HomeMy WebLinkAbout3966 SOMMAR OF ORDINA C NO. OZ ,&
This Ordinance adopts, by reference, state mandated buildin9
codes as well as permissive codes with modification.
SECTION 1: This section entitled this Ordinance "City of
Bremerton Building and Fire Safety Code."
SECTION 2: This section repeals all existing ordinances
pertainin9 to the Building Exit Code, the Uniform Building Code,
the Dangerous Building Code, the Plumbing Code, the Swimming Pool
Code, the Fire Code and Fire Prevention Code, the Life Safety
Code, the Mechanical Code includin9 provisions relatin9 to gas
fitters and mechanical installer's license requirements, the Sign
Code, and billboard requirements.
SECTION 3: This section provides that the purpose of the
ordinance is to enhance the health, safety and welfare of the
public as a whole by insuring that buildings, dwellings,
structures and land will be constructed, maintained and/or used
in a manner so as to reduce hazards, increase durability, and
require consistent patterns of community development.
S~CTION 4: This section adopts, by reference, the 1982
edition of the Uniform Administrative Code, except Table 3(b);
the 1982 edition of the Uniform Building Code and Uniform
Building Code Standards, including appendices in Chapters 1, 7,
11, 32, 35, 38, 49, 55 and 70; the 1982 edition of the Uniform
Mechanical Code, including Chapter 22 and appendices A, B and C;
the 1982 edition of the Uniform Fire Code and Uniform Fire Code
Standards, including appendices I(a), I(b), II(b), II(c), III(a),
III(b), IV(a), V(a) and VI(a); the 1982 edition of the Uniform
Plumbing Code and Standards, including appendices A, B, C, D, G
and F, except for Chapter 11; the 1982 edition of the Uniform
Sign Code; the 1982 edition of the Uniform Code for the Abatement
of Dangerous Buildings and two sets of regulations promulgated by
the Washington State Building Code Advisory Council entitled
"Regulation for Barrier Free Facilities"; and the 1983 Washington
State Energy Code.
1
SECTION 5: This section states that in case of a conflict
among the codes adopted in Section 4, the Code first named shall
govern.
SECTION 6: This section sets out abbreviations for the
titles of the various codes listed in Section 4.
SECTION 7: This section charges the Building Official with
the administration and enforcement of the City of Bremerton
Building and Fire Safety Code, except for Section 4(d) (the
Uniform Fire Code) which shall be enforced by the Fire Chief and
Appendix 70 of the Uniform Building Code which shall be enforced
by the City Engineer.
SECTION 8: This section provides amendments to Part I,
Chapter 3; Part IV, Chapter 25; Part X, Chapter 54; and Appendix
Chapter I of the Uniform Building Code. The amendments to Part
I, Part IV and Part X include deleting permit requirements of
§301(a) for buildings within group R-3 and group M occupancies
where repair costs are less than $200.00; deleting exceptions
contained in §301(b)(1)(2); broadening a permit exemption
contained in §301(b)(8) to include installation of floor covering
material; consolidating the plan review fee of §304(b) when an
individual submits plans for two or more identical buildings of
group R-3 or group M occupancies; deleting the requirement of
§305(e) for an underfloor inspection; exempting group R and M
occupancies from the foundation ventilation requirements of
§2516(c)(6) and instead requiring group R and M occupancies to
comply with the 1979 foundation ventilation requirements;
requiring that group R occupancies be subject to Chapter 54,
except that for R-3 occupancies glazing located more than
eighteen inches (18") above the surface used as a walking
surface, glazing which is no greater than eighteen inches (18")
in any dimension and glazing protected by a guardrail, handrail,
or other approved barrier are not co[%sidered hazardous locations
under §5406(d).
The amendments to Appendix Chapter 1 entitled "Life
Safety Requirements for Existing Buildings" include redefining
and ~enumbering the stated purpose of §108(a) to be to protect
2
the general public as a whole and amending and renumbering
§i08(b) to allow an owner eighteen (18) months after notice of
non-compliance with the Appendix to submit plans for compliance
and another eighteen (18) months to bring the building into
conformance with the Appendix; provided, however, that this
lenient time compliance requirements does not apply if the
existing building is otherwise declared to be dangerous under the
Uniform Code for the Abatement of Dangerous Buildings. A new
subsection is added to the appendices clarifying the
responsibilities of owners, occupants and tenants. This new
subsection states that the owner of a building remains liable for
code violations, even though an obligation is imposed on
occupants of the building and even though the owner has, by
agreement, imposed on the occupant the duty of furnishing
required equipment to comply with this code. Every owner, or his
agent, is also responsible for keeping that part of the building
or premises which he occupies or controls in a clean, sanitary
and safe condition, including the shared or public areas in a
building containing two (2) or more dwelling units. This
"responsibility" subsection further imposes on an owner the duty
to furnish required and approved sanitary facilities and
facilities for the prevention and extermination of insect and
rodent infestation. The occupant of a dwelling unit is
responsible for keeping in a clean, sanitary and safe condition
that part of the dwelling or premises which he occupies and this
includes properly disposing of his rubbish, garbage or other
organic waste and maintaining where required by the health
ordinance or the health officer approved devices, equipment or
facilities. A new subsection is added designating substandard
buildings as public nuisances and requiring abatement under the
procedures of ~203(b) of the Uniform Building Code using the more
lenient compliance time requirements of Appendices Chapter 1,
unless the condition also constitutes a dangerous building, in
which case compliance time requirements as set forth in the
Uniform Code for the Abatement o~ Dangerous Buildings must be
followed. A new section is added defining a nuisance as a public
nuisance known as common law or in equity jurisprudence as an
attractive nuisance, overcrowding, insufficient ventilation or
illumination, inadequate or unsanitary sewage or plumbing
facilities, uncleanliness and conditions which render air, food
or drink unwholesome or detrimental to human health. The exit
requirements contained in §109(b) are renumbered and the
requirement that exterior stairs be of non-combustible
construction is deleted. A new subsection is added to the exit
requirements of the appendices, which requires that every
dwelling unit or guestroom shall have access directly to the
outside or to a public corridor; all buildings or portions
thereof shall be provided for exits, exit ways and appurtenances
as required by Chapter 38 of the U.B.C. A new section is added
defining substandard buildings to include public nuisances
defined above, buildings with inadequate exits, inadequate fire
protections or fire fighting equipment, and improper occupancy.
SECTION 9: This section provides amendments to Appendix
Division 1-A of the Uniform Fire Code, entitled Life Safety
Requirements to Existing Buildings. Because this appendix is
identical to Appendix Chapter 1 of the Uniform Building Code, the
amen~nents contain the same modifications and additions set forth
in the second paragraph of §8 above.
SECTfON 10: This section sets forth amendments to the
Oniform Plumbing Code. §20.6 is amended to allow the owner of
real property to obtain a permit to do plumbing or drainage work
on his real property. The schedule of fees in §20.7 is
supplemented to provide for no fee when a plumbing permit is
obtained in conjunction with a building permit for new or
remodeled work for group R-3 and group M occupancies and to
include permit fees for each private swimming pool for each
semi-public swimming pool and for each public swimming pool of
$40.00, $50.00 and $75.00, respectively. §20.9 is amended to add
a provision subjecting any person who calls for, and receives, a
test and/or inspection where in fact the work is not ready to be
tested and/or inspected shall pay to the administrative authority
a ~ee of $30.00 which must be paid prior to any further call for
inspection and/or test.
SECTION 11: This section provides amendments to the Uniform
Sign Code. §23 is amended to add a definition of billboard.
