by a person or firm approved by the fire
department prior to the issuance of a building
permit. All devices, combination of devices,
and equipment constructed and installed in
conformity with this standard shall be approved
only for the purposes for which they are
intended. All equipment shall be approved by
a nationally recognized testing agency for the
use for which it will be installed.
B. Acceptance of System after Installation
Upon completion of the system a satisfactory
test of the entire installation shall be made
in the presence of a representative of the fire dept-
partment as specified in Section III, Item C.
Acceptance of a system will be issued
in writing after the above test is satisfactorily
- 8 -
completed. The Building Official shall not issue an
Occupancy Certificate until he has such letter of
acceptance on file. Any prior review is intended only
as assistance to the owner and installer and does not
indicate approval of the system at that time.
V. Alarm System Compqpents
A. Manual Sending Stations
A manually operated sending station shall be provided
at each main exit and in the natural path of escape
from fire at readily accessible and visible points
which are not likely to be obstructed. Each manually
operated sending station shall be securely mounted.
The bottom of the box shall be not less than four and
one-half feet (4 1/2') and not more than six feet (6')
above floor level.
B. Sounding Devices
Alarm devices shall be provided of such character and
so distributed as to be effective regardless of the
maximum noise level obtained from machinery or other
equipment or vocal sounds produced under normal
conditions of occupancy. Each system shall be so
arranged that no manual intervention will be required
following the actuation of a sending station or auto-
matic detector for causing the effective response of
all required sounding devices. No facilities shall be
-9-
provided whereby such response can be controlled or
modified except where specifically approved as provided
in this code.
C. Annunciator
Annunciators shall be required on all fire alarm systems
when the building complex consists of three or more
separate buildings, floors or fire divisions. Such
annunciators shall have all interconnecting wiring
electrically supervised. Annunciator panels shall be
installed so as to be clearly visible and identifiable
to personnel responding to an alarm.
D. Power Supply
All systems shall provide a secondary power source and
shall automatically transfer within ten seconds to that
source in the event of a primary power source inter-
ruption. Such secondary source shall provide at least
24 hours power supply. All power supply equipment and
wiring shall be installed in conformity with the re-
quirements of the Uniform Fire Code and rules and regu-
lations of the State Department of Labor and Industries,
Electrical Inspection Division and must be approved by
the Electrical Inspector for the City of Bremerton.
E. Alarm and Supervision Circuits
All circuits for operating alarm sounding devices and
appliances shall be electrically supervised with the
exception of:
-10-
(1) The Circuit of an alarm sounding device installed
in the same room with a system control unit,
provided the circuit conductors are installed in
conduit or equivalently protected against mechanical
injury or tampering with a limit of three feet of
conduit.
(2) A trouble signal circuit.
(3) The neutral of a three, four or five wire AC or
DC supply source.
(4) Alarm signal sounding appliances when ~. alternately
connected to two or more circuits at approximately
equally distributed points throughout the building
or ~. connected to a return loop circuit so that
a break or ground does not prevent the operation
of any sounding appliance and with means provided
for testing the continuity of the circuit.
Approximately equally distributed throughout shall be
interpreted to mean sounding appliances shall be installed
so that failUre of any one circuit or alarm signal shall
not prevent an alarm from being heard in the areas served
by that circuit.
All fire alarm systems shall be electrically supervised
so that the appearance of a break or ground fault of its
installation wiring circuits which prevents the required
operation of the system or failure of the main power
supply shall be indicated by a distinctive trouble signal
-11-
Ail systems shall be test free from ground except
those parts of circuits or equipment which are in-
tentionally and permanently grounded to provide ground
fault detection, emergency ground signaling or cir-
cuit protective grounding. All systems shall be so
designed that they do not depend upon the effectiveness
of any ground connection for normal operation. A switch
for silencing the trouble signal sounding appliance may
be provided only if it transfers the trouble indication
to a lamp or other acceptable visible indication
adjacent to the switch. The visible indicator shall
remain in operation until the silencing is restored to
its normal position unless the audible signal will be
obtained when a fault occurs without restoring the
switch to normal or unless the audible trouble is
again energized upon correction of the fault. Where
corridors in an institutional, residential or educa-
tional building are utilized for pressurized air handling
systems an approved automatic smoke detector system shall
be installed and connected to automatically energized
fire alarm circuit which will release hold upon devices
on required doors in fire walls and smoke separation
partitions and simultaneously de-energize the electrical
power to the mechanical equipment of the interhandling
system. Fire alarm control panel and/or trouble signal
indicators shall be installed in areas which are normally
-12-
staffed during the hours the building is occupied.
The fire alarm control panel shall have constantly
visible indicator showing that the system is normal.
Any dearrangement of this system's circuits will be
indicated by means of a trouble bell or buzzer. When
an audible trouble signal is silenced manually, the
visible signal shall continue to indicate that the
system is not operating normally and shall be corrected
immediately. When required, the control panels may be
equipped with a momentary contact reset switch. A
manually or automatically operated fire alarm system
may be arranged for the accomplishment of the incidental
functions such as release of self-opening or self-
closing doors, cutting off supplies or gas, fuel oil,
electric power, switching on emergency lights, stopping
of air handling equipment fans, etc., as long as the
accomplishment of said functions does not impair the
effectiveness or reliability of the required sounding
devices. Directions for operating together with the
instructions on how to reset the~system or de-energize
the circuit after the alarm has been sounded shall be
posted.