§1501 is added to require signs to conform to zoning regulations.
§1502 is added to require persons who own billboards to keep on
file with the City Clerk a certificate of insurance for the
amount of $1,000,000.00 per occurrence for bodily injury and
property damage unless the solid portion of the billboard's
advertising surface contains less than forty-eight square feet
(48'). §1503 is added to require billboards to be constructed
and maintained in those distcicts within the City authorized by
the City zoning ordinance. §1504 is added to provide that the
vertical dimension of a solid face billboard shall not exceed
fifteen feet (15') nor be more than thirty feet (30') above the
ground or sidewalk, depending on whether the Building Official
determines that the ground beneath the sidewalk is below sidewalk
g~ade. This section also requires that billboards located on the
ground have an open space of at least eighteen inches (18")
between the lower edge thereof and the ground and provides that
this open space may be occupied by lattice work if the open
spaces in said lattice are at least equal in width to the width
of the members of which the lattice is constructed. §1505 is
added to prohibit billboards placed on walls or roofs of
buildings from interfering with the use of any fire escape,
standpipe, necessary window, or egress from the building. In
addition, this section provides that billboards shall not project
into the street or alley a greater distance than is permitted for
appendages on buildings. §1506 is added to prohibited billboards
other than electric signs on roofed buildings from having an
advertising surface whose vertical dimension exceeds twenty feet
(20') and provides that the billboard shall not be higher than
twenty-five feet (25') above the roof. Electric signs shall not
be higher than seventy-five feet (75') above the roof. In
addition, this section provides that bents supporting the face of
a billboard shall, if located above the roof of a building, be at
5
least six feet (6') apart and the bottom of the face shall be at
least five feet (5') above the roof. The advertising surface of
such billboard must be no closer to the front lot line than five
feet (5') or be in line with the average depth of the front line
of the buildings adjacent on each side. §1507 is added to
provide that any billboard which becomes unsafe or defective
shall be removed and made to conform to the terms and
requirements of this Code. The owner of the billboard or the
owner of the ground upon which the billboard is built is
responsible for compliance. §1508 is added to require every bill
poster to contain the bill poster's name on every structure or
portion thereof upon which he places advertisements.
S~CTION 12: This section entitled "Mobile Homes" provides a
definition of mobile home as a ~actory assembled structure having
more than 320 square feet of gross floor area capable for using
as a dwelling unit with its own chasis and capable of being towed
on public highways through the use of its own axles and wheels;
provided, that a mobile home does not lose its character as a
mobile home by removal of its wheels and axles or its placement
on a permanent foundation. This section excludes mobile homes
from the provisions of the Uniform Building Code, the Uniform
Mechanical Code, the Uniform Plumbing Code as such code applies
to internal plumbing, and from the regulations for Barrier Free
Facilities. The remainder of this Building and Fire Safety Code
ordinances however, applies to mobile homes. This section also
~equires that a person obtain a permit from the Building
Official, at a cost of $75.00 or $50.00 if the mobile home is to
be placed within a mobile park, before the mobile home is located
or placed on any lot or parcel. The Building Official is charged
with issuing 'the permit if the mobile home conforms to the
requirements of the zoning ordinance and meets the mobile home
installation requirements o~ WAC 296-150(B).
SECTION 13: This section entitled "Factory Built Housing"
provides a definition of factory built housing to include any
structure designed primarily for human occupancy (other than a
mobile home) the structure or any room of which is either
entirely or substantially prefabricated or assembled at a place
other than the building site. This section e~cludes factory
built housing from the provisions of the Uniform Building Code,
the Uniform Mechanical Code, the Uniform Plumbing Code as such
code applies to internal plumbing, and regulations for Barrier
Free Facilities° ~rhe remainder of the Building and Fire Safety
Code applies to factory built housing. This section also
requires each factory built housing to have a permanent
foundation and prohibits location of a factory built house on any
lot or parcel until the Building Official approves a foundation
plan and issues a permit, the individual pays a fee in the amount
of $75.00, the Building Department determines that the unit of
factory built housing meets the requirement of the zoning
ordinance, and that the foundation forms have been properly set,
and the Building Department subsequently determines that the
foundation has been properly constructed once said ~oundation is
poured, the forms removed and the mud still ia place.
SECTION 14: l~his section entitled "Penalties" provides:
"Unless otherwise more specifically provided, any
person, firm or corporation violating any of the p~ovisions of
the City of Bremerton Building and Fire Safety Code shall be
deemed guilty of a misdemeanor and each such person, firm or
corporation shall be deemed guilty of a separate offense for each
and every day or portion thereof during which any violation of
any provisions of the City of Bremerton Building and Fire Safety
Code is committed, continued or permited and, upon conviction of
any such violation, such person, firm or corporation shall be
punished by a fine of not more than Five Hundred Dollars
($500.00) or by imprisonment for not more than ninety (90) days
or by both such fine and imprisonment for each violation."
SECTION 15: This section provides that if any portion of
this ordinance is found invalid, the remainder of the ordinance
shall not be affected.
Any person desiring the full text of the foregoing Ordinance
may so request from the City Clerk and it shall be provided
without charge.
7
.- APPROVED by the City Council on the first reading on
~D . , 1985.
PAS,' by the City Council of the City of Bremerton, signed
by the Mayor and attested to by the City Clerk in authentication
of such passage on ~. ~/'~.~.~{. /g , 1985.
ATTEST:
KATHLEEN L. MCCLUSKEY, City Clerk
Director of Administratives Services
8
AN ORDINANCE REGARDING TBE STATE BUILDING CODE ACT A ~
WHEREAS, RCW 19.27 requires the City of Bremerton to
administer and enforce the State Building Code Act within the
incorporated areas within its boundaries; and
WHEREAS, certain modifications and/or amendments to the
State Building Code Act as it applies to the City of Bremerton
are desirable;
THE CITY OF BREMERTON DOES HEREBY ORDAIN:
This ordinance shall be known as the City of Bremerton
Building and Fire Safety Code.
~qT~Q~_~.._BDpD~i of ordinance #3427, 2815, 1417 (Building Exit
Code, B.M.C. 17.06); ordinance #3755, 3582, 3548 (Uniform
Building Code, B.M.C. 17.04); ordinance #2824, 2428, 2106, 2041,
1972 (Fire Zones, B.M.C. 17.08); ordinance 1221, 1119 (Building
Inspector B.M.C. 17.12); ordinance #3439 (Dangerous Buildings
Code, B.M.C. 17.20); ordinance #3675, 3605, 3401 (Plumbing Code
B.M.C. 17.28); ordinance 3394 (Swimming Pool Code, B.M.C. 17.52);
ordinance #3678, 3639, 3428, 2802, 2479 (Fire Code and Fire
Prevention Codes, B.M.C. 18.04); ordinance #3498 (Life Safety
Code, B.M.C. 18.16); ordinance #3730, 3617, 3607 (Mechanical
Code, Gas Fitters and Mechanical Installers License B.M.C.
17.48); ordinance #3112, 3071, 2270, 2213, 2170, 2168, 2162 (Sign
Code, B.M.C. 17.44); and ordinance #3277, 2149 (Billboards,
B.M.C. 17.46)
- 1 -
The purpose of the City of Bremerton Building and Fire
Safety Code is to enhance the health, safety and welfare of the
public as a whole by ensuring that buildings, dwellings,
structures, and land will be constructed, maintained and/or used
in a manner so as to reduce hazards, increase durability and
require consistent patterns of Community Development; Provided,
notwithstanding anything in this ordinance or in the codes
adopted in Section 4 to the contrary, this ordinance and the
codes adopted in Section 4 establish duties owed to the public as
a whole and not any duties to protect any person or class of
persons.