F. Sprinkler Systems
All new and existing sprinkler systems in the City of
Bremerton shall, at the discretion and direction of
the fire chief, have an approved supervised alarm that
-13-
terminates at the fire alarm center. This alarm
shall be activated by an approved water flow switching
device. All systems shall terminate in equipment as
specified by the Fire Chief. All water flow switching
devices shall have a time delay activation switch
installed thereon. All sprinkler systems shall inter-
tie to alarm systems installed in the same building or
complex. Automatic detection, except required products
of combustion detections, may be eliminated where
sprinkler systems are installed throughout.
VI Existing Buildings
No existing buildings (except as stated in Section V-F)
shall be made to conform to the provisions of this code
except where structural deficiencies affecting life safety
are involved and in the opinion of the Fire Chief its
continued use without a fire alarm system would be hazardous
to the safety of the occupants.
VII Alarm Systems Defined
A. Type A (Local Alarm, Non-Coded)
Activation of any initiating device; sounds a continous
bell on all indicating devices until manually reset.
B. Type B (General Alarm Zone-Non-Coded)
Activation of any initiating device sounding a continuous
alarm on all indicating devices until manually reset
-14-
and indicates on an annunciator panel the zone
initiated. A signal shall be automatically transmitted
to the fire alarm headquarters.
C. Type C (General Alarm, Zone-Coded, Annunciated)
Activation of any initiating device sounds a coded
alarm announcing the area of the fire to all occupants
and indicates the zone initiated on the annunciator
panel. A signal shall be automatically transmitted to
fire alarm headquarters.
D. Type D (Dual Coded Alarm)
Activation of any initiating device shall sound a zone
coded alarm on chimes to alert staff and personnel,
and shall indicate the zone location of the originating
device on an annunciator panel. Upon first operation
of any manual or automatic detecting device, a signal
shall be automatically transmitted to the fire depart-
ment by approved auxiliary connection to a municipal
fire alarm system or by direct wire connection to the
fire department or to an approval central station.
Manual pull stations must be equipped so that a key
can be inserted and a general evacuation alarm sounded
at any time. General evacuation alarms shall be contin-
uously ringing bells or horns. Any adjustable time
delay device shall be incorporated in the system to
-15-
activate the general evacuation alarm within a
maximum of five minutes after the first actuation of
any signal sending station or detection device.
E. Type E (Automatic Fire Detection System)
An automatic detection system shall consist of fixed
temperature, fixed temperature rate of rise, or smoke
products of combustion limited to approved photo
electric cell refractory or ionization type devices
singly or in combination. When buildings are completely
sprinklered, they shall not be required to have an
automatic ,detection system other than required for
smoke or products of combustion detection. Automatic
detectors must be installed per manufacturers or testing
laboratories specifications for area coverage and
method of installation. Automatic detection system
shall also include the approved installation of manual
sending stations. Automatic detection shall terminate
at fire alarm headquarters.
VIII Occupancy Requirements
A. Definitions
The definitions of occupancies as stated in this code
shall be as defined in the 1976 Edition of the Uniform
Building Code as published by the International Con-
ference of Building Officials and adopted by Chapter 17
of the Bremerton Municipal Code.
-16-
B. Occupancy Groups
Ail occupancies which contain over 5,000 square feet
gross floor area must have minimum Type E alarm
systems, except Group I. In order for an area to be
considered separately for the purpose of computing
gross floor area, it must be a separate structure or
divided from Other portions of a structure by minimum
four-hour walls with three-hour assemblies on self-
closers and held open only by magnetic hold open
devices intertied to products of combustion detectors.
Additional requirements for specific occupancy groups
are as follows:
1. Occupancy Groups Al, A2, A-2.1
An approved public address system shall be installed
with speakers so arranged that a message on the
system shall be heard over the ambient noise level
in all areas of the building. A microphone for
the system must be readily available to the manage-
ment and/or fire fighters and be located at loca-
tion approved by Fire Chief. Every stage shall
be provided with a fire control station and shall
have the following:
(a) Tell-tale lights to indicate the operation
of all emergency light and power circuits.
(b) Manual operating devices to actuate auto-
matic spray head~proscenium~
-17-
curtain and smoke vents.
(c) Indicators to show that sprinkler system
valves are open and system is charged with
water under pressure.
(d) A public address system energized from
normal and emergency light and power sources.
(e) An alarm system connected to the manager's
office, dressing rooms and auxiliary stage
spaces. It shall not sound an alarm audible
in the audience or seating portion of the
theater.
2. Occupancy Groups El, E2, E3 and other educational
occupancies.
Groups El, E2, E3 and other educational occupancies
used for the gathering of groups of six or more
persons for the purpose of instruction. This shall
include nursery schools and kindergarten. An approved
Type A alarm system shall be provided. Automatic
detection shall be required in all hazardous areas
(storage rooms, kitchens, janitor rooms and boiler
rooms) and in rooms not normally occupied continually
during hours of occupancy. See specific requirements
for Day Care Centers under ~VIII, B., 6.