The following codes and regulations are hereby adopted by
reference subject to the modifications and/or amendments set
forth in Sections 8, 9, 10:
a. International Conference of Building Officials,
Uni£o~_.~m£O~~SLe_~O~ (1982 ed.)
Except: Table 3 B
b. International Conference of Building Officials,
~DD~Z~a, (1982 ed.) together with those appendices
in Chapters 1, 7, 11, 32, 35, 38, 49, 55 and 70;
c. International Association of Plumbing and Mechanical
Officials and International Conference of Building
Officials, ~ni£e[m___~c~~_Code (1982 ed.)
together with Chapter 22 and Appendices A, B and C.
d. Western Fire Chiefs Association and International
Conference of Building Officials,
aD~_OD~_9~_._F_J~_CQ~__$~aD~ards (1982 ed.) together
with Appendices I A, I B, II B, II C, III A, III B,
IV A, V A, and VI A;
e. International Association of Plumbing and Mechanical
Officials and International Conference of Building
Officials, O_~o~_~u~_~d~_and_S~aDDa~ (1982
- 2 -
ed.) together with Appendices A, B, C, D, G, and H
PJ~Av/~, Chapter 11 is not adopted.
f. International Conference of Building Officials,
ikLi~_$i~D__CD~e (1982 ed. ).
g. International Conference of Building Officials,
(1982 ed.);
h. Washington State Building Code Advisory Councils,
R e g ul fttiQ n__ _~__ D_aZ/~ -_~e___F~[t_i e s; adopted
pursuant to R.C.W. 70.92.100 and
i. Washington State Building Code Advisory Councils,
h[aStLin~gn_S~a~es_~n~r~2__Cg_~ (1980), WAC 51-12.
S~if~T]Q~_~_~__CgD~li~_~mpn~_~9~. In cases of conflict among the
codes adopted in Section 4 A-I, the Code first named shall govern
in descending listing.
a. International Conference of Building Officials,
iL~D__D3Ai~4~_Code (1982 ed.) shall be known as
Uniform Building Code or UBC.
b. International Conference of Building Officials,
~aifg~m_A~miDi~La~iDB_~Q~ (1982 ed.) shall be known
as the Uniform Administrative Code or the UAC.
c. International Association of Plumbing and Mechanical
officials and International Conference of Building
Officials, ~_~o3uR_~~i~al_~ode (1982 ed.) shall
be known as the Uniform Mechanical Code of UMC.
d. Western Fire Chiefs Association and International
Conference of Building Officials,
(1982 ed.) shall be known as Uniform Fire Code or
UFC.
e. International Association of Plumbing and Mechanical
Officials and International Conference of Building
Officials, QOi~Q~_~l~i~_~ (1982 ed.) shall be
known as Uniform Plumbing Code of UPC.
- 3 -
f. International Conference of Building Officials,
(1982 ed.) shall be known as the Dangerous Buildings
Code or DBC.
g. International Conference of Building Officials,
IkLLfDXm_~tglL_CQd~ (1982 ed.) shall be known as the
Uniform Sign Code or USC.
The Building Official is charged with the administration
and enforcement of the City of Bremerton Building Fire Safety
Code, except that the Fire Chief shall enforce Section 4d (U.F.C)
above with associated amendments in Section 9 below. To this end
he/she may retain necessary personnel, conduct inspections and
investigations, issue appropriate permits, maintain necessary
records and files, and do, or cause to be done, all things
necessary and proper for the administration and enforcement of
the City of Bremerton Building Fire Safety Code. Appendix 70 of
the UBC shall be enforced by the City Engineer.
a. Permit exemption for repair amendments. UBC, Section
301 (a), is hereby amended to read as
follows:
Section. 301 (a) Permits Required. It shall be
unlawful for any person, firm or corporation to
erect, construct, enlarge, alter, repair, move,
improve, remove, convert or demolish any building or
structure regulated by this code, except as specified
in subsection (b) of this section or causes same to
be done without first obtaining a separate permit for
each building or structure from the Building
Official: ~Qy~DED, nQ_~]D__p~3~Li_t_~L~_~qui~,_~
~.~PgP_ ~_ _qqqu~_~q~es _~e - the _.~
- 4 -
b. Deletion of exceptions. UBC, Section 301 (b) (1) (2)
are hereby deleted.
c. Addition to an exemption. UBC, Section 301 (b) (8) is
amended to read as follows; painting, papering and
similar finish work
d. Fee Schedule Amendment. Section 304 (b) is hereby
amended to read as follows: Plan Review Fees. When
a plan or other data is required to be submitted by
Section (b) of Section 302, a Plan Review Fee shall
be paid at the time of submitting plans and
specifications for review. Said Plan Review Fee
shall be 65% of the building permit fee as shown in
table No. 3-A; ~g_Q33JP~, if ~_~aQB s~~~~
p~___~i f ica~,_~ t~__12)~ _~[_~o~_e_~~i~
for the_~DpDD_fiDgb_Dl~n_.BDD~gyond. Where plans are
incomplete or changed so as to require additional
plan review, an additional Plan Review Fee shall be
charged at the rate shown in table No. 3-A.
e. Deleation of under-floor inspection. Section 305 (e)
(2) is hereby modified to read. CONCRETE SLAB
Inspection: to be made after all in-slab building
service equipment, conduit, piping accessories and
other ancillary equipment items are in place but
before any concrete is poured.
f. Amendments regarding foundation ventilation for
certain occupancies.
(1) UBC, Section 2516 c (6) shall have no
application to group R and M occupancies.
(2) UBC Section 2516 (c) is amended to add a new
sub-section (12) which shall be as follows:
- 5 -
~f~:; ~_gD~X~iDD]Z_D~D~" ~s_J~9 b~_~gvised to; read
_a. ~ _ _i~Ldj~c_a~t_e_d_ i R _~ h ~_ J~933_ac_O_dm.~Lh a t
M
~bD~___J~3'J__Dm~__._~q_t ~i~_,%h~.__l.~2'l_~n_ any
g. Amendment regarding glass and glazing.
(1) UBC, Section 5401 (a)l is hereby amended to read
as follows:
(a) Exterior glass and glazing in all
occupancies except Group M not over three
stories in height; and
(2) UBC Section 5406 (d) is amended to add a new
subsection 7 which shall read as follows:
7. Subsection (d) hereof shall have no
application to R-3 occupancies in the following
situations:
(a) For glazing located more than eighteen (18)
inches above the surface normally used as a
walking surface;
(b) For glazing which is no greater that
eighteen (18) inches in any dimension; and
(c) For glazing protected by a guardrail,
handrail or other approved barrier.
- 6 -
h. Appendix Chapter 1 is amended to read as follows:
GENERAL
Section 107.
(a) Purpose. The purpose of this chapter is to
enhance the health, safety and welfare of the
general public by providing for alterations to
certain such existing buildings which do not
meet the minimum requirements of the Code.
EXCEPTION: Group R, Division 3 or Group M
Occupancies.
(b) Effective Date. Within 18 months after notice
to the owner of a violation of this appendix,
plans for compliance shall be submitted and
approved, and within 18 months thereafter, the
work shall be completed or the building shall be
vacated until made to conform, provided that if
the Building Official declares that conditions
in violation of this appendix also constitute a
dangerous building under Section 302 of the
Dangerous Building Code or Section 203 of the
UBC, the Building Official shall determine the
time compliance requirements ih accordance with
Section 401 of the uniform code for the
Abatement of Dangerous Buildings.
(c) Alternate Materials and Methods. Alternate
materials and methods may be used, provided such
materials or methods comply with the spirit and
intent of this appendix.
The Building Official may modify any of the
provisions of this appendix in conformance with
Section 106 of this code.
(d) Responsibilities Defined. Every owner remains
liable for violations of duties imposed upon him
by this code even through an obligation is also
imposed on the occupants of his building, and
even though the owner has, by agreement, imposed
- 7 -
on the occupant the duty of furnishing required
equipment to comply with this code.
Every owner, or his agent, in addition to being
responsible for maintaining his building in a
sound structural condition, shall be responsible
for keeping that part of the building or
premises which he occupies or controls in a
clean, sanitary and safe condition, including
the shared or public areas in a building
containing two or more dwelling units.
Every owner shall, where required by this code,
the health ordinance or the health officer,
furnish and maintain such approved sanitary
facilities as required, and shall furnish and
maintain approved devices, equipment or
facilities for the prevention of insect and
rodent infestation, and where infestation has
taken place, shall be responsible for the
extermination of any inspects, rodents or other
pests when such extermination is not
specifically made the responsibility of the
occupant by law or ruling.
Every occupant of a dwelling unit, in addition
to being responsible for keeping in a clean,
sanitary and safe condition that part of the
dwelling or dwelling unit or premises which he
occupies and controls, shall dispose of all his
rubbish, garbage and other organic waste in a
manner required by the health ordinance and
approved by the Health Officer.
Every occupant shall, where required by this
code, the health ordinance or the health
officer, furnish and maintain approved devices,
equipment or facilities necessary to keep his
premises safe and sanitary.
- 8 -
(e) Substandard Buildings. Ail buildings or
portions thereof which are determined to be
substandard as defined in Section 116 of this
Appendix are hereby declared to be public
nuisances and shall be abated by repair,
rehabilitation, demolition or removal in
accordance with the procedure specified in
Section 401 of the Dangerous Building Code;
provided however that the time compliance
requirements of Section 107(b) of the Appendix
will apply if the condition(s) are determined by
the Building Official to be substandard and not
rise to the level of a dangerous building
defined in Section 301 of the Dangerous Building
Code or Section 203 of UBC.
DEFINITIONS
Section 108 Nuisance.
The following shall be defined as nuisances:
1. Any public nuisance known at common law or in
equity jurisprudence.
2. Any attractive nuisance which may prove
detrimental to children whether in a building, on
the premises of a building, or upon an unoccupied
lot. This includes any abandoned wells, shafts,
basements or excavations; abandoned refrigerators
and motor vehicles; or any structurally unsound
fences or structures; or any lumber, trash,
fences, debris or vegetation which may prove a
hazard for inquisitive minors.
3. Whatever is dangerous to human life or is
detrimental to health, as determined by the
health officer.
4. Overcrowding a room with occupants.
5. Insufficient ventilation or illumination.
- 9 -
6. Inadequate or unsanitary sewage or plumbing
facilities.
7. Uncleanliness, as determined by the health
officer.
8. Whatever renders air, food or drink unwholesome
or detrimental to the health of human beings, as
determined by the Health Officer.
EXITS
Section 109.
(a) Number of Exits. Every floor above the first
story used for human occupancy shall have access
to at least two separate exits, one of which may
be an exterior fire escape complying with
Subsection (d) of this section. Subject to the
approval of the Building Official, an approved
ladder devise may be used in lieu of a fire
escape when the construction feature or location
of the building on the property make the
installation of a fire escape impracticable.
EXCEPTION: In all occupancies, second stories
with an occupancy load of 10 or less may have
one exit.
An exit ladder device when used in lieu of a
fire escape shall conform with U.B.C. Standard
No. 33-3 and the following:
1. Serves an occupant loan of 10 or less or a
single dwelling unit or guest room.
2. The building does not exceed three stories
in height.
3. The access is adjacent to an opening as
specified for emergency egress or rescue or
from a balcony.
4. Shall not pass in front of any building
opening below the unit being served.
- 10 -
5. The availability of activating the device
for the ladder is accessible only from the
opening or balcony served.
6. So installed that it will not cause a person
using it to be within 6 feet of exposed
electrical wiring.
(b) Stair Construction. All required stairs shall
have a minimum run of 9 inches and a maximum
rise of 8 inches and shall have a minimum width
of 30 inches exclusive of handrails. Every
stairway shall have at least one handrail. A
landing having a minimum 30-inch run in the
direction of travel shall be provided at each
point of access to the stairway.
EXCEPTION: Fire escapes as provided for in this
Section.
EXCEPTION: On building of Types III, IV and V,
provided the exterior stairs are constructed of
wood not less than 2-inch nominal thickness.
(c) Corridors. Corridors of Groups A, B, E, I, H
and R, Division 1 Occupancies serving as an exit
for an occupant load of 30 or more shall have
walls and ceilings of not less than one-hour
fire-resistive construction as required by this
code. Existing walls surfaced with wood lath
and plaster in good condition or 1/2 inch gypsum
wallboard or openings with fixed wired glass set
in steel frames are permitted for corridor walls
and ceilings and occupancy separations when
approved. Doors opening into such corridors
shall be protected by 20-minute fire assemblies
or solid wood doors not less than 1 3/4-inch-
thick. Where the existing frame will not
accommodate the 1 3/4-inch-thick door, a 1 3/8-
inch-thick solid bonded wood core door or
equivalent insulated steel door shall be
- 11 -
permitted. Doors shall be self-closing or
automatic-closing by smoke detection. Transoms
and openings other than doors from corridors to
rooms shall comply with Section 3305 (h) of this
code or shall be covered with a minimum of 3/4-
inch plywood or 1/2-inch gypsum wallboard or
equivalent material on the room side.
EXCEPTION: Existing corridor walls, ceilings
and opening protection not in compliance with
the above may be continued when such buildings
are protected with an approved automatic
sprinkler system throughout. Such sprinkler
system may be supplied from the domestic water
system if it is of adequate volume and pressure.
(d) Fire Escapes.
1. Existing fire escapes which in the opinion
of the Building Official comply with the
intent of this section may be used as one of
the required exits. The location and
anchorage of fire escapes shall be of
approved design and construction.
2. Fire escapes shall comply with the
following:
Access from a corridor shall not be through
an intervening room.
All openings within 10 feet shall be
protected by three-fourths-hour fire
assemblies. When located within a recess or
vestibule, adjacent enclosure walls shall be
of not less than one-hour-fire-resistive
construction.
Egress from the building shall be by a clear
opening having a minimum dimension of not
less than 29 inches. Such openings shall be
openable from the inside without the use of
a key or special knowledge or effort. The
- 12 -
sill of an opening giving access shall be
not more than 30 inches above the floor of
the building or balcony.
Fire escape stairways and balconies shall
support the dead load plus a live load of
not less than 100 pounds per square foot and
shall be provided with a top and
intermediate handrail on each side. The
pitch of the stairway shall not exceed 60
degrees with a minimum width of 18 inches.
Treads shall be not less than 4 inches in
width and the rise between treads shall not
exceed 10 inches. All stair and balcony
railings shall support a horizontal force of
not less that 50 pounds per lineal foot of
railing.
Balconies shall be not less that 44 inches
in width with no floor opening other than
the stairway opening greater that 5/8 inch
in width. Stairway openings in such
balconies shall be not less that 22 inches
by 44 inches. The balustrade of each
balcony shall be not less that 36 inches
high with not more than 9 inches between
balusters.