3. Group I1 and I2 Occupancies (Except Jails, Prisons
and Reformatories).
Every building shall have a Type D system. An
-18-
approved automatic smoke detection (ionization)
shall be installed in all corridors of hospitals,
nursing homes and residential-custodial care
facilities. Such systems shall be installed in
accordance with the applicable Uniform Fire Code
Standards, but in no case shall smoke detectors be
spaced further apart than 30' on centers or more than
15' from any wall. All automatic smoke detection
shall be inter-connected to the fire alarm system.
EXCEPTION: Where each patient sleeping room is
protected by such an approved detection system and
a local detector is provided at each smoke partition.
Such corridor system will not be required on the
patient sleeping room floors.
4. Group R1 Occupancies
(a) Hotels, motels, sorority and fraternity
houses, dormitories with 50 or more persons
or two or more stories are required to
have a Type D system.
(b) All apartments with three or more units
that exit through a common interior exit-
way, and apartments three or more stories
in height shall have a Type E system.
(c) Apartments two or more stories in height
and four or more units with direct exiting,
-19-
shall be protected with a Type A system
with hazardous areas (Laundry,~ kitchens,
...... storage rooms, etc.) protected with auto-
matic protection.
(d) One and two story residential apartment
buildings under 5,000 square feet with
direct exiting shall be required to be pro-
vided with individual approved products of
combustion detector(s) centrally located
in the corridor and area giving access to
rooms used for sleeping purposes. When
activated, the detector(s) shall be capable
of providing an alarm for all occupants of
the dwelling.
(e) Hotels and motels, fraternities and sororities,
dormitories two or more stories in height
with 6-49 persons shall have a Type E system.
5. Group R3 Occupancies
Every dwelling shall be provided with approved
detectors of products of combustion other than heat
mounted on the ceiling at a point centrally located
in the corridor or area giving access to rooms used
for sleeping purposes. When activated, the detec-
tor(s) shall be capable of providing an alarm for
all occupants of the dwelling.
6. Other Occupancies (Existing)
-20-
(a) Day Care Home: 7-12 Children in the
Family Abode
The installation of self-contained smoke
detectors at the top of open stairways shall
be required where upper floors are used for
day care purposes and the Size, arrangement
and occupancy is such that a fire would not
in itself give adequate warning for all to
escape.
(b) Group Day Care Home: 1-12 Children in Other
than Family Abode
An approved manual fire alarm system shall
be provided if more than one floor level is
used for day care purposes and the size,
arrangement and occupancy of the building
is such that a fire would not in itself
give adequate warning for all to escape.
All stairwells serving as required means of
egress from floors above the second shall be
enclosed and provided a continuous protected
passageway to the outside.
EXCEPTION: Un-enclosed stairwells connecting
not more than three (3) floors may be allowed
if the building is of fire-resistive con-
struction; or, provided with automatic
sprinkler protection; or, provided with smoke
-21-
detectors in all means of egress and open
areas.
Second floor corridors shall be 1/2 hour
rated unless provided with automatic
sprinklers; or, smoke detection; or, direct
means of egress from each occupied room.
(c) Day Care Center: 13 or more Children in the
Family Abode.
A manual fire alarm system shall be provided
in all homes housing 50 or more children or
where housing is on more than one floor
level. Sounding devices and pull stations
shall be so arranged as to be accessible and
audible from all occupied areas. Homes
housing less than 50 children all on one
floor level may be required to provide a
fire alarm system if the size, arrangement,
or occupancy is such that a fire would not
in itself give adequate warning for all to
escape.
(d) Day Care Center: 13 or more Children in
Other than Family Abode
All stairwells serving as required means
of egress shall be enclosed and provide a
continuous protected passageway to the out-
side.
EXCEPTION: Stairwells connecting not more
-22-
than two (2) floors may be allowed if the
building is of fire-resistive construction;
or, provided with automatic sprinkler pro-
tection; or, provided with smoke detectors
in all means of egress and open areas. An
approved manual fire alarm system shall be
provided except where day care is limited
to the first floor only, the licensed capa-
city does not exceed 50, and each occupied
area has a direct exit to the outside.
(e) Maternity Service: Full-time care for
Mothers prior to Delivery, Residential care
for Mothers and Infants, Other Services
Related to Unwed Mothers
All stairwells serving as reqUired means of
egress from floors above the second shall be
enclosed and provide a continous protected
passageway to the outside.
EXCEPTION: Un-enclosed stairwells connecting
not more than three (3) floors may be allowed
if the building is of fire-resistive con-
struction; or, provided with automatic sprink-
ler protection; or, provided with smoke de-
tectors in all means of egress and open
areas.
-23-
An approved manual fire alarm system shall
be provided when the resident occupant load
exceeds 15.
EXCEPTION: Not required in building three
(3) stories or less in height where each
sleeping room has an exit directly to the
outside. Nursery areas not under continuous
supervision shall be provided with automatic
smoke detection.
-24-