Fire escapes shall extend to the roof or
provide an approved gooseneck ladder between
the top floor landing and the roof when
serving buildings four or more stories in
height having roofs with less than 4:12
slope. Fire escape ladders shall be
designed and connected to the building to
withstand a horizontal force of 100 pounds
per lineal foot; each rung shall support a
concentrated loan of 500 pounds placed
anywhere on the rung. All ladders shall be
- 13 -
at least 15 inches wide, located with 12
inches of the building and shall be placed
flatwise relative to the face of the
building. Ladder rungs shall be 3/4 inch in
diameter and shall be located 12 inches on
center. Openings for roof access ladders
through cornices and similar projections
shall have minimum dimensions of 30 inches
by 33 inches.
The lowest balcony shall be not more that 18
feet from the ground. Fire escapes shall
extend to the ground or be provided with
counterbalanced stairs reaching to the
ground.
Fire escapes shall not take the place of
stairways required by the codes under which
the building was constructed.
Fire escapes shall be kept clear and
unobstructed at all times and maintained in
good working order.
(e) Exit and Fire Escape Signs. Exit signs shall be
provided as required by this code.
EXCEPTION: The use of existing exit signs may
be continued when approved by the building
official.
All doors or windows providing access to a fire
escape shall be provided with fire escape signs.
(f) Exits. Every dwelling unit or guest room shall
have access directly to the outside or to a
public corridor. All buildings or portions
thereof shall be provided with exits, exitways
and appurtenances as required by Chapter 33 of
the Building Code.
Every sleeping room below the fourth story shall
have at least one operable window or exterior
door approved for emergency escape or rescue.
- 14 -
The units shall be operable from the inside to
provide a full clear opening without the use of
separate tools.
All escape or rescue windows from sleeping rooms
shall have a minimum net clear opening of 5.7
square feet. The minimum net clear opening
height dimension shall be 24 inches. The
minimum net clear opening width dimension shall
be 20 inches. Where windows are provided as a
means of egress or rescue they shall have a
finished sill height not more than 44 inches
above the floor.
ENCLOSURE OF VERTICAL SHAFTS
Section 110.
Interior vertical shafts, including but not limited
to stairways, elevator hoistways, service and utility
shafts, shall be enclosed by a minimum of one-hour
fire-resistive construction. All openings into such
shafts shall be protected with one-hour fire
assemblies which shall be maintained self closing or
be automatic closing by smoke detection. All other
openings shall be fire protected in an approved
manner. (Existing fusible link-type automatic door
closing devices may be permitted if the fusible link
rating does not exceed 135 o F.).
EXCEPTIONS:
1. In other than Group 1 Occupancies, an enclosure
will not be required for openings serving only
one adjacent floor.
2. Stairways need not be enclosed in a continuous
vertical shaft if each story is separated from
other stories by one-hour fire-resistive
construction or approved wired glass set in steel
frames. In addition, all exit corridors shall be
sprinklered and the openings between the corridor
- 15 -
and occupant space have at least one sprinkler
head above the openings on the tenant side. The
sprinkler system may be supplied from the
domestic water supply if of adequate volume and
pressure.
3. Vertical openings need not be protected if the
building is protected by an approved automatic
sprinkler system.
FIRE PROTECTION
Section 111.
Ail buildings or portions thereof shall be provided
with the degree of fire-resistive construction as
required by the Building and Fire Safety Code for the
appropriate occupancy, type of construction and
location on property; and shall be provided with the
appropriate fire-extinguishing systems or equipment
required by Chapter 38 of the Uniform Building Code.
BASEMENT ACCESS OR SPRINKLER PROTECTION
Section 112.
An approved automatic sprinkler system shall be
provided in basements or stories exceeding 1500
square feet in area and not having a minimum of 20
square feet of opening entirely above the adjoining
ground level in each 50 lineal feet or fraction there
of exterior wall on at least one side of the
building. Openings shall have a minimum clear
dimension of 30 inches. Exception: Group R,
Division 3, Occupancies.
If any portion of a basement is located more that 75
feet from required openings, the basement shall be
provided with an approved automatic sprinkler system
throughout.
A substandard sprinkler system may be installed with
the approval of the Fire Chief and Building Official
in those structures as required above.
- 16 -
STANDPIPES
Section 113.
Any buildings over four stories in height shall be
provided with an approved Class I or Class III
standpipe system.
SMOKE DETECTORS
Section 114.
Every dwelling unit and every guest room in a hotel
or lodging house used for sleeping purposes shall be
provided with smoke detectors installed in accordance
with this code.
SEPARATION OF OCCUPANCIES
Section 115.
Occupancy separations shall be provided as specified
in Section 503 of this code. When approved by the
building official, existing wood lath and plaster in
good condition or 1/2-inch gymsum wallboard may be
acceptable where one-hour occupancy separations are
required.
SUBSTANDARD BUILDINGS
DEFINITION
Section 116.
(a) General. Any building or portion thereof,
including any dwelling unit, guest room or suite
of rooms, or the premises on which the same is
located, in which there exists any of the
following listed conditions to an extent that
endangers the life, limb, health, property,
safety or welfare of the public or the occupants
thereof shall be deemed and hereby is declared
to be a substandard building.
(b) Nuisance. Any nuisance as defined in this code.
- 17 -
(c) Inadequate Exits. Ail buildings or portions
thereof not provided with adequate exit
facilities as required by this code except those
buildings or portions thereof whose exit
facilities conformed with all applicable laws at
the time of their construction and which have
been adequately maintained and increased in
relation to any increase in occupant loan,
alteration or addition, or any change in
occupancy.
When an unsafe condition exists through lack of,
or improper location of exits, additional exits
may be required to be installed.
(d) Inadequate Fire-protection or Fire-fighting
Equipment. All buildings or portions thereof
which are not provided with the fire-resistive
construction, fire-extinguishing systems, or
early warning equipment required by this code,
except those buildings or portions thereof which
conformed with all applicable laws at the time
of their construction and whose fire-resistive
integrity and fire-extinguishing systems or
early warning equipment have been adequately
maintained and improved in relation to any
increase in occupant load, alteration or
addition, or any change in occupancy.
(e) Improper Occupancy. All buildings or portions
thereof occupied for living, sleeping, cooking
or dining purposes which were not designed or
intended to be used for such occupancies.
(a) Appendix Division I A to read as follows:
1. GENERAL
(a) Purpose. The purpose of this chapter is to enhance
the health, safety and welfare of the general public
- 18-
by providing for alterations to .certain such
existing buildings which do not meet the minimum
requirements of the Code.
EXCEPTION: Group R, Division 3 or Group M
Occupancies.
(b) Effective Date. Within 18 months after notice to
the owner of a violation of this appendix, plans for
compliance shall be submitted and approved, and
within 18 months thereafter, the work shall be
completed or the building shall be vacated until
made to conform, provided that if the Fire Chief
declares that conditions in violation of this
appendix also constitute a dangerous building under
Section 302 of the Dangerous Building Code or
Section 2.201 of UFC, the Fire Chief shall determine
the time compliance requirements in accordance with
Section 401 of the Dangerous Building Code.
(c) Alternate Materials and Methods. Alternate
materials and methods may be used, provided such
materials or methods comply with the spirit and
intent of this appendix.
The Fire Chief may modify any of the provisions of
this appendix in conformance with Section 2.301 of
this code.
(d) Responsibilities Defined. Every owner remains
liable for violations of duties imposed upon him by
this code even through an obligation is also imposed
on the occupants of his building, and even though
the owner has, by agreement, imposed on the occupant
the duty of furnishing required equipmeqt to comply
with this code.
Every owner, or his agent, in addition to being
responsible for maintaining his building in a sound
structural condition, shall be responsible for
keeping that part of the building or premises which
he occupies or controls in a clean, sanitary and
-19 -
safe condition, including the shared or public areas
in a building containing two or more dwelling units.
Every owner shall, where required by this code, the
health ordinance or the Health Officer, furnish and
maintain such approved sanitary facilities as
required, and shall furnish and maintain approved
devices, equipment or facilities for the prevention
of insect and rodent infestation, and where
infestation has taken place, shall be responsible
for the extermination of any inspects, rodents or
other pests when such extermination is not
specifically made the responsibility of the occupant
by law or ruling.
Every occupant of a dwelling unit, in addition to
being responsible for keeping in a clean, sanitary
and safe condition that part of the dwelling or
dwelling unit or premises which he occupies and
controls, shall dispose of all his rubbish, garbage
and other organic waste in a manner required by the
health ordinance and approved by the Health Office.
Every occupant shall, where required by this code,
the health ordinance or the Health Officer, furnish
and maintain approved devices, equipment or
facilities necessary to keep his premises safe and
sanitary.
(e) Substandard Buildings. All buildings or portions
thereof which are determined to be substandard as
defined in Section 10 of this Appendix are hereby
declared to be public nuisances and shall be abated
by repair, rehabilitation, demolition or removal in
accordance with the procedure specified in Section
401 of the Dangerous Building Code; provided however
that the time compliance requirements of Section
l(b) of this appendix will apply if the condition(s)
are determined by the Fire Chief to be substandard
and not rise to the level of a dangerous building
- 20 -
defined in Section 302 of the Dangerous Building
Code or Section 2.201 of the UFC.
DEFINITIONS
Nuisance.
The following shall be defined as nuisances:
1. Any public nuisance known at common law or in equity
jurisprudence.
2. Any attractive nuisance which may prove detrimental to
children whether in a building, on the premises of a
building, or upon an unoccupied lot. This includes any
abandoned wells, shafts, basements or excavations;
abandoned refrigerators and motor vehicles; or any
structurally unsound fences or structures; or any
lumber, trash, fences, debris or vegetation which may
prove a hazard for inquisitive minors.
3. Whatever is dangerous to human life or is detrimental to
health, as determined by the Health Officer.
4. Overcrowding a room with occupants.
5. Insufficient ventilation or illumination.
6. Inadequate or unsanitary sewage or plumbing facilities.
7. Uncleanliness, as determined by the Health Officer.
8. Whatever renders air, food or drink unwholesome or
detrimental to the health of human beings, as determined
by the Health Officer.
2. EXITS
(a) Number of Exits. Every floor above the first story
used for human occupancy shall have access to at
least two separate exits, one of which may be an
exterior fire escape complying with Subsection (d)
of this section. Subject to the approval of the
Building Official or Fire Chief, an approved ladder
device may be used in lieu of a fire escape when
the construction feature or location of the
building on the property make the installation of a
fire escape impracticable.
- 21 -
EXCEPTION: In all occupancies, second stories with
an occupancy load of 10 or less may have one exit.
An exit ladder device when used in lieu of a fire
escape shall conform with U.B.C. Standard No. 33-3
and the following:
1. Serves an occupant load of 10 or less or a
single dwelling unit or guest room.
2. The building does not exceed three stories in
height.
3. The access is adjacent to an opening as
specified for emergency egress or rescue or
from a balcony.
4. Shall not pass in front of any building opening
below the unit being served.
5. The availability of activating the device for
the ladder is accessible only from the opening
or balcony served.
6. So installed that it will not cause a person
using it to be within 6 feet of exposed
electrical wiring.
(b) Stair Construction. All required stairs shall have
a minimum run of 9 inches and a maximum rise of 8
inches and shall have a minimum width of 30 inches
exclusive of handrails. Every stairway shall have
at least one handrail. A landing having a minimum
30-inch run in the direction of travel shall be
provided at each point of access to the stairway.
EXCEPTION: Fire escapes as provided for in this
Section.
EXCEPTION: On building of Types III, IV and V,
provided the exterior stairs are constructed of
wood not less than 2-inch nominal thickness.
(c) Corridors. Corridors of Groups A, B, E, I, H and
R, Division 1 Occupancies serving as an exit for an
occupant load of 30 or more shall have walls and
ceilings of not less than one-hour fire-resistive
- 22 -
construction as required by this code. Existing
walls surfaced with wood lath and plaster in good
condition or 1/2 inch gypsum wallboard or openings
with fixed wired glass set in steel frames are
permitted for corridor walls and ceilings and
occupancy separations when approved. Doors opening
into such corridors shall be protected by 20-minute
fire assemblies or solid wood doors not less than 1
3/4-inch-thick. Where the existing frame will not
accommodate the 1 3/4-inch-thick door, a 1 3/8-
inch-thick solid bonded wood core door or
equivalent insulated steel door shall be permitted.
Doors shall be self-closing or automatic-closing by
smoke detection. Transoms and openings other than
doors from corridors to rooms shall comply with
Section 3305 (h) of this code or shall be covered
with a minimum of 3/4-inch plywood or 1/2-inch
gypsum wallboard or equivalent material on the room
side.
EXCEPTION: Existing corridor walls, ceilings and
opening protection not in compliance with the above
may be continued when such buildings are protected
with an approved automatic sprinkler system
throughout. Such sprinkler system may be supplied
from the domestic water system if it is of adequate
volume and pressure.
(d) Fire Escapes.
1. Existing fire escapes which in the opinion of
the Fire Chief comply with the intent of this
section may be used as one of the required
exits. The location and anchorage of fire
escapes shall be of approved design and
construction.
2. Fire escapes shall comply with the following:
Access from a corridor shall not be through an
intervening room.
- 23 -
Ail openings within 10 feet shall be protected
by three-fourths-hour fire assemblies. When
located within a recess or vestibule, adjacent
enclosure walls shall be of not less than one-
hour-fire-resistive construction.
Egress from the building shall be by a clear
opening having a minimum dimension of not less
than 29 inches. Such openings shall 5e
openable from the inside without the use of a
key or special knowledge or effort. The sill
of an opening giving access shall be not more
than 30 inches above the floor of the building
or balcony.
Fire escape stairways and balconies shall
support the dead load plus a live load of not
less than 100 pounds per square foot and shall
be provided with a top and intermediate
handrail on each side. The pitch of the
stairway shall not exceed 60 degrees with a
minimum width of 18 inches. Treads shall be
not less than 4 inches in width and the rise
between treads shall not exceed 10 inches. All
stair and balcony railings shall support a
horizontal force of not less that 50 pounds per
lineal foot of, railing.
Balconies shall be not less that 44 inches in
width with no floor opening other than the
stairway opening greater that 5/8 inch in
width. Stairway openings in such balconies
shall be not less that 22 inches by 44 inches.
The balustrade of each balcony shall be not
less that 36 inches high with not more than 9
inches between balusters.
Fire escapes shall extend to the roof or
provide an approved gooseneck ladder between
the top floor landing and the roof when serving
- 24 -
buildings four or more stories in height having
roofs with less than 4:12 slope. Fire escape
ladders shall be designed and connected to the
building to withstand a horizontal force of 100
pounds per lineal foot; each rung shall support
a concentrated load of 500 pounds placed
anywhere on the rung. All ladders shall be at
least 15 inches wide, located with 12 inches of
the building and shall be placed flatwise
relative to the face of the building. Ladder
rungs shall be 3/4 inch in diameter and shall
be located 12 inches on center. Openings for
roof access ladders through cornices and
similar projections shall have minimum
dimensions of 30 inches by 33 inches.
The lowest balcony shall be not more that 18
feet from the ground. Fire escapes shall
extend to the ground or be provided with
counterbalanced stairs reaching to the ground.
Fire escapes shall not take the place of
stairways required by the codes under which the
building was constructed.
Fire escapes shall be kept clear and
unobstructed at all times and maintained in
good working order.
(e) Exit and Fire Escape Signs. Exit signs shall be
provided as required by this code.
EXCEPTION: The use of existing exit signs may be
continued when approved by the Fire Chief.
All doors or windows providing access to a fire
escape shall be provided with fire escape signs.
(f) Exits. Every dwelling unit or guest room shall
have access directly to the outside or to a public
corridor. All buildings or portions thereof shall
be provided with exits, exitways and appurtenances
as required by Chapter 33 of the Uniform Building
Code.
- 25 -
Every sleeping room below the fourth story shall
have at least one operable window or exterior door
approved for emergency escape or rescue. The units
shall be operable from the inside to provide a full
clear opening without the use of separate tools.
All escape or rescue windows from sleeping rooms
shall have a minimum net clear opening of 5.7
square feet. The minimum net clear opening height
dimension shall be 24 inches. The minimum net
clear opening width dimension shall be 20 inches.
Where windows are provided as a means of egress or
rescue they shall have a finished sill height not
more than 44 inches above the floor.
4. ENCLOSURE OF VERTICAL SHAFTS
Interior vertical shafts, including but not limited to
stairways, elevator hoistways, service and utility
shafts, shall be enclosed by a minimum of one-hour fire-
resistive construction. All openings into such shafts
shall be protected with one-hour fire assemblies which
shall be maintained self closing or be automatic closing
by smoke detection. All other openings shall be fire
protected in an approved manner. (Existing fusible
link-type automatic door closing devices may be
permitted if the fusible link rating does not exceed
135 o F.)
EXCEPTIONS:
1. In other than Group 1 Occupancies, an enclosure will
not be required for openings serving only one
adjacent floor.
2. Stairways need not be enclosed in a continuous
vertical shaft if each story is separated from other
stories by one-hour fire-resistive construction or
approved wired glass set in steel frames. In
addition, all exit corridors shall be sprinklered
and the openings between the corridor and occupant
space have at least one sprinkler head above the
openings on the tenant side. The sprinkler system
may be supplied from the domestic water supply if of
adequate volume and pressure.
3. Vertical openings need not be protected if the
building is protected by an approved automatic
sprinkler system.
5. FIRE PROTECTION
All buildings or portions thereof shall be provided with
the degree of fire-resistive construction as required by
the Uniform Building Code for the appropriate occupancy,
type of construction and location on property; and shall
be provided with the appropriate fire-extinguishing
systems or equipment required by Chapter 38 of the
Uniform Building Code.
6. BASEMENT ACCESS OR SPRINKLER PROTECTION
An approved automatic sprinkler system shall be provided
in basements or stories exceeding 1500 square feet in
area and not having a minimum of 20 square feet of
opening entirely above the adjoining ground level in
each 50 lineal feet or fraction there of exterior wall
on at least one side of the building. Openings shall
have a minimum clear dimension of 30 inches. Exception:
Group R, Division 3, Occupancies.
If any portion of a basement is located more that 75
feet from required openings, the basement shall be
provided with an approved automatic sprinkler system
throughout.
A substandard sprinkler system may be installed with the
approval of the Fire Chief and Building Official in
those structures as required above.
7. STANDPIPES
Any buildings over four stories in height shall be
provided with an approved Class I or Class III standpipe
system.
8. SMOKE DETECTORS
Every dwelling unit and every guest room in a hotel or
lodging house used for sleeping purposes shall be
provided with smoke detectors installed in accordance
with this code.
9. SEPARATION OF OCCUPANCIES
Occupancy separations shall be provided as specified in
Section 503 of this code. When approved by the Fire
Chief, existing wood lath and plaster in good condition
or 1/2-inch gymsum wallboard may be acceptable where
one-hour occupancy separations are required.
10. SUBSTANDARD BUILDINGS
DEFINITION
(a) General. Any building or portion thereof,
including any dwelling unit, guest room or suite of
rooms, or the premises on which the same is
located, in which there exists any of the following
listed conditions to an extent that endangers the
life, limb, health, property, safety or welfare of
the public or the occupants thereof shall be deemed
and hereby is declared to be a substandard
building.
(b) Nuisance. Any nuisance as defined in this code.
(c) Inadequate Exits. All buildings or portions
thereof not provided with adequate exit facilities
as required by this code except those buildings or
portions thereof whose exit facilities conformed
with all applicable laws at the time of their
construction and which have been adequately
28 -
mai--rained and increased i~ relation to any
increase in occupant loan, alterati~on or addition,
or any change in occupancy.
When an unsafe condition exists through lack of, or
improper location of exits, additional exits may be
required to be installed.
(d) Inadequate Fire-protection or Fire-fighting
Equipment. All buildings or portions thereof which
are not provided with the fire-resistive
construction or fire-extinguishing systems, or
early warning equipment required by this code,
except those buildings or portions thereof which
conformed with all applicable laws at the time of
their construction and whose fire-resistive
integrity and fire-extinguishing systems or early
warning equipment have been adequately maintained
and improved in relation to any increase in
occupant load, alteration or addition, or any
change in occupancy.
(e) Improper Occupancy. All buildings or portions
thereof occupied for living, sleeping, cooking or
dining purposes which were not designed or intended
to be used for such occupancies.
a. Addition of a permit exemption. UPC, Section 20.6 is hereby
amended to read as follows:
Application for Permit
20.6 Any person legally entitled to apply for and receive a
permit shall make such application on forms provided for that
purpose. He shall give a description of the character of the
work proposed to be done, and the location, ownership,
occupancy and use of the premises in connection therewith.
The Administrative Authority may require plans,
specifications or drawings and such other information as he
may deem necessary. Permits shall only be issued to persons
- 29 -
certified pursuant to RCW 18.106; ~dL95Lided, the owner of real
property may obtain a permit to do plumbing or drainage work
on his real property.
If the Administrative Authority determines that the plans,
specifications, drawings, descriptions or information
furnished by the applicant are in compliance with this Code,
he shall issue the permit applied for upon payment of the
required fee as hereinafter fixed.
b. Supplement regarding permit fees. The "Schedule of Fees"
within UPC, Section 20.7 is hereby supplemented to include
the following:
For Group R, Division No fee when plumbing permit
3, and Group M obtained in conjunction with
occupancies ....... building permit for new or remodel
work; all other work shall use
appropriate provisions of Section
20.7
For each private
swimming pool ...... $40.00
For each semi-public
swimming pool ...... $50.00
For each public
swimming pool ...... $75.00
c. Amendment regarding inspection notification. UPC, Section
20.9 is hereby amended to read as follows:
Notification
20.9 It shall be the duty of the person doing the work
authorized by the permit to notify the Administrative
Authority, orally or in writing, that said work is ready for
inspection.
It shall be the duty of the person doing the work authorized
by the permit to make sure that the work will stand the test
prescribed elsewhere in this Code, before giving the above
notification. Any person who calls for and receives a test
and/or inspection where, in fact, the work is not ready to be
tested and/or inspected shall pay to the Administrative
Authority a fee of $30.00 which must paid prior to any
further call for inspection and/or test.
Addition sections added to Uniform Sign Code:
Add a definition to Chapter 2
Section 203.
Billboard. Means a flat surface, as of a panel, wall or fence on
which bills are posted, a bulletin board or a structure built for
posting or placing advertising, pictures and reading matter.
Add Chapter 15 to read as follows
Section 1501.
Conformance to Zoning Regulations.
Signs may be constructed and maintained in those districts within
the City authorized by the current City of Bremerton Zoning
Ordinance.
Section 1502.
Certificate of Insurance - owner to file when - Amount every
person who owns a billboard(s) shall keep on file with the City
Clerk a Certificate of Insurance for the amount of one million
dollars per occurrence for bodily injury and property damage.
No insurance shall be required for a billboard the solid portion
of whose advertising surface contains less than forty - eight
square feet.
Section 1503.
Zoning Compliance.
Billboards may be constructed and maintained in those districts
within the City authorized by the current City of Bremerton
Zoning Ordinance.
Section 1504.
Construction - Dimension and Open Space Requirements.
.31 -
a. A vertical dimension of a billboard located on the ground and
having a solid face shall not exceed fifteen (15) feet nor
shall the height above the ground exceed thirty (30) feet
Except when determined by the Building Official that the
ground beneath the billboard is below sidewalk grade, in
which case the billboard shall not be higher than thirty (30)
feet above the sidewalk in front of the billboard.
b. Billboards located on the ground shall have an open space of
at least eighteen (18) inches between the lower edge thereof
and the ground. This space may be occupied by lattice work,
provided that the open spaces in said lattice are at least
equal in width to the width of the members of which the
lattice is constructed.
Section 1505.
Obstructing or Projecting Billboards Prohibited When.
a. Billboards placed on walls or roofs of buildings shall be
located so as not to interfere with the use of any fire
escape or standpipe or obstruct necessary windows or
interfere with egress from the building.
No billboards placed against the walls of a building shall
project into any street or alley a greater distance than is
permitted for appendages on buildings.
Section 1506.
Billboards Located Above Building Roofs - Restrictions.
a. No billboard, other than electric sign, shall, if located
above the roof of a building, have an advertising surface
whose vertical dimension exceeds twenty feet, nor shall it be
higher than twenty-five feet above the roof. Electric signs
located above the roof of a building shall not be higher than
seventy-fire feet above said roof.
b. All bents supporting the face of a billboard shall, if
located above the roof of a building, be at least six feet
apart and the bottom of the face shall be at least five feet
above the roof.
c. The advertising surface of such billboard must be no closer
to the front lot line than five feet, or be in line with the
average depth of the front line of the buildings adjacent on
each side.
Section 1507.
Unsafe or defective billboards - Notice to Repair or Remove
Authorized When.
Any billboard which may be or become unsafe or defective, and any
billboard which may be hereafter erected, altered or
reconstructed contrary to the requirements of this chapter, shall
be removed or made to conform to the terms and requirements of
this chapter by the owner thereof or by the owner of the ground
upon which the same is built, upon receipt of notice so to do
from the building inspector. It shall be the duty of the
building inspector to serve notice on any person maintaining any
billboard not in conformity with the provisions of this chapter,
which notice shall require the immediate removal of such
billboard or alteration thereof to conform to the requirements of
this chapter.
Section 1508.
Billposter's Name Required Where.
Every billposter shall cause his name to plainly appear at all
times on every structure, or portion thereof, upon which he
placed advertisements.
a. Definition. "Mobile home" shall mean a factory-assembled
structure having more than three hundred twenty (320) square
feet of gross floor area, capable for using as a dwelling
unit, with its own chassis and capable of being towed on
public highways through the use of its own axles and wheels;
~LQYi~, a mobile home shall not lose its character as a
mobile home by the removal of its wheels and axles or its
placement on a permanent foundation.
b. Pursuant to the authority of RCW 19.27.060(3) mobile homes
are hereby excluded from the provisions of the Uniform
Building Code, Uniform Mechanical Code, Uniform Plumbing Code
(but only as such applies to internal plumbing) and
Regulations for Barrier-Free Facilities. Mobile homes are
not exempted from the remainder of the City of Bremerton
Building and Fire Safety Code.
c. Before any mobile home is located or placed on any lot or
parcel, the person desiring to locate or place the mobile
home must obtain a permit from the Building Official. The
fee for such permit shall be seventy-five dollars ($75.00)
except that it shall be fifty dollars ($50.00) within a
mobile home park.
d. The Building Official shall issue the permit if the mobile
home conforms to the requirements of the City of Bremerton
Zoning Ordinance and meets the mobile home installation
requirements of WAC 296-150B, as not or hereafter amended.
a. Definition. "Factory-built housing" shall mean any structure
designed primarily for human occupancy (other than a mobile
home) the structure or any room of which is either entirely
or substantially prefabricated or assembled at a place other
than the building site.
b. Pursuant to RCW 43.22.450 through RCW 43.22.490 and RCW
19.27.060(3), factory-built housing is hereby excluded from
the provisions of the Uniform Building Code, Uniform
Mechanical Code, Uniform Plumbing Code (but only as such
applies to internal plumbing) and Regulations for Barrier-
Free Facilities. Factory-built housing is not exempted from
the remainder of the City of Bremerton Building and Fire
Safety Code.
c. Each unit of factory-built housing shall have a permanent
foundation. No unit of factory-built housing shall be
located or placed upon any lot or parcel until the following
have occurred:
(1) A person desiring to locate or place a unit of factory-
built housing shall submit to the Building Official a
foundation plan which must be approved by the same. If
the plan is approved the Building Official shall issue a
permit authorizing the placement or location.
(2) A fee in the amount of seventy-five dollars ($75.00)
shall be paid to the Building Department at the time
plans are submitted. This fee shall be used to defray
the inspections set forth in (3) and (4) below.
(3) The Building Department shall ascertain that the unit of
factory-built housing meets the requirements of the City
of Bremerton Zoning Ordinance and that the foundation
forms have been properly set;
(4) Subsequent to the inspection mentioned in (3) above the
Building Official shall, once the foundation has been
poured, the forms removed, and the mud sill in place,
ascertain if the foundation has been properly
constructed.
(5) Those approvals mentioned in Item 3 above have been
obtained.
Unless otherwise more specifically provided, any person,
firm, or corporation violating any of the provisions of the
City of Bremerton Building and Fire Safety Code shall be
deemed guilty of a misdemeanor, and each such person, firm,
or corporation shall be deemed guilty of a separate offense
for each and every day or portion thereof during which any
violation of any of the provisions of the City of Bremerton
Building and Fire Safety Code is committed, continued or
permitted, and upon conviction of any such violation such
person firm or corporation shall be punished by a fine of not
more than five hundred ($500.00) or by imprisonment for not
more than ninety (90) days, or by both such fine and
imprisonment for each violation.
If any section, subsection, sentence, clause or phase of the
City of Bremerton Building and Fire Safety Code or its
application to any person or circumstances, is then invalid,
the remainder of the City of Bremerton Building and Fire
Safety Code, or the applications to other persons or
circumstances, shall not be affected.
Approved by the City Council on the First reading this
~day of __~Q~_. ~.. , 1985.
Passed by the City Council of the City of Bremerton,
Washington, signed by the Mayor and attested by the City Clerk in
authentication of such passage this /~--~ day of
.:~.a~__~ -, 1985.
MORRIE DAWKINS, Mayor
ATTEST:
KATHLEEN L. McCLUSKEY, Clerk
DD:ceu